Study on the Application of an Ultra-High-Frequency Fractal Antenna to Partial Discharge Detection in Switchgears

被引:20
|
作者
Yao, Chenguo [1 ]
Chen, Pan [1 ,2 ]
Huang, Congjian [1 ]
Chen, Yu [1 ]
Qiao, Panpan [1 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400044, Peoples R China
[2] Jiang Bei Power Supply Bur, Chongqing 401147, Peoples R China
来源
SENSORS | 2013年 / 13卷 / 12期
基金
中国国家自然科学基金;
关键词
ELECTROMAGNETIC-WAVE; POWER TRANSFORMERS; GIS; SIMULATION; PROPAGATION; FDTD;
D O I
10.3390/s131217362
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
The ultra-high-frequency (UHF) method is used to analyze the insulation condition of electric equipment by detecting the UHF electromagnetic (EM) waves excited by partial discharge (PD). As part of the UHF detection system, the UHF sensor determines the detection system performance in signal extraction and recognition. In this paper, a UHF antenna sensor with the fractal structure for PD detection in switchgears was designed by means of modeling, simulation and optimization. This sensor, with a flat-plate structure, had two resonance frequencies of 583 MHz and 732 MHz. In the laboratory, four kinds of insulation defect models were positioned in the testing switchgear for typical PD tests. The results show that the sensor could reproduce the electromagnetic waves well. Furthermore, to optimize the installation position of the inner sensor for achieving best detection performance, the precise simulation model of switchgear was developed to study the propagation characteristics of UHF signals in switchgear by finite-difference time-domain (FDTD) method. According to the results of simulation and verification test, the sensor should be positioned at the right side of bottom plate in the front cabinet. This research established the foundation for the further study on the application of UHF technique in switchgear PD online detection. © 2013 by the authors; licensee MDPI; Basel; Switzerland.
引用
收藏
页码:17362 / 17378
页数:17
相关论文
共 50 条
  • [1] Application of ultra-high-frequency partial discharge detection in power transformers
    Zhao, Xiao-Hui
    Lu, Xiu-Li
    Yang, Jing-Gang
    Yuan, Peng
    Li, Yan-Ming
    [J]. Gaodianya Jishu/High Voltage Engineering, 2007, 33 (08): : 111 - 114
  • [2] Development of smart sensor for ultra-high-frequency partial discharge detection
    State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing
    400030, China
    不详
    650217, China
    不详
    330096, China
    [J]. Gaodianya Jishu, 12 (3944-3951):
  • [3] Partial discharge detection in GIS using ultra-high-frequency method
    Sun, Yanzhou
    Wang, Xudong
    Yin, Hua
    Yu, Fashan
    [J]. ICPASM 2005: PROCEEDINGS OF THE 8TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 2006, : 695 - +
  • [4] Ultra-high-frequency Partial Discharge Detection with Scanning and Comparing Method
    Yan, Jinping
    Du, Lin
    Li, Jian
    Wang, Youyuan
    [J]. 2014 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2014,
  • [5] The application of ultra-high-frequency partial discharge measurements to gas-insulated substations
    Kurrer, R
    Feser, K
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (03) : 777 - 782
  • [6] Partial discharge detection for GIS using narrow band ultra-high-frequency (UHF) method
    Sun, YZ
    Yin, H
    Zhang, QG
    Yu, FS
    Wang, H
    Qiu, YC
    [J]. Proceedings of the 2005 International Symposium on Electrical Insulating Materials, Vols, 1-3, 2005, : 748 - 751
  • [7] An UWB printed antenna for partial discharge UHF detection in high voltage switchgears
    [J]. Yang, Qi (yangqi_cqu@163.com), 1600, Electromagnetics Academy (69):
  • [8] The Application of High Frequency and Ultra High Frequency Partial Discharge Detection to Gas Insulated Switchgear
    Lu, Yao
    Qiu, Zhibin
    Liao, Caibo
    Li, Tonghongfei
    Wu, Zijian
    Hu, Yong
    [J]. 2022 4TH ASIA ENERGY AND ELECTRICAL ENGINEERING SYMPOSIUM (AEEES 2022), 2022, : 712 - 716
  • [9] Experimental Investigation of Partial Discharge Detection in Medium-voltage Switchgear Based on Ultra-High-Frequency Sensor
    Wang, Liuhuo
    Ning, Wenjun
    Wang, Lijun
    Lu, Hong
    Wang, Haijing
    Jia, Shenli
    Wu, Ji
    [J]. 2013 2ND INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), 2013,
  • [10] An Intelligent Sensor for the Ultra-High-Frequency Partial Discharge Online Monitoring of Power Transformers
    Li, Jian
    Li, Xudong
    Du, Lin
    Cao, Min
    Qian, Guochao
    [J]. ENERGIES, 2016, 9 (05)