Development of a membrane integrity monitoring strategy for the UF/RO Heemskerk drinking water treatment plant

被引:15
|
作者
Kruithof, JC [1 ]
Kamp, PC [1 ]
Folmer, HC [1 ]
Nederlof, MM [1 ]
van Hoof, SCJM [1 ]
机构
[1] NV PWN Water Supply Co N Holland, NL-1990 AC Velserbroek, Netherlands
关键词
conductivity measurement; integrity; particle counting; SIM-system; sulfate monitoring; vacuum testing;
D O I
10.2166/ws.2001.0122
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
At the Heemskerk water treatment plant of N.V. PWN Water Supply Company North Holland the first full scale integrated membrane system in the Netherlands is realized. The 20 Mm(3)/year (15 MGD) ultrafiltration (UF)/reverse osmosis (RO) plant servicing Ussel Lake water has been in operation since the second half of 1999. Disinfection is a major objective of the direct surface water treatment plant without chemical disinfection. After UF indicator organisms such as E. coli and Clostridia spores were absent. Integer UF membranes removed MS-2 phage spikes completely (>5.4 log), severely compromised membranes removed 2.7 log only. RO showed a high although incomplete removal of MS-2 phages (up to 4.8 log), Therefore integrity monitoring is a critical issue. Before installation, vacuum testing was applied with a criterion of 10 kPa/min. Many standard modules failed to pass the test. During operation UF is monitored by 1 mum particle counting with 0.05 mum particle counting as a quality control. A 3 log removal can be established. At this moment for RO conductivity measurement is applied enabling a 2 log removal monitoring. Short term monitoring of conductivity will be replaced by sulfate, increasing the monitoring range by 1 log unit. The total monitoring range of 5-6 log units easily satisfies the maximum disinfection requirement for the membrane steps for viruses of 3.6 log. To determine a wider range of disinfection requirements PWN together with Norit Membrane Technology developed the Spiked Integrity Monitoring (SIM(R)) System. Spiking with 14000 PAC particles/ml combined with 1 pm particle counting increased the potential for log removal monitoring of LIF to 5.8 log units. Additionally PAC particle spiking increased the potential to detect UF fiber compromising, During the first 200 days of full scale operation, system performance is excellent. Membrane integrity control is very satisfactory and SIM(R)-System integrity control has proved to be a valid technique to establish a broader range of required inactivation capacities.
引用
收藏
页码:261 / 271
页数:11
相关论文
共 50 条
  • [1] UF/RO treatment plant Heemskerk: from challenge to full scale application
    Kamp, PC
    Kruithof, JC
    Folmer, HC
    [J]. DESALINATION, 2000, 131 (1-3) : 27 - 35
  • [2] The effects of coagulation with MF/UF membrane filtration in drinking water treatment
    Jang, H. N.
    Lee, D. S.
    Ko, S. O.
    [J]. DESALINATION AND WATER TREATMENT, 2010, 19 (1-3) : 138 - 145
  • [3] Factors influencing critical flux of UF membrane in drinking water treatment
    Qi, Lu
    Zheng, Xiang
    Li, Guibai
    [J]. DESALINATION AND WATER TREATMENT, 2015, 56 (12) : 3305 - 3312
  • [4] Behavior of pharmaceuticals and drugs of abuse in a drinking water treatment plant (DWTP) using combined conventional and ultrafiltration and reverse osmosis (UF/RO) treatments
    Rosa Boleda, Ma
    Teresa Galceran, Ma
    Ventura, Francesc
    [J]. ENVIRONMENTAL POLLUTION, 2011, 159 (06) : 1584 - 1591
  • [5] Ceramic Filter for Small System Drinking Water Treatment: Evaluation of Membrane Pore Size and Importance of Integrity Monitoring
    Muhammad, Nur
    Sinha, Rajib
    Krishnan, E. Radha
    Patterson, Craig L.
    [J]. JOURNAL OF ENVIRONMENTAL ENGINEERING-ASCE, 2009, 135 (11): : 1181 - 1191
  • [6] Development of nanocomposite membrane process for drinking water treatment
    Wang, Panpan
    Song, Dan
    Sun, Zhiqiang
    Ru, Lin
    Wang, Haidong
    Wang, Feihong
    Jiang, Haicheng
    Ma, Jun
    [J]. ABSTRACTS OF PAPERS OF THE AMERICAN CHEMICAL SOCIETY, 2017, 253
  • [7] The Development of Household Membrane Filters for Drinking Water Treatment
    Li, Xunchao
    Li, Cong
    [J]. ENERGY ENGINEERING AND ENVIRONMENT ENGINEERING, 2014, 535 : 446 - 450
  • [8] Grey water treatment with spiral wound UF and RO membranes
    Reang, Sukanta
    Nath, Harjeet
    [J]. MATERIALS TODAY-PROCEEDINGS, 2021, 46 : 6253 - 6259
  • [9] Low-pressure membrane integrity tests for drinking water treatment: A review
    Guo, H.
    Wyart, Y.
    Perot, J.
    Nauleau, F.
    Moulin, P.
    [J]. WATER RESEARCH, 2010, 44 (01) : 41 - 57
  • [10] Iron and manganese removal and membrane fouling during UF in conjunction with prechlorination for drinking water treatment
    Choo, KH
    Lee, H
    Choi, SJ
    [J]. JOURNAL OF MEMBRANE SCIENCE, 2005, 267 (1-2) : 18 - 26