Dielectric properties of mixed mineral and synthetic ester oil

被引:7
|
作者
Mahidhar, Gorla Durga Pawan [1 ]
Somasundaram Karthikeyan, Amizhtan [1 ]
Sarathi, Ramanujam [1 ]
Taylor, Nathaniel [2 ]
Edin, Hans [2 ]
机构
[1] Indian Inst Technol Madras, Dept Elect Engn, Chennai 600036, TN, India
[2] KTH Royal Inst Technol, Sch Elect Engn & Comp Sci, SE-10044 Stockholm, Sweden
关键词
corona; power transformer insulation; insulation testing; partial discharges; electric breakdown; transformer oil; ultraviolet spectroscopy; frequency-domain analysis; transformer insulation; continuous breakdown studies; AC voltage; frequency-domain spectroscopy studies; dielectric properties; synthetic ester oil; corona inception voltage; ultra-high frequency technique; statistical study; breakdown voltage; standard lightning impulse voltages; mixed mineral oil; UHF technique; interfacial tension; flash point; ionic mobility; UV-vis spectroscopy; liquid chemical stability; polarisation current; UHF signal energy analysis; phase-resolved partial discharge analysis; DC voltages; NATURAL ESTER; UHF SENSORS; PART; VOLTAGE; INSULATION; TRANSFORMERS; STREAMERS; BREAKDOWN; IEC60270; LIQUIDS;
D O I
10.1049/iet-smt.2019.0227
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The dielectric properties of 20% synthetic ester oil mixed with mineral oil were studied for its potential applications as an insulator in transformers. The corona inception voltage of mixed oil under AC and DC voltages was measured by the ultra-high frequency (UHF) technique. A statistical study of the breakdown voltage of mixed oil under AC, DC and standard lightning impulse voltages was carried out to obtain a database which would be useful for designing transformer insulation. Further, the mixture was subjected to continuous breakdown studies under AC voltage with lightning impulse voltages, at regular intervals and characterised through measurement of interfacial tension, flash point, ionic mobility as well as UV-vis spectroscopy and frequency-domain spectroscopy studies to understand the liquid's chemical stability. The results of the study have shown that the mixture was stable even after several breakdowns. The ionic mobility and polarisation current have increased, indicating higher losses in the oil. UHF signal energy analysis and phase-resolved partial discharge analysis have revealed a reduction in discharge activity with mixed oils.
引用
收藏
页码:704 / 714
页数:11
相关论文
共 50 条
  • [41] Influence of Moisture and Ageing on Dielectric Response of Ester and Mineral Oil Impregnated Pressboard Insulation
    Bandara, Kapila
    Saha, Tapan K.
    Ekanayake, Chandima
    [J]. 2015 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2015,
  • [42] Partial Discharges with Fast Switched Voltage on Impregnated Pressboard in a Mineral Oil and a Synthetic Ester
    Aakre, Torstein Grav
    Fagerli, Brynjar
    Lundgaard, Lars E.
    Niayesh, Kaveh
    [J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2024, 31 (05) : 2469 - 2476
  • [43] Streamer Characteristic and Breakdown in a Mineral Oil and a Synthetic Ester Liquid under DC Voltage
    Xiang, J.
    Liu, Q.
    Wang, Z. D.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (05) : 1636 - 1643
  • [45] Study of frequency domain dielectric properties of vegetable oil and mineral oil transformer
    Li, Linduo
    Ren, Qiaolin
    Xiao, Sa
    Yang, Wenyan
    Xiong, Wei
    Fu, Boqiao
    [J]. JOURNAL OF ENGINEERING-JOE, 2019, (16): : 1599 - 1601
  • [46] Aging Properties of Monoesters and Comparison with Tri-ester and Mineral Oil
    Rajab, A.
    Tsuchie, M.
    Kozako, M.
    Hikita, M.
    Suzuki, Takashi
    [J]. 2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [47] Dielectric Properties of Sunflower, Rapeseed and Commonly Used Mineral Oil
    Ulrych, Jiri
    Mentlik, Vaclav
    [J]. 2016 17TH INTERNATIONAL SCIENTIFIC CONFERENCE ON ELECTRIC POWER ENGINEERING (EPE), 2016, : 347 - 350
  • [48] Dielectric Properties of Natural Ester Mixed with Nanoparticles under Thermal Stress
    Kittikhuntharadol, Yannaphol
    Vittayakorn, Wanwilai
    Pattanadech, Norasage
    [J]. 2020 8TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD 2020), 2020, : 350 - 353
  • [49] Influence of Conductive Nanoparticles on the Breakdown Voltage of Mineral Oil, Synthetic and Natural Ester Oil-based Nanofluids
    Khaled, Usama
    Beroual, Abderrahmane
    [J]. 2019 IEEE 20TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2019,
  • [50] Effect of dielectric strength of mineral oil on mixing with a natural ester oil as a polar contaminant under AC stress
    Uppal, Anjali
    Agarwal, Ritika
    Sharma, Pavitra
    Velandy, Jeyabalan
    Narasimhan, C. S.
    Morde, Girish A.
    [J]. 4TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON 2019), 2019,