Prototype energy models for data centers

被引:33
|
作者
Sun, Kaiyu [1 ]
Luo, Na [1 ]
Luo, Xuan [1 ]
Hong, Tianzhen [1 ]
机构
[1] Lawrence Berkeley Natl Lab, Bldg Technol & Urban Syst Div, One Cyclotron Rd, Berkeley, CA 94720 USA
关键词
Data center; EnergyPlus; Energy efficiency; Prototype energy model; Approach temperature; OpenStudio; AIR-DISTRIBUTION SYSTEMS; BUILDING ENERGY; PERFORMANCE; SIMULATION; DENSITY; FLOW; MANAGEMENT;
D O I
10.1016/j.enbuild.2020.110603
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Data centers in the United States consume about two percent of the nation's electricity. Because heat gains from IT equipment drive cooling demand, data centers offer unique opportunities for energy savings. However, no prototype energy model for data centers is available in the suite of existing U.S. Department of Energy's Commercial Prototype Building Models. This study presented the development of two new data center prototype models and their implementation in OpenStudio and EnergyPlus. The small-size data center model represents a computer room in a building served by computer room air conditioners (CRACs); while the large-sized model represents stand-alone data centers served by computer room air handlers (CRAHs) with a central chiller plant. For each data center model, two levels of IT equipment (ITE) load density were considered, to cover the wide range of IT power density of data centers: 40 and 100 W/ft(2) (430 and 1076 W/m(2)) for the computer room, and 100 and 500 W/ft(2) (1076 and 5382 W/m(2)) for the stand-alone data center. All other assumptions, such as building envelope, lighting, HVAC efficiencies and schedules, were based on the minimal requirements of ASHRAE Standard 90.1 at various vintages. We introduced a novel concept of supply and return air approach temperatures to capture the essential effects of non-uniform airflow and temperature distribution in data centers. The approach temperatures were pre-computed by computational fluid dynamics (CFD) simulations for various configurations of ITE loads and airflow containment management in data centers. A new feature was developed in EnergyPlus to implement the approach temperature method. A case study was conducted to demonstrate the use of the data center models. The two data center models cover all U.S. climate zones and can be used to evaluate energy saving measures for data centers, as well as to support development of data center energy efficiency codes and standards. (C) 2020 Elsevier B.V. All rights reserved.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] Development of a New Prototype Energy Model for Data Centers
    Sun, Kaiyu
    Hong, Tianzhen
    Luo, Xuan
    ASHRAE TRANSACTIONS 2019, VOL 125, PT 2, 2019, 125 : 137 - 144
  • [2] Energy Models driven Green Routing for Data Centers
    Saha, Shivashis
    Deogun, Jitender S.
    Xu, Lisong
    2012 IEEE GLOBAL COMMUNICATIONS CONFERENCE (GLOBECOM), 2012,
  • [3] Energy Saving in Data Centers
    Bein, Wolfgang
    ELECTRONICS, 2018, 7 (01):
  • [4] ENERGY STANDARD FOR DATA CENTERS
    Rodgers, Terry L. .
    Mcfarlane, Robert E.
    Prisco, Joseph F.
    ASHRAE JOURNAL, 2023, 65
  • [5] On Energy Conservation in Data Centers
    Albers, Susanne
    PROCEEDINGS OF THE 29TH ACM SYMPOSIUM ON PARALLELISM IN ALGORITHMS AND ARCHITECTURES (SPAA'17), 2017, : 35 - 44
  • [6] On Energy Conservation in Data Centers
    Albers, Susanne
    ACM TRANSACTIONS ON PARALLEL COMPUTING, 2019, 6 (03)
  • [7] Machine learning assisted development of IT equipment compact models for data centers energy planning
    Manaserh, Yaman M.
    Tradat, Mohammad I.
    Bani-Hani, Dana
    Alfallah, Aseel
    Sammakia, Bahgat G.
    Nemati, Kourosh
    Seymour, Mark J.
    APPLIED ENERGY, 2022, 305
  • [8] BINARY PROGRAMMING MODELS FOR ENERGY-EFFICIENT VIRTUAL MACHINES PLACEMENT IN DATA CENTERS
    Radulescu , Delia Mihaela
    Radulescu, Marius
    Radulescu, Constanta Zoie
    Lazaroiu, Gheorghe
    UNIVERSITY POLITEHNICA OF BUCHAREST SCIENTIFIC BULLETIN SERIES C-ELECTRICAL ENGINEERING AND COMPUTER SCIENCE, 2024, 86 (03): : 335 - 346
  • [9] Energy-aware workload management models for operation cost reduction in data centers
    Bodenstein, Christian
    Schryen, Guido
    Neumann, Dirk
    EUROPEAN JOURNAL OF OPERATIONAL RESEARCH, 2012, 222 (01) : 157 - 167
  • [10] Energy efficiency in data centers - Reply
    Schmidt, Roger
    ASHRAE JOURNAL, 2008, 50 (02) : 10 - 10