Inversion of Oil-Immersed Paper Resistivity in Transformer Based on Dielectric Loss Factor

被引:4
|
作者
Ruan, Jiangjun [1 ]
Xie, Yiming [1 ]
Jin, Shuo [2 ]
Shi, Yu [3 ]
Tian, Yu [1 ]
Deng, Yongqing [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan 430072, Hubei, Peoples R China
[2] Hubei Univ Technol, Sch Elect & Elect Engn, Wuhan 430068, Hubei, Peoples R China
[3] Anhui Univ Sci & Technol, Sch Elect & Informat Engn, Huainan 232001, Peoples R China
来源
IEEE ACCESS | 2019年 / 7卷
关键词
Inversion; oil-immersed paper resistivity; dielectric loss factor; Newton-Raphson method; transformer; POWER TRANSFORMERS; FREQUENCY-DOMAIN; INSULATION; DIAGNOSTICS; REPLACEMENT; LIFE;
D O I
10.1109/ACCESS.2019.2907288
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The aging of the transformer oil-paper insulation distributes spatially, which results in changes in paper resistivity in different regions. This paper establishes an iterative inversion algorithm using the finite element method to calculate the oil-immersed paper resistivity in different regions of a transformer. This algorithm sets the transformer dielectric loss factor tan delta at low frequency, the dielectric parameters of the transformer oil as inputs and the oil-immersed paper resistivity as output. The resistivity obtained from inversion can be used as a reference to access the insulation state of the oil-paper insulation. This paper aims at achieving the nondestructive detection of the partial state of the oil-paper insulation.
引用
收藏
页码:44050 / 44058
页数:9
相关论文
共 50 条
  • [21] Effect of melamine modified cellulose nanocrystals on the performance of oil-immersed transformer insulation paper
    QiJie Chen
    MeiCun Kang
    QiongHua Xie
    JianHui Wang
    [J]. Cellulose, 2020, 27 : 7621 - 7636
  • [22] Fault diagnosis of oil-immersed transformer based on MGTO-BSCN
    Yi, Lingzhi
    Long, Jiao
    Huang, Jianxiong
    Xu, Xunjian
    Feng, Wenqing
    She, Haixiang
    [J]. JOURNAL OF INTELLIGENT & FUZZY SYSTEMS, 2023, 44 (04) : 6021 - 6034
  • [23] Generation and prevention of latent oil leak in oil-immersed transformer
    Chen, Xinhui
    Zhou, Wenjie
    [J]. Bianyaqi/Transformer, 2000, 37 (02): : 23 - 25
  • [24] RAPID MEASUREMENT OF DETERIORATION OF OIL-IMMERSED PAPER
    HINO, T
    SUGANUMA, T
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1972, EI 7 (03): : 122 - &
  • [25] DIELECTRIC STRENGTH OF OIL-IMMERSED TRANSFORMER INSULATION WITH SUPERIMPOSED AC AND LIGHTNING IMPULSE VOLTAGE
    KAMATA, Y
    ENDOH, K
    FURUKAWA, S
    ENDOH, F
    NONOMURA, K
    IWATA, Y
    HORIUCHI, S
    TAKASU, N
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1990, 25 (04): : 683 - 687
  • [26] Fault Diagnosis for Oil-immersed Transformer Based on Missing Data Imputation
    Liao, Caibo
    Yang, Jinxin
    Qiu, Zhibin
    Hu, Xiong
    Jiang, Zihao
    Li, Xin
    [J]. Gaodianya Jishu/High Voltage Engineering, 2024, 50 (09): : 4091 - 4100
  • [27] Loss-of-Life Analyses Based on Modified Arrhenius and Relative Aging Rate for Non-Thermally Upgraded Paper in Oil-Immersed Transformer
    Saleh, Najiyah
    Azis, Norhafiz
    Jasni, Jasronita
    Kadir, Mohd Zainal Abidin Ab
    Talib, Mohd Aizam
    [J]. PERTANIKA JOURNAL OF SCIENCE AND TECHNOLOGY, 2024, 32 (02): : 647 - 667
  • [28] Study on the deformation of the oil-immersed transformer tank by FEA
    Zhang, Jianhua
    Sun, Lingyu
    Zhang, Xiaojun
    Li, Jiapeng
    [J]. EQUIPMENT MANUFACTURING TECHNOLOGY, 2012, 422 : 51 - +
  • [29] Increase of Static Electrification in an Aged Oil-Immersed Transformer
    Kobayashi, Takayuki
    Yajima, Kouji
    Yamada, Shin
    Amimoto, Tsuyoshi
    Hosokawa, Noboru
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 2009, 167 (03) : 10 - 19
  • [30] Study on Improving the Dielectric Properties of Oil-immersed Paper by Doping Nano-cellulose
    Kong, Xiaoxiao
    Du, Boxue
    Jiang, Jinpeng
    Tao, Wuye
    [J]. Gaodianya Jishu/High Voltage Engineering, 2022, 48 (05): : 2020 - 2027