Steady state and transient voltage control on long EHV transmission lines

被引:0
|
作者
de Carvalho, MA [1 ]
da Fonte, LAM [1 ]
机构
[1] Univ Fed Pernambuco, Dept Engn Eletr & Sistemas Potencia, BR-50739 Recife, PE, Brazil
关键词
linear reactor; line energization; line rejection; overvoltages; reactive compensation; reactive power; saturated reactor; voltage control;
D O I
暂无
中图分类号
TP3 [计算技术、计算机技术];
学科分类号
0812 ;
摘要
This paper deals with the replacement of linear reactors, which are often used for reactive compensation on EHV long transmission lines by naturally saturated reactors, Besides a steady-state, smoother voltage control that such a change brings, the chief concern is to release the transmission line's entire capacity to load supply. EMTP-ATP simulation results for a specific application of naturally saturated reactors at CHESF's 500 W power grid are shown in order to justify this proposal. The reactor's mathematical model is also described in this paper as well as the methodology used to determine the set of the model's parameters.
引用
收藏
页码:409 / 414
页数:6
相关论文
共 50 条
  • [1] TRANSIENT ELECTROSTATIC INDUCTION BY EHV TRANSMISSION LINES
    COMSA, RP
    YU, LYM
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (12): : 1783 - &
  • [2] Steady-state Operation of Very Long EHV AC Cable Lines
    Colla, L.
    Gatta, F. M.
    Geri, A.
    Lauria, S.
    Maccioni, M.
    [J]. 2009 IEEE BUCHAREST POWERTECH, VOLS 1-5, 2009, : 1569 - +
  • [3] A new directional relay for the protection of EHV transmission lines based on the detection of transient voltage signals
    Lyonette, DRM
    Bo, ZQ
    Weller, G
    Jiang, F
    [J]. 2000 IEEE POWER ENGINEERING SOCIETY WINTER MEETING - VOLS 1-4, CONFERENCE PROCEEDINGS, 2000, : 1827 - 1831
  • [4] ELECTROSTATIC VOLTAGE INDUCED BELOW EHV TRANSMISSION LINES
    HIDAKA, K
    TSURUMI, S
    KITANI, Y
    YOKOTA, S
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 1967, 87 (03) : 48 - &
  • [5] Steady state and transient ampacities of gas-insulated transmission lines
    Eteiba, MB
    [J]. 11TH IEEE MEDITERRANEAN ELECTROTECHNICAL CONFERENCE, PROCEEDINGS, 2002, : 424 - 428
  • [6] Steady State versus Transient Signal for Fault Location in Transmission Lines
    Hashim, M. N.
    Osman, M. K.
    Ibrahim, M. N.
    Abidin, A. F.
    [J]. 1ST INTERNATIONAL CONFERENCE ON GREEN AND SUSTAINABLE COMPUTING (ICOGES) 2017, 2018, 1019
  • [7] FACTS Controllers to Improve Voltage Profile and Enhancement of Line Loadability in EHV Long Transmission Lines
    Shankaralingappa, C. B.
    Jangamashetti, Suresh. H.
    [J]. 2008 JOINT INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON) AND IEEE POWER INDIA CONFERENCE, VOLS 1 AND 2, 2008, : 82 - +
  • [8] FAULT LOCATOR FOR LONG EHV TRANSMISSION-LINES
    SANT, MT
    PAITHANKAR, YG
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 1983, 6 (04) : 305 - 310
  • [9] Voltage instability and collapse of series compensated EHV transmission lines
    Tripathy, SC
    Viswanathan, B
    Heydeman, J
    [J]. ELECTRIC MACHINES AND POWER SYSTEMS, 1998, 26 (06): : 601 - 615
  • [10] Evaluation of Steady State Voltage and Current per Phase of Power Transmission Lines
    Couto, V. F.
    Cabral, S. H. L.
    [J]. IEEE LATIN AMERICA TRANSACTIONS, 2015, 13 (10) : 3317 - 3323