Influence on Formation of Methanol and Ethanol in Oil-Filled Transformers Under Accelerated Thermal Aging

被引:0
|
作者
Homeier, K. [1 ]
Imani, M. [1 ]
Muenster, T. [1 ]
Kinkeldey, T. [1 ]
Werle, P. [1 ]
Philipp, D. [2 ]
机构
[1] Leibniz Univ Hannover, Inst Elect Power Syst, Schering Inst, Div High Voltage Engn & Asset Management, Hannover, Germany
[2] Analysen Serv GmbH, Environm & Oil Lab, Leipzig, Germany
关键词
Methanol; Ethanol; Thermal aging; Cellulose deterioration; DP value; PART; 2; PAPER; DEGRADATION;
D O I
10.1007/978-3-030-31676-1_90
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This contribution investigates the suitability of short-chain alcohols for estimating the condition of a cellulose insulation in power transformers. To model an accelerated thermal aging of a transformer, strips of insulation paper impregnated with different insulation liquids were kept in a glass vessel, filled with the dielectric liquid and catalyzer inclusions, in a heating chamber. After oil sampling at predefined intervals, the concentrations of furanic compounds, the degree of polymerization (DP) value and the concentrations of methanol and ethanol in the insulation liquid were measured. Three different types of insulation liquids were utilized, such as the well-known uninhibited and inhibited mineral oil as well as a new inhibited insulation liquid with different oil components, inhibitor content and manufacturing process. These insulation liquids were investigated to obtain their various aging behavior regarding the generation of 2FAL and short-chain alcohols by thermal accelerated stress.
引用
收藏
页码:958 / 968
页数:11
相关论文
共 50 条
  • [1] Possible Indicators of Aging in Oil-Filled Transformers Part 1: Measurements
    Birlasekaran, S.
    Ledwich, G.
    IEEE ELECTRICAL INSULATION MAGAZINE, 2010, 26 (01) : 26 - 32
  • [2] On-line diagnostics of oil-filled transformers
    Varl, A
    PROCEEDINGS OF THE 2002 IEEE 14TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS, 2002, : 253 - 257
  • [3] AGING OF OIL-FILLED CABLE DIELECTRICS
    KAGAYA, S
    YAMAMOTO, T
    INOHANA, A
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1970, PA89 (07): : 1420 - &
  • [4] Rapid Assessment of the Operational Status of the Oil-filled Transformers
    Levin, Vladimir
    Kerimkulov, Nurzhan
    2016 11TH INTERNATIONAL FORUM ON STRATEGIC TECHNOLOGY (IFOST), PTS 1 AND 2, 2016,
  • [5] Model for Predictive Control of Temperature in Oil-filled Transformers
    Mastorakis, Nikos E.
    Bulucea, Cornelia Aida
    Manolea, Gheorghe
    Popescu, Marius Constantin
    Perescu-Popescu, Liliana
    PROCEEDINGS OF THE 11TH WSEAS INTERNATIONAL CONFERENCE ON AUTOMATIC CONTROL, MODELLING AND SIMULATION: CONTROLLING, MODELLING AND SIMULATION, 2009, : 157 - +
  • [6] DE-SLUDGING ENERGIZED OIL-FILLED TRANSFORMERS
    PARRISH, RH
    KELLY, JJ
    PLANT ENGINEERING, 1979, 33 (20) : 101 - 105
  • [7] Improvement for diagnosing internal abnormalities in oil-filled transformers
    Zama, Shigeyuki
    Kobayashi, Takayuki
    Ikeda, Jiro
    Eto, Atsushi
    PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 941 - 944
  • [8] Application of common transformers faults diagnosis methods on biodegradable oil-filled transformers
    N. A. Muhamad
    B. T. Phung
    T. R. Blackburn
    Electrical Engineering, 2012, 94 : 207 - 216
  • [9] Application of common transformers faults diagnosis methods on biodegradable oil-filled transformers
    Muhamad, N. A.
    Phung, B. T.
    Blackburn, T. R.
    ELECTRICAL ENGINEERING, 2012, 94 (04) : 207 - 216
  • [10] PARTICLE CONTAMINATION LEVELS IN OIL-FILLED LARGE POWER TRANSFORMERS
    OOMMEN, TV
    PETRIE, EM
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (05): : 1459 - 1465