Development and experimental validation of a high-temperature heat pump for heat recovery and building heating

被引:13
|
作者
Wang Kai [1 ]
Cao Feng [1 ]
Xing Ziwen [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China
关键词
High-temperature heat pump; Geothermal water; Heat recovery; Building heating; Oil cooling; Cooled oil temperature;
D O I
10.1016/j.enbuild.2009.02.004
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The performance of a high-temperature heat pump unit using geothermal water for heat recovery in buildings is experimentally evaluated. The unit consists of a twin-screw refrigeration compressor, a condenser, an evaporator and an oil cooling system. The effect of the cooled oil temperature on the performance of the heat pump unit is experimentally investigated. Results show that the unit stably produces outlet hot water at a constant temperature of 85 degrees C and performs well in a wide range of high-temperature conditions with a high energy efficiency ratio. The results also indicate that the key to improving the performance of a high-temperature heat pump unit often depend on the selection of proper cooled oil temperature. The optimum cooled oil temperature is 50-65 degrees C when the condensing temperature is above 70 degrees C. At these temperatures, the oil cooling system can increase the energy efficiency ratio of the heat pump by 6.3%. (c) 2009 Elsevier B.V. All rights reserved.
引用
下载
收藏
页码:732 / 737
页数:6
相关论文
共 50 条
  • [1] Development and experimental validation of high temperature heat pump for heat recovery
    School of Energy and Power Engineering, Xi'an Jiaotong University, Xi'an 710049, China
    Hsi An Chiao Tung Ta Hsueh, 2008, 10 (1309-1312):
  • [2] Investigation of a High-Temperature Heat Pump for Heating Purposes
    Bellos, Evangelos
    Tsimpoukis, Dimitrios
    Lykas, Panagiotis
    Kitsopoulou, Angeliki
    Korres, Dimitrios N.
    Vrachopoulos, Michail Gr.
    Tzivanidis, Christos
    APPLIED SCIENCES-BASEL, 2023, 13 (04):
  • [3] The development of a hydrocarbon high temperature heat pump for waste heat recovery
    Bamigbetan, O.
    Eikevik, T. M.
    Neksa, P.
    Bantle, M.
    Schlemminger, C.
    ENERGY, 2019, 173 : 1141 - 1153
  • [4] HIGH-TEMPERATURE HEAT PUMP INTEGRATION INTO DISTRICT HEATING SYSTEM
    Jakovleva, Ludmila
    20TH INTERNATIONAL SCIENTIFIC CONFERENCE ENGINEERING FOR RURAL DEVELOPMENT, 2021, : 1312 - 1316
  • [5] The potential of wastewater heat and exergy: Decentralized high-temperature recovery with a heat pump
    Meggers, Forrest
    Leibundgut, Hansjurg
    ENERGY AND BUILDINGS, 2011, 43 (04) : 879 - 886
  • [6] Development and field test of a high-temperature heat pump used in crude oil heating
    He, Yongning
    Cao, Feng
    Jin, Lei
    Yang, Dongfang
    Wang, Xiaolin
    Xing, Ziwen
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART E-JOURNAL OF PROCESS MECHANICAL ENGINEERING, 2017, 231 (03) : 392 - 404
  • [7] Experimental exergy and energy analysis of a novel high-temperature heat pump with scroll compressor for waste heat recovery
    Mateu-Royo, Carlos
    Navarro-Esbri, Joaquin
    Mota-Babiloni, Adrian
    Moles, Francisco
    Amat-Albuixech, Marta
    APPLIED ENERGY, 2019, 253
  • [8] A high-temperature hybrid absorption-compression heat pump for waste heat recovery
    Liu, Changchun
    Jiang, Yingchun
    Han, Wei
    Kang, Qilan
    ENERGY CONVERSION AND MANAGEMENT, 2018, 172 : 391 - 401
  • [9] HIGH-TEMPERATURE HEAT-PUMP
    PITT, R
    BRENNSTOFF-WARME-KRAFT, 1983, 35 (1-2): : 30 - 35
  • [10] Travelling-wave thermoacoustic high-temperature heat pump for industrial waste heat recovery
    Yang, Zhao
    Zhuo, Yang
    Ercang, Luo
    Yuan, Zhou
    ENERGY, 2014, 77 : 397 - 402