An air cooled tube-fin evaporator model for an expansion valve control law

被引:25
|
作者
Aprea, C
Renno, C
机构
[1] Univ Salerno, Dept Mech Engn, I-84084 Salerno, Italy
[2] Univ Naples Federico II, Fac Engn, DETEC, I-80125 Naples, Italy
关键词
evaporator models; control devices; heat transfer; phase transition; numerical methods; nonlinear differential systems;
D O I
10.1016/S0895-7177(99)00170-3
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
For control purposes, a mathematical model of a tube-fin evaporator of a vapour compression plant running with R22 is analyzed. The refrigerant behavior in an evaporating region is described by a homogeneous model. The balance equations, together with the constitutive equations, determine a differential system which makes explicit the mechanism of dynamic behavior. At first, the numerical solution of the steady state is obtained, both in evaporating and superheated regions. Moreover, the numerical analysis allows us to evaluate the transition phase and to locate the interface. Subsequently, various analytical aspects are discussed. For the nonlinear two-phase flow, the dependence of the solution on the boundary data is estimated by means of a qualitative analysis. Then, a linearized model for the single-phase how is deduced and solved explicitly. The analytical solution is compared with the numerical results and the degree of superheating is estimated in terms of the model parameters. (C) 1999 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:135 / 146
页数:12
相关论文
共 50 条
  • [41] Effect of water maldistribution in multi-circuit evaporator on superheat control dynamics of thermostatic-expansion-valve refrigeration system
    Zhao, Rijing
    Huang, Dong
    Leng, Yongqiang
    Zhang, Zhenya
    APPLIED THERMAL ENGINEERING, 2017, 115 : 955 - 961
  • [42] Adaptive-model predictive control of electronic expansion valves with adjustable setpoint for evaporator superheat minimization
    Tesfay, Mehari
    Alsaleem, Fadi
    Arunasalam, Parthiban
    Rao, Arvind
    BUILDING AND ENVIRONMENT, 2018, 133 : 151 - 160
  • [43] A dynamic mathematical model of a direct expansion (DX) water-cooled air-conditioning plant
    Deng, SM
    BUILDING AND ENVIRONMENT, 2000, 35 (07) : 603 - 613
  • [44] Research on the control laws of the electronic expansion valve for an air source heat pump water heater
    Jiang, Mingliu
    Wu, Jingyi
    Wang, Ruzhu
    Xu, Yuxiong
    BUILDING AND ENVIRONMENT, 2011, 46 (10) : 1954 - 1961
  • [45] A three-dimensional numerical study and comparison between the air side model and the air/water side model of a plain fin-and-tube heat exchanger
    Borrajo-Pelaez, R.
    Ortega-Casanova, J.
    Cejudo-Lopez, J. M.
    APPLIED THERMAL ENGINEERING, 2010, 30 (13) : 1608 - 1615
  • [46] Influence of outlet water temperature on refrigeration performance of modular air-cooled chilled (hot)water units with electronic expansion valve
    Jiang, Yantao
    He, Li
    Huagong Xuebao/CIESC Journal, 2012, 63 (05): : 1379 - 1384
  • [47] A DISTRIBUTED MODEL FOR AIR-TO-REFRIGERANT FIN-AND-TUBE EVAPORATORS WITH SPECIAL EMPHASIS ON TWO-PHASE ZONE
    Li, Haiyan
    Tong, Lige
    Sun, Xinxing
    Wang, Li
    Yin, Shaowu
    PROCEEDINGS OF THE ASME INTERNATIONAL HEAT TRANSFER CONFERENCE - 2010, VOL 4: HEAT TRANSFER MEASUREMENT TECHNIQUES, HEAT TRANSFER EQUIPMENT, THERMOELECTRICS, 2010, : 193 - 197
  • [48] Turbulence model-free approach for predictions of air flow dynamics and heat transfer in a fin-and-tube exchanger
    Nagaosa, Ryuichi S.
    ENERGY CONVERSION AND MANAGEMENT, 2017, 142 : 414 - 425
  • [49] Online Model-Based Thermal Prediction for Flexible Control of an Air-Cooled Hydrogenerator
    Oyvang, Thomas
    Noland, Jonas Kristiansen
    Hegglid, Gunne J.
    Lie, Bernt
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2019, 66 (08) : 6311 - 6320
  • [50] A control-oriented hybrid model for a direct expansion air conditioning system
    Xu, Xiangguo
    Huang, Zhiyuan
    Wang, Xiaofei
    Zhong, Ziwen
    Zhang, Xiaobo
    ENERGY AND BUILDINGS, 2017, 155 : 76 - 87