Theoretical Performance Investigation of Vapour Compression Refrigeration System Using HFC and HC Refrigerant Mixtures as Alternatives to Replace R22

被引:31
|
作者
Shaik, Sharmas Vali [1 ]
Babu, T. P. Ashok [1 ]
机构
[1] Natl Inst Technol Karnataka, Dept Mech Engn, Mangalore 575025, Karnataka, India
来源
INTERNATIONAL CONFERENCE ON RECENT ADVANCEMENT IN AIR CONDITIONING AND REFRIGERATION, RAAR 2016 | 2017年 / 109卷
关键词
COP; Compressor discharge temperature; GWP; HFC and HC blends; ODP;
D O I
10.1016/j.egypro.2017.03.053
中图分类号
O414.1 [热力学];
学科分类号
摘要
The present paper describes the theoretical thermodynamic performance of vapour compression refrigeration system using HFC and HC blends as an alternatives to replace the refrigerant R22. In this study thermodynamic analysis of window air conditioner with R431A, R410A, R419A, R134a, R1270, R290 and fifteen refrigerant mixtures consists of R134a, R1270 and R290 was carried out based on actual vapour compression cycle. All the investigated refrigerant mixtures are ozone friendly in nature and they possess GWP in the range of 0.0244 to 1.685 times the GWP of R22. Thermodynamic performance analysis of all the investigated refrigerant mixtures were evaluated at the condensing and evaporating temperatures of 54.4oC and 7.2oC respectively. The results show that COP for the refrigerant mixture R134a/R1270/R290 (50/5/45 by mass percentage) is 2.10% higher among the R22, R431A, R410A, R419A, R134a, R1270, R290, and fifteen studied refrigerant mixtures. The compressor discharge temperature of all the studied refrigerants were lower than that of R22 by 4.8 degrees C-22.2 degrees C. The power consumption per ton of refrigeration for the refrigerant mixture R134a/R1270/R290 (50/5/45 by mass percentage) is 2.01% lower among R22, R431A, R410A, R419A, R134a, R1270, R290, and fifteen studied refrigerant mixtures. Overall the thermodynamic performance of refrigerant mixture R134a/R1270/R290 (50/5/45 by mass percentage) is better than that of R22 with reasonable savings in the energy and hence it is an appropriate ecologically energy efficient alternative refrigerant to substitute R22 used in air conditioning applications. (C) 2017 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:235 / 242
页数:8
相关论文
共 50 条
  • [11] Energy performance of R22 blended with nanofluids in refrigeration system
    Vandaarkuzhali, S.
    Xavier, J. F.
    Ramadoss, R.
    Jayaseelan, V
    Sudhakar, K.
    JOURNAL OF OPTOELECTRONIC AND BIOMEDICAL MATERIALS, 2021, 13 (02): : 33 - 44
  • [12] Thermodynamic performance analysis and flammability study of various new ozone friendly non azeotropic refrigerant mixtures as alternatives to replace R22 used in residential air conditioners
    Shaik, Sharmas Vali
    Babu, Talanki Puttaranga Ashok
    INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2018, 36 (04) : 1470 - 1481
  • [13] EXPERIMENTAL ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING NANO LUBRICANT WITH REFRIGERANT R134a
    Shewale, Vinod C.
    Kapse, Arvind A.
    Sonawane, Vijay R.
    THERMAL SCIENCE, 2024, 28 (5A): : 3687 - 3697
  • [14] EXPERIMENTAL ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING NANO LUBRICANT WITH REFRIGERANT R134a
    SHEWALE, Vinod C.
    KAPSE, Arvind A.
    SONAWANE, Vijay R.
    Thermal Science, 2024, 28 (05): : 3687 - 3697
  • [15] The Thermodynamic Analysis of the Refrigerants Alternative to R22 in the Vapor Compression Refrigeration System
    Cingiz, Zafer
    Katircioglu, Ferzan
    Cay, Yusuf
    Kolip, Ahmet
    JOURNAL OF POLYTECHNIC-POLITEKNIK DERGISI, 2020, 23 (04): : 1205 - 1212
  • [16] Experimental study of a gas-injection refrigeration system using refrigerant mixtures to replace R404A
    Yoon, Il-Joo
    Kim, Jinyoung
    Lee, Dongchan
    Chung, Hyun Joon
    Kim, Yongchan
    APPLIED THERMAL ENGINEERING, 2023, 218
  • [17] PERFORMANCE ANALYSIS OF R22 DMF TURBO ABSORPTION REFRIGERATION SYSTEM
    AGARWAL, RS
    AGARWAL, AK
    BINGADHI, SM
    ENERGY CONVERSION AND MANAGEMENT, 1987, 27 (02) : 211 - 217
  • [18] Performance of propane/isobutane mixtures in a vapour-compression refrigeration system
    Richardson, R.N.
    Butterworth, J.S.
    International Journal of Refrigeration, 1995, 18 (01): : 58 - 62
  • [19] Theoretical Evaluation of Energy Performance of a Vapour Compression Refrigeration System Using Sustainable Refrigerants
    Shaik, Sharmas Vali
    Babu, T. P. Ashok
    INTELLIGENT MANUFACTURING AND ENERGY SUSTAINABILITY, ICIMES 2019, 2020, 169 : 361 - 370
  • [20] Boiling Heat Transfer Coefficient of R22 and an HFC/HC Refrigerant Mixture in a Fin-and-Tube Evaporator of a Window Air Conditioner
    Raj, M.
    Lal, D.
    HEAT TRANSFER-ASIAN RESEARCH, 2010, 39 (06): : 410 - 439