Theoretical Performance Investigation of Vapour Compression Refrigeration System Using HFC and HC Refrigerant Mixtures as Alternatives to Replace R22

被引:31
|
作者
Shaik, Sharmas Vali [1 ]
Babu, T. P. Ashok [1 ]
机构
[1] Natl Inst Technol Karnataka, Dept Mech Engn, Mangalore 575025, Karnataka, India
来源
INTERNATIONAL CONFERENCE ON RECENT ADVANCEMENT IN AIR CONDITIONING AND REFRIGERATION, RAAR 2016 | 2017年 / 109卷
关键词
COP; Compressor discharge temperature; GWP; HFC and HC blends; ODP;
D O I
10.1016/j.egypro.2017.03.053
中图分类号
O414.1 [热力学];
学科分类号
摘要
The present paper describes the theoretical thermodynamic performance of vapour compression refrigeration system using HFC and HC blends as an alternatives to replace the refrigerant R22. In this study thermodynamic analysis of window air conditioner with R431A, R410A, R419A, R134a, R1270, R290 and fifteen refrigerant mixtures consists of R134a, R1270 and R290 was carried out based on actual vapour compression cycle. All the investigated refrigerant mixtures are ozone friendly in nature and they possess GWP in the range of 0.0244 to 1.685 times the GWP of R22. Thermodynamic performance analysis of all the investigated refrigerant mixtures were evaluated at the condensing and evaporating temperatures of 54.4oC and 7.2oC respectively. The results show that COP for the refrigerant mixture R134a/R1270/R290 (50/5/45 by mass percentage) is 2.10% higher among the R22, R431A, R410A, R419A, R134a, R1270, R290, and fifteen studied refrigerant mixtures. The compressor discharge temperature of all the studied refrigerants were lower than that of R22 by 4.8 degrees C-22.2 degrees C. The power consumption per ton of refrigeration for the refrigerant mixture R134a/R1270/R290 (50/5/45 by mass percentage) is 2.01% lower among R22, R431A, R410A, R419A, R134a, R1270, R290, and fifteen studied refrigerant mixtures. Overall the thermodynamic performance of refrigerant mixture R134a/R1270/R290 (50/5/45 by mass percentage) is better than that of R22 with reasonable savings in the energy and hence it is an appropriate ecologically energy efficient alternative refrigerant to substitute R22 used in air conditioning applications. (C) 2017 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:235 / 242
页数:8
相关论文
共 50 条
  • [1] Energy and exergy analysis of R22 and its alternatives in a vapour compression refrigeration system
    Menlik, Tayfun
    Demircioglu, Ahmet
    Ozkaya, Musa Galip
    INTERNATIONAL JOURNAL OF EXERGY, 2013, 12 (01) : 11 - 30
  • [2] Performance analysis: Of vapour compression refrigeration with R22/R124/R152a refrigerant
    Kiatsiriroat, T
    Thalang, KN
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1997, 21 (03) : 221 - 232
  • [3] A THEORETICAL COMPARISON OF TWO ECO-FRIENDLY REFRIGERANTS AS ALTERNATIVES TO R22 USING A SIMPLE VAPOUR COMPRESSION REFRIGERATION SYSTEM
    Bolaji, Bukola Olalekan
    Abiala, Israel Olutunji
    Ismaila, Salami Olasunkanmi
    Borokinni, Francis Olusesi
    TRANSACTIONS OF FAMENA, 2014, 38 (03) : 59 - 70
  • [4] Theoretical exploration of low GWP refrigerant mixtures as replacement to HFC-134A in a vapour compression refrigeration system
    Hasheer Sk, Mohammed
    Kolla, Srinivas
    Kondala Rao, Dasari
    Naga Venkata Sai Ram, Yellapragada
    JOURNAL OF THERMAL ENGINEERING, 2023, 9 (04): : 912 - 920
  • [5] Performance Investigation of Natural Refrigerant R290 as a Substitute to R22 in Refrigeration Systems
    Choudhari, C. S.
    Sapali, S. N.
    INTERNATIONAL CONFERENCE ON RECENT ADVANCEMENT IN AIR CONDITIONING AND REFRIGERATION, RAAR 2016, 2017, 109 : 346 - 352
  • [6] INVESTIGATION OF THE PERFORMANCE BEHAVIOR OF A COMPRESSION REFRIGERATING UNIT WITH HALOGEN REFRIGERANT MIXTURES R22/R142B, R22/R114 AND R22/R12
    TREPP, C
    SAVOIE, P
    KRAUS, WE
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1992, 15 (02): : 101 - 111
  • [7] EXPERIMENTAL ANALYSIS ON VAPOUR COMPRESSION REFRIGERATION SYSTEM USING NANOLUBRICANT WITH HFC-134a REFRIGERANT
    Babu, A. Manoj
    Nallusamy, S.
    Rajan, K.
    NANO HYBRIDS, 2015, 9 : 33 - 43
  • [8] Thermodynamic Performance Analysis of Eco friendly Refrigerant Mixtures to Replace R22 Used in Air conditioning Applications
    Shaik, Sharmas Vali
    Babu, T. P. Ashok
    INTERNATIONAL CONFERENCE ON RECENT ADVANCEMENT IN AIR CONDITIONING AND REFRIGERATION, RAAR 2016, 2017, 109 : 56 - 63
  • [9] Experimental comparison of R22 with R417A performance in a vapour compression refrigeration plant subjected to a cold store
    Aprea, C
    Renno, C
    ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (11-12) : 1807 - 1819
  • [10] R134a and various mixtures of R22/R134a as an alternative to R22 in vapour compression heat pumps
    Karagoz, S
    Yilmaz, M
    Comakli, O
    Ozyurt, O
    ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (02) : 181 - 196