Combined wavelet transform and regression technique for secondary current compensation of current transformers

被引:54
|
作者
Li, F [1 ]
Li, Y [1 ]
Aggarwal, R [1 ]
机构
[1] Univ Bath, Dept Elect & Elect Engn, Bath BA2 7AY, Avon, England
关键词
D O I
10.1049/ip-gtd:20020296
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A technique is proposed to effectively and efficiently compensate for secondary current of current transformers, particularly in the presence of remanent flux. The technique first utilises the wavelet transform to accurately distinguish the distorted section from the healthy section of a secondary current waveform. Secondly the technique uses the regression method to recover the distorted section making use of features extracted from the healthy section, essentially to restore the secondary current to a scaled down replica of the primary system current. The proposed technique is demonstrated on a sample power system, achieving an average compensation error of 1.5% under varying degrees of saturation caused by different levels of remanent flux.
引用
收藏
页码:497 / 503
页数:7
相关论文
共 50 条
  • [31] The use of wavelet transform on eddy current nondestructive detecting
    Sun, XY
    Sun, HQ
    Liu, JY
    Gao, N
    Guo, LW
    Sheng, JN
    FIFTH INTERNATIONAL SYMPOSIUM ON INSTRUMENTATION AND CONTROL TECHNOLOGY, 2003, 5253 : 316 - 321
  • [32] Arcing current Features Extraction Using Wavelet Transform
    Chen, J. C.
    Phung, B. T.
    Zhang, D.
    Blackburn, T. R.
    Ambikairajah, E.
    PROCEEDINGS OF 2014 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM 2014), 2014, : 221 - 224
  • [33] An H∞ technique for the reconstruction of the primary current in industrial transformers
    Bittanti, S
    Cuzzola, FA
    Corbetta, G
    ROBUST CONTROL DESIGN 2000, VOLS 1 & 2, 2000, 1-2 : 59 - 64
  • [34] Detection of high impedance faults using current transformers for sensing and identification based on features extracted using wavelet transform
    Chen, Jichao
    Phung, Toan
    Blackburn, Trevor
    Ambikairajah, Eliathamby
    Zhang, Daming
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (12) : 2990 - 2998
  • [35] Detection of Open Circuiting of Secondary Winding of Current Transformer Using Combined Feature of Hilbert Transform and Stockwell Transform
    Mahela, Om Prakash
    Joshi, Himmani
    Sharma, Deepak
    Sahay, Shuvam
    2018 IEEE 8TH POWER INDIA INTERNATIONAL CONFERENCE (PIICON), 2018,
  • [36] Detection and correction of distorted current transformer current using wavelet transform and artificial intelligence
    Hong, Y. -Y.
    Chang-Chian, P. -C.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2008, 2 (04) : 566 - 575
  • [37] Vibration compensation technique for an optical current transducer
    Niewczas, P
    Cruden, A
    Michie, WC
    Madden, WI
    McDonald, JR
    Andonovic, I
    OPTICAL ENGINEERING, 1999, 38 (10) : 1708 - 1714
  • [38] A compensation technique for transistor mismatch in current mirrors
    Bandi, SR
    Mukund, PR
    IEEE INTERNATIONAL SOC CONFERENCE, PROCEEDINGS, 2004, : 320 - 323
  • [39] The Phase Compensation Technique in Fiber Current Transformer
    Di Zhigang
    Zhang Jingxuan
    Jia Chunrong
    2013 THIRD INTERNATIONAL CONFERENCE ON INTELLIGENT SYSTEM DESIGN AND ENGINEERING APPLICATIONS (ISDEA), 2013, : 1479 - 1482
  • [40] An improved temperature compensation technique for current biasing
    Arbat, A.
    Dieguez, A.
    Samitier, J.
    2007 IEEE INTERNATIONAL SYMPOSIUM ON CIRCUITS AND SYSTEMS, VOLS 1-11, 2007, : 1923 - 1926