Experimental study on forced convective boiling heat transfer of pure refrigerants and refrigerant mixtures in a horizontal tube

被引:116
|
作者
Shin, JY [1 ]
Kim, MS [1 ]
Ro, ST [1 ]
机构
[1] SEOUL NATL UNIV,DEPT MECH ENGN,SEOUL 151742,SOUTH KOREA
关键词
refrigerant; zeotropic mixture; nucleated boiling; horizontal tube; heat transfer coefficient; measurement;
D O I
10.1016/S0140-7007(97)00004-2
中图分类号
O414.1 [热力学];
学科分类号
摘要
Convective boiling heat transfer coefficients of pure refrigerants (R22, R32, R134a, R290, and R600a) and refrigerant mixtures (R32/R134a, R290/R600a, and R32/R125) are measured experimentally and compared with Gungor and Winterton correlation. The test section is made of a seamless stainless steel tube with an inner diameter of 7.7 mm and is uniformly heated by applying electric current directly to the tube. The exit temperature of the test section was kept at 12 degrees C +/- 0.5 degrees C for all refrigerants in this study. Heat fluxes are varied from 10 to 30 kW m(-2) and mass fluxes are set to the discrete values in the range of 424-742 kg m(-2) s(-1) for R22, R32, R134a, R32/R134a, and R32/R125; 265-583 kg m(-2) s(-1) for R290, R600a, and R290/R600a. Heat transfer coefficients depend strongly on heat flux at a low quality region and become independent as quality increases, The Gungor and Winterton correlation for pure substances and the Thome-Shakil modification of this correlation for refrigerant mixtures overpredicts the heat transfer coefficients measured in this study. (C) 1997 Elsevier Science Ltd and IIR.
引用
收藏
页码:267 / 275
页数:9