Numerical Study of Electromagnetic Loss and Heat Transfer in an Oil-Immersed Transformer

被引:10
|
作者
Si, Wen-Rong [1 ]
Fu, Chen-Zhao [1 ]
Wu, Xu-Tao [2 ]
Zhou, Xiu [2 ]
Li, Xiu-Guang [2 ]
Yu, Yi-Ting [3 ]
Jia, Xiao-Yu [4 ]
Yang, Jian [4 ]
机构
[1] State Grid Shanghai Elect Power Res Inst, Shanghai 200437, Peoples R China
[2] State Grid Ningxia Elect Power Res Inst, Yinchuan 750001, Peoples R China
[3] Northwestern Polytech Univ, MOE Key Lab Micro Nano Syst Aerosp, Xian 710072, Peoples R China
[4] Xi An Jiao Tong Univ, MOE Key Lab Thermofluid Sci & Engn, Xian 710049, Peoples R China
关键词
TEMPERATURE; FLOW;
D O I
10.1155/2020/6514650
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Transformer is one of the most important pieces of equipment in power system. The insulation aging and lifespan of transformer are significantly affected by hot spot distributions of internal components inside. In the present paper, the electromagnetic losses of different components and heat transfer process in a three-phase forced oil circulation transformer (400 kVA-15 kV/400 V) are numerically studied with finite element method. The leakage magnetic flux and eddy current loss density for metal components and oil tank are carefully analyzed, and the effect of metal components' electromagnetic loss on hot spot temperature of different components and oil flow in transformer is also studied. It is found that the surface current of metal components is generated by leakage magnetic flux, and surface current density is large when leakage magnetic flux concentrates. The effect caused by relative magnetic permeability of metal components is remarkable on electromagnetic loss of metal components and oil tank, while the effect caused by relative magnetic permeability of transformer tank is relatively small. Due to the mixing of metal components on oil flow, the heat transfer of core is enhanced, its hot spot temperature is lowered, and the hot spot locations of coil and core also change. These results are meaningful for further understanding of heat transfer process in transformer and important for the optimal design of transformer.
引用
收藏
页数:13
相关论文
共 50 条
  • [41] Data augmentation for fault diagnosis of oil-immersed power transformer
    Li, Ke
    Li, Jian
    Huang, Qi
    Chen, Yuhui
    [J]. ENERGY REPORTS, 2023, 9 : 1211 - 1219
  • [42] ANALYSIS OF EXTERNAL HEAT DISSIPATION ENHANCEMENT OF OIL-IMMERSED TRANSFORMER BASED ON FALLING FILM MEASURE
    Li, Yingguang
    Zhou, Zeru
    Lin, Biren
    Zhang, Hao
    Huo, Weifeng
    Deng, Honglei
    Liu, Gang
    [J]. THERMAL SCIENCE, 2022, 26 (06): : 4519 - 4533
  • [43] Mechanism of Increase of Electrostatic Charging Tendency in Insulating Oil for Oil-Immersed Transformer
    Okabe, Sigemitsu
    Kotoh, Masanori
    Tsuchie, Motoo
    Amimoto, Tsuyoshi
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 2011, 176 (04) : 26 - 33
  • [44] Experimental and numerical investigation of wicked heat pipe cooling efficacy in oil-immersed transformers
    Dastjerd, Fateme Tavakoli
    Niazmand, Hamid
    Mahian, Omid
    [J]. APPLIED THERMAL ENGINEERING, 2024, 250
  • [45] Case Analysis of 220 kV Oil-immersed Current Transformer Defect
    Li Pei
    Li Hongbo
    Niu Lin
    Gao Nannan
    Zhang Yan
    Zhang Yanyan
    Pei Ying
    Yin Qinghua
    [J]. 2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 2178 - 2182
  • [46] Fault diagnosis of oil-immersed power transformer by DGA-NN
    Li, Qing-Quan
    Wang, Wei
    Wang, Xiao-Long
    [J]. Gaodianya Jishu/High Voltage Engineering, 2007, 33 (08): : 48 - 51
  • [47] RESEARCH PROGRESS ON INSULATION CONDITION ESTIMATION FOR OIL-IMMERSED POWER TRANSFORMER
    Zhang, Guan-Jun
    Dong, Ming
    Mu, Hai-Bao
    Wei, Jian-Lin
    Yan, Zhang
    [J]. ISEIM 2008: PROCEEDINGS OF 2008 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING, 2008, : 21 - 21
  • [48] Effect of loads on temperature distribution characteristics of oil-immersed transformer winding
    Zhao, Zhengang
    Jiang, Zhangnan
    Li, Yang
    Li, Chuan
    Zhang, Dacheng
    [J]. Distributed Generation and Alternative Energy Journal, 2022, 37 (02): : 237 - 254
  • [49] Synthetic diagnostic method for insulation fault of oil-immersed power transformer
    Qian, Z
    Yang, MZ
    Yan, Z
    [J]. PROCEEDINGS OF THE 6TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 & 2, 2000, : 872 - 875
  • [50] Thermal Modeling of an Inverted-Type Oil-Immersed Current Transformer
    Mahajan, Satish M.
    Robalino, Diego M.
    Sivan, Vinod
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2511 - 2518