Research of Insulation Properties of Polymer Materials Using In Oil-Filled Transformers under High Temperature

被引:0
|
作者
Tu, Youping [1 ]
Sun, Weizhong [2 ]
Yue, Caipeng [1 ]
Chen, Guanghui [1 ]
Wang, Wei [1 ]
机构
[1] North China Elect Power Univ, Dept Elect & Elect Engn, Beijing 102206, Peoples R China
[2] Yunan Elect Power Res Inst, Kunming 650217, Peoples R China
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Traditionally, oil-filled transformers have utilized densified cellulose paper as the primary conductor insulation. However, cellulosic insulation is a relatively low temperature material and thermal degradation due to overload conditions and long-term aging can lead to transformer failures. In order to improve the structure and insulation performance of oil-filled transformers, this paper choose 4 insulation materials with special applications to research, electrical properties of polymer before and after aged under 130 square at different times have been examined, the examined dielectric parameters are dielectric constant, dissipation factor and ac electric breakdown strength. The characteristics of dielectric constant and dissipation factor versus temperature before and after aged under 130 square at different times have been analyzed. Preliminary results show that PTFE and Polycarbonate are ideal substitutes of cellulose paper.
引用
收藏
页码:583 / 586
页数:4
相关论文
共 50 条
  • [1] Assessment of Insulation System State for Oil-Filled High-Voltage Transformers
    Zenova E.V.
    Chernyshev V.A.
    [J]. Russian Electrical Engineering, 2019, 90 (02): : 140 - 146
  • [2] Model for Predictive Control of Temperature in Oil-filled Transformers
    Mastorakis, Nikos E.
    Bulucea, Cornelia Aida
    Manolea, Gheorghe
    Popescu, Marius Constantin
    Perescu-Popescu, Liliana
    [J]. PROCEEDINGS OF THE 11TH WSEAS INTERNATIONAL CONFERENCE ON AUTOMATIC CONTROL, MODELLING AND SIMULATION: CONTROLLING, MODELLING AND SIMULATION, 2009, : 157 - +
  • [3] RESEARCH ON THE EFFECT OF AMBIENT TEMPERATURE VARIATION ON THERMOMETERS FOR OIL-FILLED POWER TRANSFORMERS
    Dai, Yuansheng
    Shan, Huaping
    [J]. 2012 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2012,
  • [4] Estimating the DP Value of the Paper Insulation of Oil-Filled Power Transformers Using an ANFIS Algorithm
    Rhamadhan, Firza Zulmi
    Kinkeldey, Tobias
    Werle, Peter
    Suwarno
    [J]. 2021 11TH INTERNATIONAL CONFERENCE ON POWER, ENERGY AND ELECTRICAL ENGINEERING (CPEEE 2021), 2021, : 202 - 207
  • [5] INSULATION PROPERTIES OF EHV DC OIL-FILLED CABLES
    ANDO, N
    ENDO, T
    NUMAJIRI, F
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1973, EI-8 (03): : 113 - 113
  • [6] Cellulose insulation in oil-filled power transformers: Part II - Maintaining insulation integrity and life
    Oommen, TV
    Prevost, TA
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2006, 22 (02) : 5 - 14
  • [7] Cellulose insulation in oil-filled power transformers: Part I - History and development
    Prevost, TA
    Oommen, TV
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2006, 22 (01) : 28 - 35
  • [8] Models, Simulations and the Reality of Temperature Rise in Oil-Filled Transformers
    Bokes, Peter
    [J]. APPLIED PHYSICS OF CONDENSED MATTER (APCOM 2019), 2019, 2131
  • [9] REVIEW OF CHEMICAL INDICATORS OF DEGRADATION OF CELLULOSIC ELECTRICAL PAPER INSULATION IN OIL-FILLED TRANSFORMERS
    EMSLEY, AM
    STEVENS, GC
    [J]. IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1994, 141 (05) : 324 - 334
  • [10] Fault Analysis of Oil-Filled Power Transformers Using Spectroscopy Techniques
    Kalathiripi, Hussain
    Karmakar, Subrata