Energy and exergy investigation of a combined cooling, heating, power generation, and seawater desalination system

被引:70
|
作者
Moghimi, Mandi [1 ]
Emadi, Mohammadali [1 ]
Akbarpoor, Ali Mirzazade [2 ]
Mollaei, Mohammadreza [1 ]
机构
[1] Iran Univ Sci & Technol, Sch Mech Engn, Tehran, Iran
[2] KN Toosi Univ Technol, Fac Mech Engn, Tehran, Iran
关键词
CCHP; Gas turbine; Multi-effect desalination (MED); HRSG; Ejector refrigeration system; Exergy; MULTIOBJECTIVE OPTIMIZATION; THERMOECONOMIC OPTIMIZATION; ENVIRONMENTAL-ANALYSES; EJECTOR; CYCLE; COGENERATION; PERFORMANCE; SIMULATION; PLANTS; WATER;
D O I
10.1016/j.applthermaleng.2018.05.092
中图分类号
O414.1 [热力学];
学科分类号
摘要
In the present paper, a combined cooling, heating and power and a multi effect desalination with thermal vapor compression system was used to simultaneously produce electricity, fresh water, refrigeration, and hot water for domestic use. In order to link the Brayton cycle to the water desalination and ejector refrigeration systems, a dual-pressure heat recovery steam generator unit was utilized. In this research, the considered system was analyzed in terms of exergy and energy under various operational conditions and also pollution generated by combustion process is determined. To consider the effects of design parameters on the efficiency of the system, a parametric analysis was further conducted to examine influences of such factors as compressor compression ratio, inlet temperature of turbine, vapor pressure entering into the desalination unit, and the number of desalination units on exergy and energy efficiencies of the cycle. The results indicated the capability of the proposed system for providing fresh water, power, cooling and heating loads of 85.57 kg/s, 30 MW, 2.03 MW and 1.11 MW, respectively. Finally, total exergy destruction and exergy and energy efficiencies of the cycle were obtained to be 55.82 MW, 36.03%, and 39.22%, respectively.
引用
收藏
页码:814 / 827
页数:14
相关论文
共 50 条
  • [1] Energy, exergy and exergoeconomic analysis of a combined cooling, desalination and power system
    Zhou, Shihe
    Liu, Xinyu
    Bian, Yongning
    Shen, Shengqiang
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2020, 218
  • [2] Energy and Exergy Analysis of Combined Cooling Heating and Power System
    Dong, Xiangyuan
    Guo, Shuqing
    Yu, Hailong
    [J]. PROCEEDINGS OF 2009 INTERNATIONAL CONFERENCE ON INFORMATION, ELECTRONIC AND COMPUTER SCIENCE, VOLS I AND II, 2009, : 343 - 346
  • [3] A Combined System of Hydrate Seawater Desalination, Cooling and Power Generation Using LNG Cold Energy
    Miao, Wang
    Bao, Junjiang
    Zhang, Ning
    Zhang, Xiaopeng
    [J]. Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2023, 44 (06): : 1452 - 1458
  • [4] Energy and Exergy Analysis of a Combined Cooling Heating and Power System with Regeneration
    Jose, Jobel
    Parthasarathy, Rajesh Kanna
    Arumugam, Senthil Kumar
    [J]. SUSTAINABILITY, 2023, 15 (18)
  • [5] Novel combined desalination, heating and power system: Energy, exergy, economic and environmental assessments
    Saini, Prashant
    Singh, Jeeoot
    Sarkar, Jahar
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2021, 151
  • [6] Energy, Exergy, Economic, and environmental assessment of a trigeneration system for combined power, cooling, and water desalination system driven by solar energy
    Parvez, Mohd
    Ahamad, Taufique
    Lal, Shiv
    Khan, Osama
    Khalid, Faizan
    Yahya, Zeinebou
    [J]. International Journal of Thermofluids, 2024, 22
  • [7] ENERGY AND EXERGY INVESTIGATIONS UPON TRI-GENERATION BASED COMBINED COOLING, HEATING, AND POWER (CCHP) SYSTEM FOR COMMUNITY APPLICATIONS
    Sharma, Meeta
    Singh, Onkar
    [J]. PROCEEDINGS OF THE ASME GAS TURBINE INDIA CONFERENCE, 2017, VOL 2, 2018,
  • [8] Energy, exergy and environmental analysis of a hybrid combined cooling heating and power system utilizing biomass and solar energy
    Wang, Jiangjiang
    Yang, Ying
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 124 : 566 - 577
  • [9] Energy matching and optimization analysis of waste to energy CCHP (combined cooling, heating and power) system with exergy and energy level
    Gao, Penghui
    Dai, Yanjun
    Tong, YenWah
    Dong, Pengwei
    [J]. ENERGY, 2015, 79 : 522 - 535
  • [10] Exergy and thermoeconomic analysis of the combined MED desalination system and the Allam power generation system
    Nazarzadehfard, Amir
    Saraei, Alireza
    Mehrabadi, Saeed Jafari
    Mohsenimonfared, Hamid
    [J]. INTERNATIONAL JOURNAL OF ENERGY AND ENVIRONMENTAL ENGINEERING, 2021, 12 (04) : 679 - 687