Sterilization effectiveness of in-duct ultraviolet germicidal irradiation system in liquid desiccant and indirect/direct evaporative cooling-assisted 100% outdoor air system

被引:20
|
作者
Bang, Jong-Il [1 ]
Park, Joon-Young [2 ]
Jo, Ye-Lim [1 ]
Jeong, Jae-Weon [3 ]
Choi, Anseop [1 ]
Sung, Minki [1 ]
机构
[1] Sejong Univ, Dept Architectural Engn, 209 Neungdong Ro, Seoul 05006, South Korea
[2] Device Solut, Samsung Elect, Facil Team, 90 Samsung Ro, Pyeongtaek Si 17786, Gyeonggi Do, South Korea
[3] Hanyang Univ, Dept Architectural Engn, 222 Wangsimni Ro, Seoul 04763, South Korea
基金
新加坡国家研究基金会;
关键词
Liquid desiccant and indirect/direct evaporative cooling-assisted 100% Outdoor air system (LD-IDECOAS); In-duct ultraviolet germicidal irradiation (ID-UVGI); Irradiation analysis; Microbial contamination; Indoor air quality; PERFORMANCE; CONTAMINATION; BACTERIA; DISINFECTION;
D O I
10.1016/j.buildenv.2020.107350
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Microorganism contamination in air conditioning systems can cause respiratory diseases in building occupants. This study aims to evaluate and predict the performance of an in-duct ultraviolet germicidal irradiation (IDUVGI) system to reduce the microorganisms that can grow in the liquid desiccant and indirect/direct evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS). Bacteria and mold on the direct evaporative cooling (DEC) element and in the outdoor and supply air were monitored using a swab and Petrifilm for surfaces and impact sampler for air during the operation of the LD-IDECOAS. Microbial contamination was first verified in the air before performing the sterilization experiment. The experimental results showed that the airborne bacteria were reduced by 78.3% after the operation of the ID-UVGI system but there was almost no reduction in the airborne mold. The bacteria and mold concentration on the DEC surface were decreased by 99.7% and 96.7% respectively 3 h after the ID-UVGI operation. Even after the ID-UVGI system was operated for 6 days, the microbial contamination in the downstream water was not decreased significantly; the inside of the DEC element was suspected to be improperly sterilized. The operating times of the ID-UVGI system needed to inactivate the microorganisms were predicted from the UV-C intensity distribution by irradiation analysis. Legionella sp. and Penicillium sp. were predicted to be inactivated by 99.9% with UV-C exposures of 6 s and 15 min 57 s or less respectively when the LD-IDECOAS is operated at the highest air flow rate.
引用
收藏
页数:11
相关论文
共 22 条
  • [21] A Variable Volume and Temperature (VVT) Control Strategy for a Liquid-Desiccant and Dew Point Evaporative Cooler-Assisted 100% Outdoor Air System (LDEOS)
    Ham, Sang-Woo
    Kim, Hui-Jeong
    Cho, Sang-Hyeon
    Jeong, Jae-Weon
    2016 ASHRAE ANNUAL CONFERENCE PAPERS, 2016,
  • [22] Evaluation of thermal comfort in an office building served by a liquid desiccant-assisted evaporative cooling air-conditioning system
    Cho, Hye-Jin
    Jeong, Jae-Weon
    ENERGY AND BUILDINGS, 2018, 172 : 361 - 370