Measurement and evaluation of indoor thermal environment in a naturally ventilated industrial building with high temperature heat sources

被引:35
|
作者
Wang, Yi [1 ]
Gao, Jie [1 ]
Xing, Xiao [1 ]
Liu, Yuanlu [1 ]
Meng, Xiaojing [1 ]
机构
[1] Xian Univ Architecture & Technol, Sch Environm & Municipal Engn, 13 Yanta RD, Xian 710055, Shaanxi, Peoples R China
基金
中国国家自然科学基金; 国家杰出青年科学基金;
关键词
Natural ventilation; Industrial building; Wetbulb globe temperature; Thermal environmental parameters; Design stage; CLIMATE-CHANGE; OCCUPATIONAL-HEALTH; STRESS; PRODUCTIVITY; CONVECTION; AIR;
D O I
10.1016/j.buildenv.2015.11.014
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this study, indoor thermal environment and workers' perceptions were investigated at four different locations in a naturally ventilated industrial building with high temperature heat sources in summer and winter. The results demonstrated that the differences between the mean radiant temperature and air temperature were between 0.8 degrees C and 5.3 degrees C in summer and between 1.6 degrees C and 11.0.0 in winter, and the average air velocity generally ranged from 0.3 m/s to 1.5 m/s. Moreover, the average wet bulb globe temperature (WBGT) was between 27.3 degrees C and 29.0 degrees C in summer and between 5.7 degrees C and 8.9 degrees C in winter, which coincided with the workers' perceptions of the thermal environment. The WBGT thus may be one of the potential indices to evaluate the indoor thermal environment in summer and winter. A prediction model for the indoor WBGT using the thermal environmental parameters was developed strictly based on the law of analogy for heat and mass transfer. The predictions agreed quite well with the measured data for WBGT of between 24 degrees C and 30 degrees C in summer and 2 degrees C-10 degrees C in winter, and the absolute differences between the predicted and measured WBGT were between 0 degrees C and 1.1 degrees C with an average of 0.3 degrees C in summer and between 0 degrees C and 1.2 degrees C with an average of 0.5 degrees C in winter. Therefore, the proposed indoor WBGT prediction model was valid and can be used to determine the acceptable thermal environmental parameters during the design stage for naturally ventilated industrial buildings with high temperature heat sources. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:35 / 45
页数:11
相关论文
共 50 条
  • [1] Occupant Perceptions of an Indoor Thermal Environment in a Naturally Ventilated Building
    Ilyas, Salman
    Emery, Ashley
    Heerwagen, Judith
    Heerwagen, Dean
    [J]. ASHRAE TRANSACTIONS 2012, VOL 118, PT 2, 2012, 118 : 114 - 121
  • [2] A new evaluation index for indoor hot environment in naturally ventilated building with hot surface
    Gao, Jie
    Wang, Yi
    Wu, Xiaozhou
    Cui, Yashan
    [J]. INDOOR AND BUILT ENVIRONMENT, 2022, 31 (03) : 745 - 758
  • [3] The impacts of facade and ventilation strategies on indoor thermal environment for a naturally ventilated residential building in Singapore
    Wang, LP
    Wong, NH
    [J]. INDOOR AIR 2005: PROCEEDINGS OF THE 10TH INTERNATIONAL CONFERENCE ON INDOOR AIR QUALITY AND CLIMATE, VOLS 1-5, 2005, : 1320 - 1324
  • [4] Measurement and evaluation of indoor air quality in naturally ventilated residential buildings
    Yin, Haiguo
    Liu, Chunxue
    Zhang, Leiming
    Li, Angui
    Ma, Zhenjun
    [J]. INDOOR AND BUILT ENVIRONMENT, 2019, 28 (10) : 1307 - 1323
  • [5] RNN-based forecasting of indoor temperature in a naturally ventilated residential building
    Weng, Kui
    Mourshed, Monjur
    [J]. PROCEEDINGS OF BUILDING SIMULATION 2019: 16TH CONFERENCE OF IBPSA, 2020, : 3103 - 3108
  • [7] Indoor Thermal Environment in Different Generations of Naturally Ventilated Public Residential Buildings in Singapore
    Deng, Ji-Yu
    Wong, Nyuk Hien
    Hii, Daniel Jun Chung
    Yu, Zhongqi
    Tan, Erna
    Zhen, Meng
    Tong, Shanshan
    [J]. ATMOSPHERE, 2022, 13 (12)
  • [8] Numerical evaluation of the effect of traffic pollution on indoor air quality of a naturally ventilated building
    Chang, TJ
    [J]. JOURNAL OF THE AIR & WASTE MANAGEMENT ASSOCIATION, 2002, 52 (09) : 1043 - 1053
  • [9] Investigation of thermal plume and thermal stratification flow in naturally ventilated spaces with multiple heat sources
    Yang, Changqing
    Chen, Lu
    Li, Tong
    Lu, Na
    Gao, Teng
    Gao, Xiaopan
    Li, Angui
    [J]. BUILDING AND ENVIRONMENT, 2023, 244
  • [10] The impacts of ventilation strategies and facade on indoor thermal environment for naturally ventilated residential buildings in Singapore
    Liping, Wang
    Hien, Wong Nyuk
    [J]. BUILDING AND ENVIRONMENT, 2007, 42 (12) : 4006 - 4015