Inhibition of Rejuvenation Liquid on Trees in XLPE Cables under Switching Impulse Voltages

被引:8
|
作者
Zhu, Guangya [1 ]
Zhou, Kai [1 ]
Gong, Wei [1 ]
He, Min [1 ]
Kong, Jiaming [1 ]
Li, Kangle [1 ]
机构
[1] Sichuan Univ, Sch Elect Engn & Informat, 24 Yihuan Rd, Chengdu 610065, Sichuan, Peoples R China
基金
美国国家科学基金会;
关键词
cross-linked polyethylene (XLPE); pre-injected rejuvenation liquid; inhibition effect; water trees; electrical trees; WATER TREES; ELECTRICAL TREES; PART; PROPAGATION; INSULATION; MECHANISM; INSIGHT;
D O I
10.3390/en12112133
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, the inhibitory effect of preinjected rejuvenation liquid on trees in cross-linked polyethylene (XLPE) cables was investigated. Experimental samples were prepared by inserting needles into XLPE samples, and many equally-spaced holes existed in the outer semiconductive layer. All cable samples were divided into two groups. One sample group was treated with rejuvenation liquid, while the other group was the control group. A tree accelerated aging system was used to obtain trees in the XLPE cable samples. During the aging experiment, an impulse voltage was applied to the samples repeatedly. The micromorphologies of the two groups were observed. Based on the micromorphologies, two parameters were determined: the initiation rate of electrical trees and the average length of trees. Furthermore, the electric field distribution was simulated to analyze the initiation of electrical trees. The results indicate that an electrical tree is much harder to initiate in the pretreated XLPE cables than in the untreated cables. This phenomenon is likely attributed to the dielectrophoretic forces in the pretreated cables. Moreover, rejuvenation liquid deposited in XLPE causes a substantial reduction in the Maxwell stress of molecular chains. Rejuvenation liquid inhibits electrical tree initiation and water tree growth to a great extent.
引用
收藏
页数:14
相关论文
共 35 条
  • [1] Investigation in to growth of electrical trees in XLPE cables under transient voltages
    Sarathi, R
    Sridhar, K
    [J]. PROCEEDINGS OF THE 1998 IEEE INTERNATIONAL CONFERENCE ON CONDUCTION AND BREAKDOWN IN SOLID DIELECTRICS - ICSD '98, 1998, : 329 - 332
  • [2] IMPULSE STRENGTH OF NATURALLY AGED XLPE-CABLES CONTAINING WATER TREES
    DENSLEY, RJ
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1978, 13 (05): : 389 - 391
  • [3] Electrical breakdown characteristics of the XLPE cables under AC, DC, and pulsating voltages
    Grzybowski, S
    Fan, J
    [J]. PROCEEDINGS OF THE 5TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 1997, : 389 - 393
  • [4] Behavior of XLPE medium voltage cable under switching impulse
    Abdallah, MA
    [J]. Proceedings of the 2005 International Symposium on Electrical Insulating Materials, Vols, 1-3, 2005, : 364 - 367
  • [5] Comparison of the accelerated aging under different thermal cycles and voltages impulses in XLPE cables
    Ramírez, J
    Da Silva, E
    Sanz, J
    Bermúdez, J
    Rodríguez, J
    [J]. 2005 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, 2005, : 229 - 232
  • [6] Corona characteristics of aerial conductors under switching impulse voltages
    Sun, Ying
    Montenegro, Alejandro
    Tobin, Tom
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (01) : 206 - 213
  • [7] Electrical Tree Initiation Characteristics Under DC-impulse Composite Voltages in XLPE
    Liu, Hechen
    Li, Yanda
    Zhang, Mingjia
    Xu, Xiaobin
    Liu, Yunpeng
    Zheng, Xinlong
    [J]. Gaodianya Jishu/High Voltage Engineering, 2019, 45 (08): : 2637 - 2643
  • [8] Enhancing Inhibition of Electrical Treeing in XLPE Cables Based on the Targeted Movement of Rejuvenation Fluid Induced by Electric Field
    Wu, Yaping
    Zhou, Kai
    Lin, Siyan
    Wang, Zikang
    Chen, Yidong
    Zhu, Guangya
    Fu, Yao
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (03) : 1048 - 1055
  • [9] Performance of Composite Outdoor Insulator Under Superimposed Direct and Switching Impulse Voltages
    Pinzan, Davide
    Branco, Fabio
    Haddad, Manu A.
    Slama, Mohammed El Amine
    Albano, Maurizio
    Waters, Ronald T.
    Leite, Helder
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (02) : 1193 - 1201
  • [10] Effect of humidity on the breakdown of air gaps under oscillatory switching impulse voltages
    Bharadwaj, RM
    Prabhakar, BR
    [J]. CONFERENCE RECORD OF THE 1996 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1996, : 320 - 323