Selection of wetted media for pre-cooling of air entering natural draft dry cooling towers

被引:39
|
作者
He, Suoying [1 ]
Xu, Yi [1 ]
Zhang, Guanhong [1 ]
Hooman, Kamel [2 ]
Gao, Ming [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
[2] Univ Queensland, Sch Mech & Min Engn, Brisbane, Qld 4072, Australia
基金
中国国家自然科学基金;
关键词
Natural draft cooling tower; Wetted medium; Air mass flow rate; Heat rejection rate; ARTIFICIAL NEURAL-NETWORK; THERMAL-ENERGY STORAGE; SOLAR POWER-PLANTS; PARAMETRIC ANALYSIS; EVAPORATIVE COOLER; PERFORMANCE; OPTIMIZATION; PADS; FLOW; WATER;
D O I
10.1016/j.applthermaleng.2016.11.179
中图分类号
O414.1 [热力学];
学科分类号
摘要
The performance of natural draft dry cooling towers (NDDCTs) can be improved by wetted-medium evaporative pre-cooling. However, the pre-cooling benefit is season dependent and is significantly affected by wetted media. To further investigate the effect of wetted medium type on pre-cooling performance, the current study simulates a pre-cooled NDDCT using two typical types of wetted media, i.e., film (Cellulose7060 and PVC1200) and trickle (Trickle125 and Trickle100). A MATLAB program was developed and was validated against published data. The model was then used to carry out case study of a 120 m-high NDDCT pre-cooled using the selected wetted media with fixed thickness of 300 mm. Both the medium performance and pre-cooled NDDCT performance were compared to recommend the characteristics of wetted media promising for evaporative pre-cooling. Simulation finds that the media with high or low cooling efficiencies and pressure drops are not promising for the studied pre-cooling case while those media with middle cooling efficiencies and pressure drops intend to produce much performance enhancement and Cellulose7060 is a representative of such kind of medium. For the 120 m-high NDDCT, the wetted-medium pre-cooling can raise the heat rejection rate of the tower without pre cooling from 45 MW to 92 MW, 76 MW, 68 MW and 65 MW by Cellulose7060, PVC1200, TricIde125 and Tricldel 00, respectively at ambient temperature of 50 degrees C and humidity of 20%. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:857 / 863
页数:7
相关论文
共 50 条
  • [41] PERFORMANCE TESTING OF LARGE NATURAL DRAFT COOLING TOWERS
    MORGENWE.FE
    COMBUSTION, 1969, 40 (11): : 16 - &
  • [42] Natural draft cooling towers with flue gas inlet
    Eisenkrein, Helena
    Kotz-Pollklaesener, Christian
    CONCRETE SOLUTIONS: PROCEEDINGS OF CONCRETE SOLUTIONS, 5TH INTERNATIONAL CONFERENCE ON CONCRETE REPAIR, 2014, : 719 - 726
  • [43] Heat and mass transfer in natural draft cooling towers
    Kashani M.M.H.
    Dobrego K.V.
    Journal of Engineering Physics and Thermophysics, 2013, 86 (05) : 1072 - 1082
  • [44] Remarks on the Design of Natural Draft Cooling Towers.
    Diver, Marius
    Annales de l'Institut Technique du Batiment et des Travaux Publics, 1977, (353): : 61 - 91
  • [45] PLUME EFFECTS OF NATURAL DRAFT HYPERBOLIC COOLING TOWERS
    VISBISKY, RF
    BIERMAN, GF
    BITTING, CH
    COMBUSTION, 1970, 42 (04): : 54 - &
  • [46] BUCKLING OF NATURAL DRAFT COOLING TOWERS AND STRUCTURAL SAFETY
    Kraetzig, Wilfried B.
    Andres, Matthias
    Eckstein, Ulrich
    JOURNAL OF THE INTERNATIONAL ASSOCIATION FOR SHELL AND SPATIAL STRUCTURES, 2016, 57 (01): : 13 - 24
  • [47] Direct Air Capture via Natural Draft Dry Cooling Tower
    Dong, Peixin
    Li, Xiaoxiao
    Yu, Yuanyuan
    Zhang, Zekun
    Feng, Junjie
    INTERNATIONAL JOURNAL OF GREENHOUSE GAS CONTROL, 2021, 109
  • [48] NOISE FROM NATURAL DRAFT COOLING-TOWERS
    REINICKE, WL
    RIEDEL, EP
    NOISE CONTROL ENGINEERING JOURNAL, 1980, 15 (01) : 28 - 36
  • [49] TRENDS IN AIR-COOLING SYSTEMS AND DRY COOLING-TOWERS
    KUHN, W
    CHEMISCHE TECHNIK, 1977, 29 (11): : 647 - 647
  • [50] Energy Impact of Air Pre-cooling on Screw Air Compressor
    Guo, Da
    Ma, Zhixian
    Zhang, Jili
    Liu, Mingsheng
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 937 - 944