Selection of wetted media for pre-cooling of air entering natural draft dry cooling towers

被引:39
|
作者
He, Suoying [1 ]
Xu, Yi [1 ]
Zhang, Guanhong [1 ]
Hooman, Kamel [2 ]
Gao, Ming [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
[2] Univ Queensland, Sch Mech & Min Engn, Brisbane, Qld 4072, Australia
基金
中国国家自然科学基金;
关键词
Natural draft cooling tower; Wetted medium; Air mass flow rate; Heat rejection rate; ARTIFICIAL NEURAL-NETWORK; THERMAL-ENERGY STORAGE; SOLAR POWER-PLANTS; PARAMETRIC ANALYSIS; EVAPORATIVE COOLER; PERFORMANCE; OPTIMIZATION; PADS; FLOW; WATER;
D O I
10.1016/j.applthermaleng.2016.11.179
中图分类号
O414.1 [热力学];
学科分类号
摘要
The performance of natural draft dry cooling towers (NDDCTs) can be improved by wetted-medium evaporative pre-cooling. However, the pre-cooling benefit is season dependent and is significantly affected by wetted media. To further investigate the effect of wetted medium type on pre-cooling performance, the current study simulates a pre-cooled NDDCT using two typical types of wetted media, i.e., film (Cellulose7060 and PVC1200) and trickle (Trickle125 and Trickle100). A MATLAB program was developed and was validated against published data. The model was then used to carry out case study of a 120 m-high NDDCT pre-cooled using the selected wetted media with fixed thickness of 300 mm. Both the medium performance and pre-cooled NDDCT performance were compared to recommend the characteristics of wetted media promising for evaporative pre-cooling. Simulation finds that the media with high or low cooling efficiencies and pressure drops are not promising for the studied pre-cooling case while those media with middle cooling efficiencies and pressure drops intend to produce much performance enhancement and Cellulose7060 is a representative of such kind of medium. For the 120 m-high NDDCT, the wetted-medium pre-cooling can raise the heat rejection rate of the tower without pre cooling from 45 MW to 92 MW, 76 MW, 68 MW and 65 MW by Cellulose7060, PVC1200, TricIde125 and Tricldel 00, respectively at ambient temperature of 50 degrees C and humidity of 20%. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:857 / 863
页数:7
相关论文
共 50 条
  • [1] A review of wetted media with potential application in the pre-cooling of natural draft dry cooling towers
    He, Suoying
    Gurgenci, Hal
    Guan, Zhiqiang
    Huang, Xiang
    Lucas, Manuel
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 44 : 407 - 422
  • [2] THE INLET AIR PRE-COOLING OF NATURAL DRAFT DRY COOLING TOWERS-WETTED MEDIUM ISSUE
    He, Suoying
    Zhang, Guanhong
    Xu, Yi
    Sun, Fengzhong
    PROCEEDINGS OF THE ASME POWER CONFERENCE JOINT WITH ICOPE-17, 2017, VOL 1, 2017,
  • [3] Pre-cooling with Munters media to improve the performance of Natural Draft Dry Cooling Towers
    He, Suoying
    Gurgenci, Hal
    Guan, Zhiqiang
    Alkhedhair, Abdullah M.
    APPLIED THERMAL ENGINEERING, 2013, 53 (01) : 67 - 77
  • [4] Experimental study of the application of two trickle media for inlet air pre-cooling of natural draft dry cooling towers
    He, Suoying
    Guan, Zhiqiang
    Gurgenci, Hal
    Hooman, Kamel
    Lu, Yuanshen
    Alkhedhair, Abdullah M.
    ENERGY CONVERSION AND MANAGEMENT, 2015, 89 : 644 - 654
  • [5] Numerical simulation of water spray for pre-cooling of inlet air in natural draft dry cooling towers
    Alkhedhair, Abdullah
    Gurgenci, Hal
    Jahn, Ingo
    Guan, Zhiqiang
    He, Suoying
    APPLIED THERMAL ENGINEERING, 2013, 61 (02) : 416 - 424
  • [6] Water spray for pre-cooling of inlet air for Natural Draft Dry Cooling Towers - Experimental study
    Alkhedhair, Abdullah
    Guan, Zhiqiang
    Jahn, Ingo
    Gurgenci, Hal
    He, Suoying
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2015, 90 : 70 - 78
  • [7] CFD analysis of pre-cooling water spray system in natural draft dry cooling towers
    Xia, Lin
    Gurgenci, Hal
    Liu, Deyou
    Guan, Zhiqiang
    Zhou, Ling
    Wang, Pei
    APPLIED THERMAL ENGINEERING, 2016, 105 : 1051 - 1060
  • [8] Economic Analyses of Natural Draft Dry Cooling Towers Pre-cooled Using Wetted Media
    Zhang, Guanhong
    He, Suoying
    Zhang, Zhiyu
    Xu, Yi
    Wang, Rui
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 423 - 430
  • [9] Parametric study on spray cooling system for optimising nozzle design with pre-cooling application in natural draft dry cooling towers
    Alkhedhair, Abdullah
    Jahn, Ingo
    Gurgenci, Hal
    Guan, Zhiqiang
    He, Suoying
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2016, 104 : 448 - 460
  • [10] Investigation on the control mechanism of spray pre-cooling the inlet air of natural draft dry cooling tower
    He, Suoying
    Li, Yang
    Wang, Mingwei
    Wang, Aiping
    Alkhedhair, Abdullah M.
    Guan, Hongjun
    Wu, Xuehong
    Shi, Yuetao
    Gao, Ming
    APPLIED THERMAL ENGINEERING, 2022, 217