Annual operating energy savings of liquid desiccant and evaporative-cooling-assisted 100% outdoor air system

被引:61
|
作者
Kim, Min-Hwi [1 ]
Park, Joon-Young [1 ]
Sung, Min-Ki [3 ]
Choi, An-Seop [2 ]
Jeong, Jae-Weon [1 ]
机构
[1] Hanyang Univ, Div Architectural Engn, Seoul 133791, South Korea
[2] Sejong Univ, Dept Architectural Engn, Seoul 143747, South Korea
[3] Sejong Univ, Dept Architectural Engn, Seoul 143791, South Korea
基金
新加坡国家研究基金会;
关键词
Evaporative cooling; Liquid desiccant; 100% outdoor air system; Water-side free cooling; Solar thermal system; VENTILATION PRECONDITIONING SYSTEM; MASS-TRANSFER; PACKED-COLUMN; DEHUMIDIFICATION; PERFORMANCE; HEAT; DEHUMIDIFIER/REGENERATOR;
D O I
10.1016/j.enbuild.2014.03.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The purpose of this research is to investigate the annual operating energy performance of a desiccant and evaporative-cooling-assisted 100% outdoor air system. The seasonal mode of operation of the proposed system is also suggested and used for estimating the energy saving potentials. The TRNSYS 16 program integrated with a commercial equation solver is used for the energy simulation of the proposed system, and then two existing air handling alternatives: a conventional variable air volume (VAV) system and an existing evaporative-cooling-assisted system are compared with the proposed system. The proposed system shows operating energy savings of 82% over the conventional VAV system during the summer, and 54% and 37% in the winter and the intermediate season operations, respectively. Ultimately, the proposed system provides 68% annual operating energy saving over the conventional VAV system, and 23% savings compared to the established evaporative-cooling-assisted system. It is also found that the extreme energy benefit can be obtained by enhancing the evaporative cooling effects using the liquid desiccant (LD) unit. The operating energy saving of the LD unit can be achieved by applying the water-side free cooling and the solar thermal system. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:538 / 550
页数:13
相关论文
共 50 条
  • [31] Indoor Air Quality Enhancement Performance of Liquid Desiccant and Evaporative Cooling-Assisted Air Conditioning Systems
    Kim, Beom-Jun
    Park, Junseok
    Jeong, Jae-Weon
    SUSTAINABILITY, 2019, 11 (04)
  • [32] TRNSYS simulation for solar-assisted liquid desiccant evaporative cooling
    Reddy, Sneha
    Priya, S. Shanmuga
    Carollo, Andrew J.
    Kumar, S. Harish
    INTERNATIONAL JOURNAL OF AMBIENT ENERGY, 2020, 41 (01) : 105 - 111
  • [33] Impact of district heat source on primary energy savings of a desiccant-enhanced evaporative cooling system
    Dong, Hye-Won
    Lee, Sung-Joon
    Yoon, Dong-Seob
    Park, Joon-Young
    Jeong, Jae-Weon
    ENERGY, 2017, 123 : 432 - 444
  • [34] An evaporative and desiccant cooling system for air conditioning in humid climates
    Camargo, J.R.
    Godoy Jr., E.
    Ebinuma, C.D.
    Journal of the Brazilian Society of Mechanical Sciences and Engineering, 2005, 27 (03) : 243 - 247
  • [35] Cooling performance of a 100% outdoor air system integrated with indirect and direct evaporative coolers
    Kim, Min-Hwi
    Jeong, Jae-Weon
    ENERGY, 2013, 52 : 245 - 257
  • [36] Studying the performance of a liquid desiccant indirect evaporative cooling system
    Cui, Xin
    Liu, Yanhua
    Liu, Yilin
    Jin, Liwen
    Zhao, Min
    Meng, Xiangzhao
    INNOVATIVE SOLUTIONS FOR ENERGY TRANSITIONS, 2019, 158 : 5659 - 5665
  • [37] Evaluation of thermal comfort in an office building served by a liquid desiccant-assisted evaporative cooling air-conditioning system
    Cho, Hye-Jin
    Jeong, Jae-Weon
    ENERGY AND BUILDINGS, 2018, 172 : 361 - 370
  • [38] Study on the Hybrid Liquid Desiccant Evaporative Cooling Air-Conditioning Refrigeration Circulation System
    Liu, Xiong
    ELECTRICAL POWER & ENERGY SYSTEMS, PTS 1 AND 2, 2012, 516-517 : 1250 - 1256
  • [39] Energy Saving Potential of a Thermoelectric Heat Pump-Assisted Liquid Desiccant System in a Dedicated Outdoor Air System
    Kim, Min-Hwi
    Park, Joon-Young
    Jeong, Jae-Weon
    ENERGIES, 2017, 10 (09):
  • [40] Desiccant cooling assisted vapor compression system: A double stage desiccant cooling cycle via evaporative condenser
    Choi, Sung
    Choi, Sun
    APPLIED THERMAL ENGINEERING, 2021, 198