Annual operating energy savings of liquid desiccant and evaporative-cooling-assisted 100% outdoor air system

被引:61
|
作者
Kim, Min-Hwi [1 ]
Park, Joon-Young [1 ]
Sung, Min-Ki [3 ]
Choi, An-Seop [2 ]
Jeong, Jae-Weon [1 ]
机构
[1] Hanyang Univ, Div Architectural Engn, Seoul 133791, South Korea
[2] Sejong Univ, Dept Architectural Engn, Seoul 143747, South Korea
[3] Sejong Univ, Dept Architectural Engn, Seoul 143791, South Korea
基金
新加坡国家研究基金会;
关键词
Evaporative cooling; Liquid desiccant; 100% outdoor air system; Water-side free cooling; Solar thermal system; VENTILATION PRECONDITIONING SYSTEM; MASS-TRANSFER; PACKED-COLUMN; DEHUMIDIFICATION; PERFORMANCE; HEAT; DEHUMIDIFIER/REGENERATOR;
D O I
10.1016/j.enbuild.2014.03.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The purpose of this research is to investigate the annual operating energy performance of a desiccant and evaporative-cooling-assisted 100% outdoor air system. The seasonal mode of operation of the proposed system is also suggested and used for estimating the energy saving potentials. The TRNSYS 16 program integrated with a commercial equation solver is used for the energy simulation of the proposed system, and then two existing air handling alternatives: a conventional variable air volume (VAV) system and an existing evaporative-cooling-assisted system are compared with the proposed system. The proposed system shows operating energy savings of 82% over the conventional VAV system during the summer, and 54% and 37% in the winter and the intermediate season operations, respectively. Ultimately, the proposed system provides 68% annual operating energy saving over the conventional VAV system, and 23% savings compared to the established evaporative-cooling-assisted system. It is also found that the extreme energy benefit can be obtained by enhancing the evaporative cooling effects using the liquid desiccant (LD) unit. The operating energy saving of the LD unit can be achieved by applying the water-side free cooling and the solar thermal system. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:538 / 550
页数:13
相关论文
共 50 条
  • [1] Energy saving potential of liquid desiccant in evaporative-cooling-assisted 100% outdoor air system
    Kim, Min-Hwi
    Park, Jun-Seok
    Jeong, Jae-Weon
    ENERGY, 2013, 59 : 726 - 736
  • [2] Operating energy savings in a liquid desiccant and dew point evaporative cooling-assisted 100% outdoor air system
    Ham, Sang-Woo
    Lee, Sung-Joon
    Jeong, Jae-Weon
    ENERGY AND BUILDINGS, 2016, 116 : 535 - 552
  • [3] Primary energy savings in desiccant and evaporative cooling-assisted 100% outdoor air system combined with a fuel cell
    Kim, Min-Hwi
    Dong, Hae-Won
    Park, Joon-Young
    Jeong, Jae-Weon
    APPLIED ENERGY, 2016, 180 : 446 - 456
  • [4] Energy Performance of a Liquid Desiccant and Evaporative Cooling-Assisted 100% Outdoor Air System in Commercial Ships
    Park, Joon-Young
    Lee, Sung-Joon
    Yoon, Dong-Seob
    Jeong, Jae-Weon
    2016 ASHRAE ANNUAL CONFERENCE PAPERS, 2016,
  • [5] Operating Energy Savings of a Liquid Desiccant and Evaporative Cooling-Assisted Air-Handling System in Marine Applications
    Park, Joon-Young
    Jeong, Jae-Weon
    ENERGIES, 2017, 10 (04)
  • [6] Retrofit of a liquid desiccant and evaporative cooling-assisted 100% outdoor air system for enhancing energy saving potential
    Kim, Min-Hwi
    Yoon, Dong-Seop
    Kim, Hui-Jeong
    Jeong, Jae-Weon
    APPLIED THERMAL ENGINEERING, 2016, 96 : 441 - 453
  • [7] Energy conservation benefit of water-side free cooling in a liquid desiccant and evaporative cooling-assisted 100% outdoor air system
    Kim, Min-Hwi
    Park, Joon-Young
    Ham, Sang-Woo
    Jeong, Jae-Weon
    ENERGY AND BUILDINGS, 2015, 104 : 302 - 315
  • [8] Energy Performance of Liquid Desiccant and Evaporative Cooling-Assisted 100% Outdoor Air Systems under Various Climatic Conditions
    Li, Shiying
    Jeong, Jae-Weon
    ENERGIES, 2018, 11 (06):
  • [9] Energy conservation potential of an indirect and direct evaporative cooling assisted 100% outdoor air system
    Kim, M. H.
    Kim, J. H.
    Kwon, O. H.
    Choi, A. S.
    Jeong, J. W.
    BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2011, 32 (04): : 345 - 360
  • [10] Energy benefit of a cascade liquid desiccant dehumidification in a desiccant and evaporative cooling-assisted building air-conditioning system
    Park, Joon-Young
    Dong, Hye-Won
    Cho, Hye-Jin
    Jeong, Jae-Weon
    APPLIED THERMAL ENGINEERING, 2019, 147 : 291 - 301