Influence of Design Parameters and Defects on Electric Field Distributions inside MV Cable Joints

被引:0
|
作者
Metwally, I. A. [1 ]
Al-Badi, A. H. [1 ]
Al-Hinai, A. S. [1 ]
Al Kamali, F. [1 ]
AI-Ghaithi, H. [1 ]
机构
[1] Sultan Qaboos Univ, Coll Engn, Dept Elect & Comp Engn, Muscat, Oman
来源
PROCEEDINGS OF THE 18TH MEDITERRANEAN ELECTROTECHNICAL CONFERENCE MELECON 2016 | 2016年
关键词
cable joints; electric field distribution; defects; failure; finite element method;
D O I
暂无
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
This paper presents a 2d finite-element analysis for a 33-kV, three-phase, three-core cross-linked polyethylene (XLPE) underground cable (UGC) straight joint of the heat shrink type. The aim of this work is to show how the joint design parameters and different defects affect the electric field distribution, and find optimum material properties to enhance the lifetime of cable joints. This is investigated by calculating the electric field distributions and showing how the optimized selection of joint material properties can reduce the localized high electric field to avoid partial discharge activities. Several design parameters are investigated such as insulation layer's thickness and relative permittivity, and termination angles of ferrule and its insulation. In addition, size and location of different defects such as air voids, water droplets, sharp tips and delamination are examined. The paper concludes important points for proper design of medium-voltage (MV) cable joints to enhance their lifetime and hence increase the reliability of such cable systems.
引用
收藏
页数:6
相关论文
共 50 条
  • [41] Reduction of Electric-Field Intensification and Hot-Spot Formation inside Cable Terminations
    Metwally, I. A.
    Al-Badi, A.
    Al-Hinai, A.
    Al-Mayasi, M.
    Al-Harthi, A.
    Al-Hashmi, K.
    Al-Zaabi, I.
    2014 17TH IEEE MEDITERRANEAN ELECTROTECHNICAL CONFERENCE (MELECON), 2014, : 193 - 197
  • [42] The influence of pulsed electric field on hematological parameters in rat
    Coskun, Ozlem
    Comlekci, Selcuk
    TOXICOLOGY AND INDUSTRIAL HEALTH, 2013, 29 (09) : 862 - 866
  • [43] Design and Optimization of Electric Field near Head of 2×6 MV Tandem Accelerator
    Zhang X.
    Peng Z.
    Hu Y.
    Yuanzineng Kexue Jishu/Atomic Energy Science and Technology, 2022, 56 (04): : 718 - 724
  • [44] Influence of a Localized Transverse Magnetic Field on Dose Distributions of MV Photon Beams in Inhomogeneous Medium
    Ahn, Woo Sang
    Choi, Wonsik
    Ka, Young Ran
    Kwak, Jungwon
    Jung, In-Hye
    Ahn, Sohyun
    Shin, Seong Soo
    JOURNAL OF MAGNETICS, 2020, 25 (03) : 409 - 414
  • [45] Dual channel cable in conduit thermohydraulics: Influence of some design parameters
    Nicollet, S
    Duchateau, JL
    Fillunger, H
    Martinez, A
    Parodi, S
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2000, 10 (01) : 1102 - 1105
  • [46] Electric field tailoring in HVDC cable joints utilizing electro-thermal simulation: effect of field grading materials
    Baferani, Mohamadreza Arab
    Shahsavarian, Tohid
    Li, Chuanyang
    Tefferi, Mattewos
    Jovanovic, Ivan
    Cao, Yang
    2020 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2020, : 400 - 404
  • [47] THE INFLUENCE OF ELECTRIC FIELD AND TEMPERATURE ON THE ELECTRICAL CONDUCTIVITY OF POLYETHYLENE FOR POWER CABLE INSULATIONS
    Taranu, Lucian Viorel
    Notingher, Petru
    Stancu, Cristina
    UNIVERSITY POLITEHNICA OF BUCHAREST SCIENTIFIC BULLETIN SERIES C-ELECTRICAL ENGINEERING AND COMPUTER SCIENCE, 2018, 80 (04): : 45 - 56
  • [48] Analysis of electric field and partial discharge characteristics of cable joint stress cone dislocation defects
    Sun, Yuwei
    Lv, Anqiang
    Xie, Zhiyuan
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2024, 18 (05) : 231 - 244
  • [49] One method for strong electric field reduction at cable terminations and their influence on environment
    Raicevic, N.
    Aleksic, S.
    7TH INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY AND ELECTROMAGNETIC ECOLOGY, PROCEEDINGS, 2007, : 88 - 91