Rationalisation and reliability improvement of fire-fighting systems - the Novi Sad case study

被引:2
|
作者
Stipic, Matija [2 ]
Prodanovic, Dusan [1 ]
Kolakovic, Srdan [3 ]
机构
[1] Univ Belgrade, Fac Civil Engn, Belgrade 11000, Serbia
[2] Vojvodinaprojekt, Novi Sad 21000, Serbia
[3] Fac Engn, Novi Sad 21000, Serbia
关键词
water supply system; fire flow; filling station; pillar hydrant; network rationalisation;
D O I
10.1080/15730620802541649
中图分类号
TV21 [水资源调查与水利规划];
学科分类号
081501 ;
摘要
Water supply systems are commonly used to supply fire-fighting water in most EU countries. To provide fast access to water, the standard practice is to install a huge number of hydrants along the entire water supply network. Pipe diameters and working pressures in the network are designed for a combination of the maximum hourly water demand and fire-fighting needs. However, in poorly managed water supply systems most of the hydrants are out of order. Although hundreds of hydrants exist in the network, the reality is that fire water tankers are usually refilled at just a few locations that are equipped with reliable hydrants maintained by the fire brigades. This paper presents a somewhat different approach for the provision of fire-fighting water. The approach discussed in the paper is based on the concept being introduced in the city of Novi Sad, Serbia, by cooperative efforts of the municipal Water Supply and Sewerage Company and the fire-fighting service. In addition to presenting the experience gained in the case study, some generic conclusions are drawn. As an alternative to having a number of unreliable and small hydrants distributed throughout the network, the new concept proposes the construction of several strategically positioned filling stations, with high-flow-rate pillar hydrants and good access roads for the manoeuvering of fire water tankers. If properly designed and distributed around the city, such filling stations would increase the reliability of fire-fighting operations. The filling stations' design methodology presented in this paper is composed of a fire-risk spatial assessment, a hydraulic check of water supply network operations and a worst-case traffic load analysis. By employing the proposed methodology, not only can the reliability of fire-fighting operations be increased, but if accepted and implemented the methodology can lead to leakage reduction and improvements in water quality and the system's energy efficiency. In the test case of Novi Sad, a large number of hydrants were replaced by 14 filling stations that have been designed and constructed. A hydraulic model of the water supply network was calibrated using pressure-drop tests and flow capacity measurements of the existing hydrants. The model was used to examine the performance of the designed filling stations during their parallel operation. The paper presents the results of the test application and recommendations for the possible implementation of the concept.
引用
收藏
页码:169 / 181
页数:13
相关论文
共 50 条
  • [41] Study on the effect of laying electric tracing belt on low temperature protection of polar marine fire-fighting pipelines
    Zhang Rongchuan
    ENERGY REPORTS, 2023, 9 : 99 - 105
  • [42] Study on the effect of laying electric tracing belt on low temperature protection of polar marine fire-fighting pipelines
    Zhang Rongchuan
    ENERGY REPORTS, 2023, 9 : 99 - 105
  • [43] Water transportation planning in connection with extreme weather conditions; case study - Port of Novi Sad, Serbia
    Komazec, Nenad
    Soskic, Svetislav
    Milic, Aleksandar
    Strbac, Katarina
    Valjarevic, Aleksandar
    OPEN GEOSCIENCES, 2024, 16 (01)
  • [44] What will Prevail within Citybreak Travel, Motivation or Demotivation? Case Study of Novi Sad, Vojvodina, Serbia
    Vujicic, Miroslav D.
    Stamenkovic, Igor
    Stankov, Ugljesa
    Kovacic, Sanja
    Vasiljevic, Dordije A.
    Locke, Jasmina Popov
    GEOGRAPHICA PANNONICA, 2020, 24 (01): : 42 - 55
  • [45] Study on integrated fire-fighting technology of fully-mechanized caving mining of the deeply inclined combustible thick seam
    Wu, Haijun
    Xu, Changfu
    Yuan, Shasha
    Yao, Haifei
    Zheng, Zhongya
    PROGRESS IN MINE SAFETY SCIENCE AND ENGINEERING II, 2014, : 3 - 8
  • [46] INFLUENCE OF AMBIENCE TEMPERATURE AND OPERATIONAL-CONSTRUCTIVE PARAMETERS ON LANDFILL GAS GENERATION - CASE STUDY NOVI SAD
    Vujic, Goran
    Jovicic, Nebojsa
    Petrovic-Djurovic, Maja
    Ubavin, Dejan
    Nakomcic, Branka
    Jovicic, Gordana
    Gordic, Dusan
    THERMAL SCIENCE, 2010, 14 (02): : 555 - 564
  • [47] Risk Assessment Approach for Prioritizing Danube Basin-Specific Pollutants: a Case Study in the Novi Sad Region
    Milovanovic, Dusan
    Spanik, Ivan
    Miloradov, Mirjana Vojinovic
    Mihajlovic, Ivana
    Radonic, Jelena
    Machynakova, Andrea
    Petrovic, Maja
    POLISH JOURNAL OF ENVIRONMENTAL STUDIES, 2019, 28 (06): : 4297 - 4309
  • [48] A Study on Operation Algorithm of Load Test Device Using Energy Storage System for Field Test in Fire-Fighting Emergency Generator
    Choi, Seung-Kyou
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2022, 17 (04) : 2541 - 2551
  • [49] A Study on Operation Algorithm of Load Test Device Using Energy Storage System for Field Test in Fire-Fighting Emergency Generator
    Seung-Kyou Choi
    Journal of Electrical Engineering & Technology, 2022, 17 : 2541 - 2551
  • [50] Neurotoxicity in complex environmental mixtures—a case-study at River Danube in Novi Sad (Serbia) using zebrafish embryos
    Riccardo Massei
    Werner Brack
    Sven Seidensticker
    Henner Hollert
    Melis Muz
    Tobias Schulze
    Martin Krauss
    Eberhard Küster
    Environmental Science and Pollution Research, 2023, 30 : 96138 - 96146