Intelligent tuning of the 2-DOF PID controller on the DCS for steam temperature control of thermal power plant

被引:0
|
作者
Kim, DH [1 ]
Hong, WP [1 ]
Hwang, JH [1 ]
Lee, SH [1 ]
机构
[1] Hanbat Natl Univ, Dept Elec Elect Instrumentat & Control Eng, Yusong Gu, Seoul 305719, South Korea
来源
2002 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE, CONFERENCE RECORD | 2002年
关键词
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In the thermal power plant, there are six manipulated variables; main steam flow, feedwater flow, air flow, spray flow, and gas recirculation flow. Also, there are five controlled variables such as generator output, main steam pressure, main steam temperature, exhaust gas O density, and reheater steam temperature. Therefore, the thermal power plant control system is a multi-input and output system. In the control system, the main steam temperature typically is regulated by the fuel flow rate and the spray flow rate, and the reheater steam temperature is regulated by the gas recirculation flow rate. However, it is difficult to maintain strict control of the steam temperature in order to avoid thermal stress, because of variation of the heating value according to the fuel source, the time delay of changes in main steam temperature versus changes in fuel flow rate, difficulty of control on the main steam temperature control and the reheater steam temperature control system owing to the dynamic response characteristics of changes in steam temperature and the reheater steam temperature, fluctuation of inner fluid water and steam flow rates widely during load-following operation. Up to the present time, the PID controller has been used to operate this system. However, it is very difficult to achieve an optimal PID gain without any experience, since the gain of the PID controller has to be manually tuned by trial and error procedures. This paper focuses on the characteristic comparison of the PID controller, the modified 2-DOF PID Controller on the DCS, in order to design an optimal controller which can be operated on the thermal generating plant in Seoul, Korea. The modified 2-DOF PID Controller is designed with a 2-degrees parameter, to enable them to fit into the thermal plant during disturbances vs. many kinds noises and load-following operation. In order to attain an optimal control method, transfer function and operating data from start-up, running, and stop procedures of the thermal plant have been acquired. Through this research, the stable range of a 2-DOF parameter for only this system could be found for the start-up procedure and this parameter could be used for the tuning problem. Also, this paper tried whether intelligent tuning method based on the immune network algorithms can be used effectively in a tuning for these controllers.
引用
收藏
页码:1 / 13
页数:13
相关论文
共 50 条
  • [31] Optimal design for 2-DOF PID controller based on fuzzy genetic algorithms
    Yang, Yanxi
    Liu, Ding
    Yi Qi Yi Biao Xue Bao/Chinese Journal of Scientific Instrument, 2006, 27 (08): : 868 - 872
  • [32] Design of Optimal 2-DOF PID controller using GWO Technique for Automatic Generation control of a multi-source Power System
    Debnath, Manoj Kumar
    Singh, ManjitBahadur
    Mallick, Ranjan Kumar
    2016 IEEE UTTAR PRADESH SECTION INTERNATIONAL CONFERENCE ON ELECTRICAL, COMPUTER AND ELECTRONICS ENGINEERING (UPCON), 2016, : 531 - 536
  • [33] DE optimized parallel 2-DOF PID controller for load frequency control of power system with governor dead-band nonlinearity
    Sahu, Rabindra Kumar
    Panda, Sidhartha
    Rout, Umesh Kumar
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 49 : 19 - 33
  • [34] PID self-tuning immune fuzzy control of steam temperature control system in fossil-fired power plant
    Xu, Changbo
    Liu, Congcong
    Bi, Zhenfu
    Zhang, Chengjin
    WCICA 2006: SIXTH WORLD CONGRESS ON INTELLIGENT CONTROL AND AUTOMATION, VOLS 1-12, CONFERENCE PROCEEDINGS, 2006, : 3973 - +
  • [35] Water Level Control in the Thermal Power Plant Steam Separator Based on New PID Tuning Method for Integrating Processes
    Kvascev, Goran S.
    Djurovic, Zeljko M.
    ENERGIES, 2022, 15 (17)
  • [37] Robust 2-DoF PID control for Congestion control of TCP/IP Networks
    Vilanova, R.
    Alfaro, V. M.
    INTERNATIONAL JOURNAL OF COMPUTERS COMMUNICATIONS & CONTROL, 2010, 5 (05) : 968 - 975
  • [38] A new PID controller tuning system and its application to a flue gas temperature control in a gas turbine power plant
    Yukitomo, M
    Iino, Y
    Hino, S
    Takahaski, K
    Nagata, K
    PROCEEDINGS OF THE 1998 IEEE INTERNATIONAL CONFERENCE ON CONTROL APPLICATIONS, VOLS 1 AND 2, 1996, : 1373 - 1377
  • [39] Intelligent autopilot control design for a 2-DOF helicopter model
    Jafarzadeh, Saeed
    Mirheidari, Rooholah
    Motlagh, Mohammad Reza Jahed
    Barkhordari, Mojtaba
    INTERNATIONAL JOURNAL OF COMPUTERS COMMUNICATIONS & CONTROL, 2008, 3 : 337 - 342
  • [40] Automatic Generation Control by Hybrid Invasive Weed Optimization and Pattern Search Tuned 2-DOF PID Controller
    Manoharan, N.
    Dash, S. S.
    Rajesh, K. S.
    Panda, S.
    INTERNATIONAL JOURNAL OF COMPUTERS COMMUNICATIONS & CONTROL, 2017, 12 (04) : 533 - 549