Two-Part Tariff of Pumped Storage Power Plants for Wind Power Accommodation

被引:8
|
作者
Li, Hua [1 ,2 ]
Zheng, Hongwei [1 ,2 ]
Zhou, Bowen [1 ,2 ]
Li, Guangdi [1 ,2 ]
Yang, Bo [1 ,2 ]
Hu, Bo [3 ]
Ma, Min [3 ]
机构
[1] Northeastern Univ, Coll Informat Sci & Engn, Shenyang 110819, Peoples R China
[2] Northeastern Univ, Key Lab Integrated Energy Optimizat & Secure Oper, Shenyang 110819, Peoples R China
[3] State Grid Liaoning Elect Power Co Ltd, Shenyang 110006, Peoples R China
关键词
pumped storage power plant; wind power accommodation; electricity market; two-part tariff; ENERGY-STORAGE; SYSTEM; STRATEGY; CHINA;
D O I
10.3390/su14095603
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Pumped storage power plants face many challenges in competing in the electricity market, and high pumping costs lead to high prices for their power generation, which is one of the important factors that has limited their development. To address this problem, this paper studies the pumped storage two-part tariff mechanism considering wind power accommodation and uses the peak-valley price difference of wind power to realize the rationality and economy of a pumped storage charging and discharging strategy. It can improve the competitiveness of pumped storage power plants participating in electricity market transactions. Then, by considering the economic advantages of "pumped storage + clean energy", a pumped storage and wind power joint optimal dispatching model was established based on the original pumped storage pricing method. This model takes the total system cost reduction after the introduction of pumped storage as the objective function to derive a reasonable pumped storage strategy. After which, the two-part tariff for pumped storage power plants was formulated based on the principle of reasonable revenue. Finally, a sensitivity analysis of various relevant parameters of the power plant was conducted through case studies to verify the effectiveness of the two-part tariff mechanism of pumped storage. It was found that the electricity tariff is lowest when the ratio of plant capacity to upper reservoir capacity is 1:6.37 (MW/million m(3)).
引用
收藏
页数:18
相关论文
共 50 条
  • [31] On two-part tariff competition in a homogeneous product duopoly
    Griva, Krina
    Vettas, Nikolaos
    INTERNATIONAL JOURNAL OF INDUSTRIAL ORGANIZATION, 2015, 41 : 30 - 41
  • [32] On the electrical two-part tariff-The Brazilian perspective
    Steele Santos, Paulo E.
    Leme, Rafael Coradi
    Galvao, Leandro
    ENERGY POLICY, 2012, 40 : 123 - 130
  • [33] A new self-scheduling strategy for integrated operation of wind and pumped-storage power plants in power markets
    Varkani, Ali Karimi
    Daraeepour, Ali
    Monsef, Hassan
    APPLIED ENERGY, 2011, 88 (12) : 5002 - 5012
  • [34] Economic Dispatch Planning Based on Considerations of Wind Power Generation and Pumped Storage Hydroelectric Plants for Isolated Power Systems
    Kuo, Ming-Tse
    Lu, Shiue-Der
    Tsou, Ming-Chang
    2015 IEEE/IAS 51ST INDUSTRIAL & COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE (I&CPS), 2015,
  • [35] Two-part Compound Bidding Mode of Wind Power Considering Demand-side Interaction
    Xiao, Yunpeng
    Wang, Xifan
    Dang, Can
    Du, Chao
    2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014,
  • [36] Strategies for the optimal operation of pumped storage power plants
    Jukic, Domagoj-Kresimir
    Kugi, Andreas
    Kemmetmueller, Wolfgang
    AT-AUTOMATISIERUNGSTECHNIK, 2024, 72 (02) : 143 - 159
  • [37] Can pumped storage power plants be a strategic reserve?
    Knackfuss, Guenter
    Bergmann, Heike
    WASSERWIRTSCHAFT, 2014, 104 (7-8) : 102 - 103
  • [38] Use of Pumped Storage Hydroelectric Power Plants in Uzbekistan
    Mukhammadiev M.M.
    Klichev S.I.
    Applied Solar Energy (English translation of Geliotekhnika), 2018, 54 (06): : 468 - 471
  • [39] Concepts and Implementation of modern Pumped Storage Power Plants
    Schmid, M.
    Lechner, A.
    ELEKTROTECHNIK UND INFORMATIONSTECHNIK, 2016, 133 (4-5): : 208 - 210
  • [40] The Two-Part Tariff FURTHER NOTES BY AN ELECTRICAL ENGINEER
    Rowson, R. B.