Power differential method for discrimination between fault and magnetizing inrush current in transformers

被引:119
|
作者
Yabe, K
机构
[1] Intelligent Systems Department, Computer and Communications R. and D. Center, Tokyo Electric Power Company, Yokohama
关键词
transformer protection; microprocessor-based relays; protection relays; magnetizing inrush; active power relays;
D O I
10.1109/61.636909
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
To avoid the needless trip by magnetizing inrush current, the second harmonic component is commonly used for blocking differential relay in power transformers, However, the second harmonic component in fault current is increased by the introduction of underground 500kV lines. This paper describes a new method to discriminate internal fault from inrush current by the sum of active power flowing into transformers from each terminal. The average power is almost zero for energizing, but an internal fault consumes large power. To check the performance of this method, actual inrush current and voltage waveforms of 500/154kV transformer are accurately measured by digital equipment. The usefulness is confirmed by applying the method to the measured inrush and simulated fault data.