1 atm subcooled liquid nitrogen cryogenic system with GM-refrigerator for a HTS power transformer

被引:0
|
作者
Yoshida, S [1 ]
Ohashi, K [1 ]
Umeno, T [1 ]
Suzuki, Y [1 ]
Kamioka, Y [1 ]
Kimura, H [1 ]
Tsutsumi, K [1 ]
Iwakuma, M [1 ]
Funaki, K [1 ]
Bhono, T [1 ]
Yagi, Y [1 ]
机构
[1] Taiyo Toyo Sanso Co Ltd, Kawasaki, Kanagawa 2100866, Japan
关键词
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
A subcooled liquid nitrogen cryogenic system with GM-refrigerators was developed. The system was operated successfully in a commercial distribution power grid for three consecutive weeks without additional liquid nitrogen supply. The system consists of two main units. One is a HTS transformer unit and the HTS transformer is installed in a G-FRP cryostat. The other one is a pump unit. The pump unit has a liquid nitrogen pump and two GM-refrigerators of 290 W at 64 K for 50 Hz operation in a stainless steel dewar. The refrigerator cold heads are immersed in liquid nitrogen and produce directly subcooled liquid nitrogen in the pump unit. Those two units are connected by transfer-tubes and I atmosphere (0.1 MPa) subcooled liquid nitrogen is circulated through the system. In the field test, the refrigerators were operated at 60 Hz and it took 12 hours to cool the transformer down to 70 K and 26 hours to 66 K. The refrigerator cold heads were controlled not to be below 64 K during operation. In spite of a heat generation by the HTS transformer, the subcooled liquid nitrogen temperature in the HTS transformer unit was kept lower than 68 K.
引用
收藏
页码:473 / 480
页数:8
相关论文
共 12 条
  • [1] 1 atm subcooled liquid nitrogen cryogenic system for oxide superconducting power transformer
    Yoshida, S
    Yagi, Y
    Umeno, T
    Ishida, T
    Kamioka, Y
    Ogino, H
    Iwakuma, M
    Funaki, K
    Yasukawa, Y
    Konno, M
    [J]. ADVANCES IN CRYOGENIC ENGINEERING, VOL 43 PTS A AND B, 1998, 43 : 1191 - 1198
  • [2] Subcooled liquid nitrogen refrigerator for HTS power systems
    Suzuki, Y
    Yoshida, S
    Kamioka, Y
    [J]. CRYOGENICS, 2003, 43 (10-11) : 597 - 602
  • [3] Cryogenic cooling system of HTS transformers by natural convection of subcooled liquid nitrogen
    Chang, HM
    Choi, YS
    Van Sciver, SW
    Dal Choi, K
    [J]. CRYOGENICS, 2003, 43 (10-11) : 589 - 596
  • [4] Sub-cooled Liquid Nitrogen Cryogenic System with Neon Turbo-refrigerator for HTS Power Equipment
    Yoshida, S.
    Hirai, H.
    Nara, N.
    Ozaki, S.
    Hirokawa, M.
    Eguchi, T.
    Hayashi, H.
    Iwakuma, M.
    Shiohara, Y.
    [J]. ADVANCES IN CRYOGENIC ENGINEERING, 2014, 1573 : 1246 - 1253
  • [5] Integrated design of cryogenic refrigerator and liquid-nitrogen circulation loop for HTS cable
    Chang, Ho-Myung
    Ryu, Ki Nam
    Yang, Hyung Suk
    [J]. CRYOGENICS, 2016, 80 : 183 - 192
  • [6] A compact cryocooling system with subcooled liquid nitrogen for small HTS magnets
    Chang, Ho-Myung
    Kim, Min-Jee
    Sim, Jung Wook
    Lee, Bang-Wook
    Oh, Il-Sung
    [J]. IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2008, 18 (02) : 1479 - 1482
  • [7] Cryogenic system with the sub-cooled liquid nitrogen for cooling HTS power cable
    Fan, YF
    Gong, LH
    Xu, XD
    Li, LF
    Zhang, L
    Xiao, LY
    [J]. CRYOGENICS, 2005, 45 (04) : 272 - 276
  • [8] Cryogenic system design for HTS power transmission cable cooling with sub-cooled liquid nitrogen
    Fan, YF
    Zhang, L
    Gong, LH
    [J]. CRYOGENICS AND REFRIGERATION - PROCEEDINGS OF ICCR'2003, 2003, : 277 - 280
  • [9] Cryogenic design of liquid-nitrogen circulation system for long-length HTS cables with altitude variation
    Chang, Ho-Myung
    Ryu, Ki Nam
    Yang, Hyung Suk
    [J]. CRYOGENICS, 2017, 83 : 50 - 56
  • [10] A cryogenic dc-dc power converter for a 100kW synchronous HTS generator at liquid nitrogen temperatures
    Bailey, Wendell
    Wen, Hauming
    Yang, Yifeng
    Forsyth, Andrew
    Jia, Chungjiang
    [J]. SUPERCONDUCTIVITY CENTENNIAL CONFERENCE 2011, 2012, 36 : 1002 - 1007