CO2 Heat Pump Water Heater: System Design and Experimental Study

被引:0
|
作者
Liu, Yefeng [1 ]
Zhuo, Zhiyang [1 ]
Zhang, Feng [1 ]
Bao, Tuanwei [2 ]
机构
[1] Univ Shanghai Sci & Technol, Shanghai 200093, Peoples R China
[2] Shanghai Delphi Automot Air Conditioning Syst Ltd, Shanghai 201204, Peoples R China
关键词
Carbon dioxide; Heat pump water heater; Trans-critical cycle; Experimental study;
D O I
10.1007/978-3-642-39581-9_14
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A performance testing experiment platform of heat pump water heater of CO2 trans-critical cycle whose evaporator and gas cooler are both sleeve type heat exchanger has been designed and then constructed. CO2 refrigerant charge amount of the system is 1.23 kg. System performance has been researched by adjusting the degree of opening of the expansion valve and controlling the flow of water of the gas cooler. The results show that: The system can provide hot water of 65 degrees when its cop is 3.2. And hot water of above 80 degrees can be obtained when system's cop is above 2.0. The water flow of the gas cooler has the greatest impact on the cop of the system, the temperature of water out of the gas cooler, and the exhaust pressure of the system. With highly efficient heat exchanger, the temperature of water out of the gas cooler could be increased while compressor discharge temperature is remained the same. So when the system provides high temperature water, it could run in higher cop.
引用
收藏
页码:131 / 142
页数:12
相关论文
共 50 条
  • [41] The Influence of Internal Heat Exchanger on the Performance of Transcritical CO2 Water Source Heat Pump Water Heater
    Feng, Fan
    Zhang, Ze
    Liu, Xiufang
    Liu, Changhai
    Hou, Yu
    [J]. ENERGIES, 2020, 13 (07)
  • [42] Development of natural refrigerant (CO2) heat pump water heater for residential use
    Taira, Teruhiko
    [J]. Nihon Enerugi Gakkaishi, 1600, 9 (649-654):
  • [43] Effects of refrigerant charge on performances of transcritical CO2 heat pump water heater
    Jin D.
    Koyama S.
    Xue J.
    Takata N.
    [J]. Xinan Jiaotong Daxue Xuebao/Journal of Southwest Jiaotong University, 2010, 45 (05): : 680 - 684
  • [44] Field Measurement of Central CO2 Heat Pump Water Heater for Multifamily Retrofit
    Banks, Adria
    Grist, Colin
    Heller, Jonathan
    Lim, Hyunwoo
    [J]. SUSTAINABILITY, 2022, 14 (13)
  • [45] Experimental evaluation of CO2 water heater
    Hwang, YH
    Radermacher, R
    [J]. NATURAL WORKING FLUIDS'98: IIR - GUSTAV LORENTZEN CONFERENCE, 1998, 1998 (04): : 368 - 375
  • [46] Experimental Study of the Compressor in a R410a Heat Pump Water Heater System
    Wang, Fengkun
    Fan, Xiaowei
    Lian, Zhiwei
    Wang, Fang
    [J]. 6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 671 - 678
  • [47] Advanced Energy System of Solar Power Combined Electric Vehicle and CO2 Heat Pump Water Heater
    Chisaka, Hideyuki
    Nakagawa, Tsuguhiko
    [J]. 2015 INTERNATIONAL CONFERENCE ON INFORMATION SCIENCE AND MANAGEMENT ENGINEERING (ICISME 2015), 2015, : 154 - 158
  • [48] Experimental Investigation on Transcritical CO2 Heat Pump System
    Liu, Yingfu
    Zhao, Mingxing
    Jin, Guangya
    [J]. 2016 INTERNATIONAL CONFERENCE ON ARCHITECTURE AND CIVIL ENGINEERING (ICACE 2016), 2016, : 605 - 609
  • [49] Experiment of a CO2 water-to-water heat pump system
    [J]. 2001, Science Press (31):
  • [50] Experimental and numerical study of a CO2 water-to-water heat pump for hot water generation
    Illan-Gomez, F.
    Sena-Cuevas, V. F.
    Garcia-Cascales, J. R.
    Velasco, F. J. S.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 132 : 30 - 44