Corrosion Detection and Analysis of the Underground Grounding Grid in a 220kv Transformer Substation

被引:0
|
作者
Zhou, Ziqiang [1 ]
Hu, Jiayuan [1 ]
Zhu, Liwei [1 ]
机构
[1] Zhejiang Elect Power Corp, Res Inst, Hangzhou 310014, Zhejiang, Peoples R China
关键词
Transformer substation; large grounding grid; electrical impedance tomography; corrosion detection; corrosion monitoring; DIAGNOSIS;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The first corrosion detection for the large grounding grid of a 220kV substation was performed based on electrical impedance tomography (EIT) technology. The impedance value of grounding grid branch which represented the corrosion state of metal was calculated using the current and voltage data acquired on-site through injecting a direct current from one down conductor and collecting voltage data from other down conductors. The results indicated that the impedance increase ratio of the No.143 grounding grid branch in test area D was higher than the warning value (>15 times), indicating a breakage has occurred on this grounding grid branch. The two-dimension corrosion image of the whole underground grounding grid was calculated and drawn accurately and visually using the corrosion diagnosis software. The corrosion rate of carbon steel was monitored in the serious corrosion area later, to realize the online corrosion monitoring of grounding grid metal. EIT technology realized the underground grounding grid statues visible exhibition, and could be used to detect the corrosion state, corrosion area and failure location of the underground grounding grid rapidly and effectively. This could reduce the blindness of corrosion detection for grounding grid and provide guidelines on the corrosion maintenance of underground grounding grid in large substation.
引用
收藏
页码:331 / 340
页数:10
相关论文
共 50 条
  • [1] Main Transformer Fault Analysis in 220kV Substation
    Wu, Dong-xun
    Wang, Miao
    Liu, Ji-wu
    [J]. PROCEEDINGS OF 2019 IEEE 3RD INFORMATION TECHNOLOGY, NETWORKING, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (ITNEC 2019), 2019, : 551 - 554
  • [2] The Design of 220kV Substation Grounding Grid with difference soil resistivity using wenner and Schlumberger Methods
    Ibrahim, Mohammed Abdaldaim
    Li, Lin
    Wang, Ping
    [J]. 2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2018, : 2525 - 2530
  • [3] Corrosion failure analysis of the galvanized lightning rod in a 220 kV transformer substation
    Hu, Jiayuan
    Fang, Zhixing
    Qian, Zhouhai
    Shen, Xiaoming
    Zhou, Haifei
    Jin, Dongchun
    [J]. ANTI-CORROSION METHODS AND MATERIALS, 2017, 64 (06) : 620 - 625
  • [4] Unequally Spaced Grounding Grid Designed from Equally Spaced Grounding Grid for 220/132 kV Substation
    Kumar, Anup
    Kumar, Vijay
    Ashok, Pathare Akshay
    [J]. 2018 INTERNATIONAL CONFERENCE ON ADVANCES IN COMMUNICATION AND COMPUTING TECHNOLOGY (ICACCT), 2018, : 114 - 116
  • [5] Analysis of Abnormal Discharge of 220kV Transformer
    Liu Hong
    Liang Jizhong
    Wang Wei
    Guo Ruizhou
    [J]. PROCEEDINGS OF 2018 IEEE 3RD ADVANCED INFORMATION TECHNOLOGY, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (IAEAC 2018), 2018, : 2388 - 2392
  • [6] The analysis of overheat failure for 220kV voltage transformer with live detection
    Chi Dan-yi
    Huang Fucun
    Sui Dong-peng
    Geng Li-na
    Zhao Dan
    [J]. JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2058 - 2059
  • [7] Research on protective distance between arrester and transformer of 220kV AIS substation
    Zhou, Yuanyuan
    Zhou, Lixing
    Li, Lei
    Gan, Lingxia
    Xu, Yinfeng
    [J]. ICEET: 2009 INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENT TECHNOLOGY, VOL 2, PROCEEDINGS, 2009, : 236 - 239
  • [8] Influence study of a new 220kV Substation access on regional power grid
    Su, Yongchun
    Wang, Xiaoming
    Shu, Zhan
    [J]. PROCEEDINGS OF THE 2015 4TH INTERNATIONAL CONFERENCE ON SENSORS, MEASUREMENT AND INTELLIGENT MATERIALS, 2016, 43 : 221 - 225
  • [9] Abnormal trip analysis of circuit breaker in 220kV substation
    Niu, Shu
    Wang, Wei
    [J]. PROCEEDINGS OF 2019 IEEE 3RD INFORMATION TECHNOLOGY, NETWORKING, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (ITNEC 2019), 2019, : 210 - 213
  • [10] Analysis of A 220kV Current Transformer Explosion Accident
    Zhu Yi
    Rong Hua
    Liu Xu
    Ren Honggang
    Wang Shimin
    Wang Aimin
    Wang Hai
    Wang Jia
    [J]. PROCEEDINGS OF THE 2016 4TH INTERNATIONAL CONFERENCE ON MACHINERY, MATERIALS AND COMPUTING TECHNOLOGY, 2016, 60 : 1451 - 1455