Thermal modeling of indirect water heater in city gate station of natural gas to evaluate efficiency and fuel consumption

被引:10
|
作者
Mostafavi, Seyed Alireza [1 ]
Shirazi, Mohammad [2 ]
机构
[1] Arak Univ, Dept Mech Engn, Fac Engn, Arak, Iran
[2] Natl Iranian Gas Co, Arak, Markazi Provinc, Iran
关键词
Natural gas presure reduction; City gate station; Indirect water heater; Efficiency; Gas composition; Geometry;
D O I
10.1016/j.energy.2020.118390
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, a comprehensive model of indirect water heater for a pressure reduction station of natural gas has been presented. Effiiency and fuel consumption of heater have been estimated by applying energy and mass conservation equations. Three terms of energy including heat absorbed by natural gas, heat transferred to environment from stack and heat loses to environment from heater body have been evaluated. Thermal properties of natural gas has been calcualated using AGA8 state equation. Therefore, the model is a function of climate, heater geometry and natural gas characteristics including temperature, pressure and its composition. The results are compared with data recorded from real station in Iran (Arak, Kheriabad and Malekabad stations) and very good agreement has been observed. Reducing temperature and increasing pressure of inlet gas, thickening glass wool insulation and rising fire tube radius led to an increase in heater's thermal efficiency from 20 to 60% and consequently fuel consumption of heater was reduced. Finally, choosing the sutible geometery yeilded a higher heater efficincy with a raise from 44% to 70%. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:18
相关论文