Effects of ambient humidity and thermal aging on properties of Nomex insulation in mining dry-type transformer

被引:15
|
作者
Li, Lu [1 ]
Song, Jiancheng [1 ]
Lei, Zhipeng [1 ]
Kang, Ailiang [1 ]
Wang, Zhengyu [2 ]
Men, Rujia [1 ]
Ma, Yun [3 ]
机构
[1] Taiyuan Univ Technol, Coll Elect & Power Engn, Shanxi Key Lab Min Elect Equipment & Intelligent, Taiyuan 030024, Shanxi, Peoples R China
[2] State Grid Henan Elect Power Co, Zhengzhou Power Supply Co, Zhengzhou, Henan, Peoples R China
[3] State Grid Shanxi Elect Power Co, Jinzhong Power Supply Co, Jinzhong, Shanxi, Peoples R China
来源
HIGH VOLTAGE | 2021年 / 6卷 / 01期
基金
中国国家自然科学基金;
关键词
PARTIAL DISCHARGE; SURFACE-CHARGE; FLASHOVER; SPACERS; OIL; DC;
D O I
10.1049/hve.2019.0293
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Temperature and humidity are the main factors that cause the decomposition of Nomex paper widely used as turn-to-turn insulation material of mining dry-type transformers. In this study, for understanding the effect of ambient humidity and thermal aging on the properties of Nomex paper, specimens with the initial moisture content of 7% were aged in the oven for 168, 504, 672 h at 180 degrees C, respectively. After thermal aging, corona discharge experiments of unaged and aged specimens with different aging degrees were carried out at different relative humidity (RH) levels from 10 to 70%. The characteristic parameters of corona discharge, such as the average discharge amplitude and the number of discharges, were measured. Then, the surface conductivity and the surface potential decay rate were measured. The morphology and attenuated total internal reflectance Fourier transform infrared spectroscopy were also analysed for explaining the difference of properties between unaged and aged specimens. The experiment results indicate that the average discharge amplitude decreases with the increase of RH or the deepening of the aging degree of specimens, but the number of discharges shows the reversal tendency. The changes in the physical structure and chemical composition, which is induced by the hydrolysis reaction of Nomex paper, accelerate the surface potential decay and increase the surface conductivity.
引用
收藏
页码:71 / 81
页数:11
相关论文
共 50 条
  • [11] Thermal Prognosis of Dry-type Transformer: Simulation Study on Load and Ambient Temperature Impacts
    Bagheri, M.
    Subramaniam, A.
    Bhandari, S.
    Chandar, S.
    Nadarajan, S.
    Gupta, A. K.
    Panda, S. K.
    IECON 2015 - 41ST ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2015, : 1158 - 1163
  • [12] Automated Dry-type Transformer Aging Evaluation: A Simulation Study
    Soltanbayev, Ilyas
    Sarmukhanov, Radkhan
    Kazymov, Sanzhar
    Otelgen, Talgat
    Bagheri, Mehdi
    2017 INTERNATIONAL SIBERIAN CONFERENCE ON CONTROL AND COMMUNICATIONS (SIBCON) PROCEEDINGS, 2017,
  • [13] Real-time Dry-type Transformer Aging Evaluation
    Soltanbayev, Ilyas
    Bagheri, Mehdi
    Toan Phung
    2017 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM), VOLS 1 & 2, 2017, : 551 - 554
  • [14] Thermal response and failure mode evaluation of a dry-type transformer
    Blanco Alonso, Pelayo E.
    Meana-Fernandez, Andres
    Fernandez Oro, Jesus M.
    APPLIED THERMAL ENGINEERING, 2017, 120 : 763 - 771
  • [15] Thermal field and hottest spot of the ventilated dry-type transformer
    Zheng, DC
    Yang, JX
    Wen, ZH
    PROCEEDINGS OF THE 6TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 & 2, 2000, : 141 - 143
  • [16] A Novel Method to Predict Severity of Thermal Aging and Degree of Polymerization for Reliable Diagnosis of Dry-Type Insulation
    Mishra, S.
    Baral, A.
    Mishra, D.
    Chakravorti, S.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (02) : 631 - 640
  • [17] Optimization of Mechanical Properties of Insulation Materials for Dry-Type Transformers
    Huang, Jing
    Chen, Bangfa
    Li, Woyang
    2023 IEEE/IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA, I&CPS ASIA, 2023, : 184 - 188
  • [18] Thermal Analysis of a Dry-Type Distribution Power Transformer Using FEA
    Arjona, M. A.
    Hernandez, C.
    Escarela-Perez, R.
    Melgoza, E.
    2014 INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES (ICEM), 2014, : 2270 - 2274
  • [19] Investigation of Causes of Dry-Type Transformer On-Load Tap-Changer Insulation
    Brilinskiy, Andrey S.
    Evdokunin, Georgy A.
    Chudny, Vladimir S.
    Mingazov, Radmir I.
    Ponomarev, Timofey A.
    PROCEEDINGS OF THE 2018 IEEE CONFERENCE OF RUSSIAN YOUNG RESEARCHERS IN ELECTRICAL AND ELECTRONIC ENGINEERING (EICONRUS), 2018, : 591 - 597
  • [20] Research on Thermal Aging Characteristics of Dry-type Transformer Epoxy Resin Based on Dielectric Response and Activation Energy
    Feng, J. J.
    Zhang, X.
    Wang, W.
    Zhang, W.
    Ren, P.
    Peng, P.
    2019 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2019, : 178 - 181