Effects of ambient humidity and thermal aging on properties of Nomex insulation in mining dry-type transformer

被引:15
|
作者
Li, Lu [1 ]
Song, Jiancheng [1 ]
Lei, Zhipeng [1 ]
Kang, Ailiang [1 ]
Wang, Zhengyu [2 ]
Men, Rujia [1 ]
Ma, Yun [3 ]
机构
[1] Taiyuan Univ Technol, Coll Elect & Power Engn, Shanxi Key Lab Min Elect Equipment & Intelligent, Taiyuan 030024, Shanxi, Peoples R China
[2] State Grid Henan Elect Power Co, Zhengzhou Power Supply Co, Zhengzhou, Henan, Peoples R China
[3] State Grid Shanxi Elect Power Co, Jinzhong Power Supply Co, Jinzhong, Shanxi, Peoples R China
来源
HIGH VOLTAGE | 2021年 / 6卷 / 01期
基金
中国国家自然科学基金;
关键词
PARTIAL DISCHARGE; SURFACE-CHARGE; FLASHOVER; SPACERS; OIL; DC;
D O I
10.1049/hve.2019.0293
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Temperature and humidity are the main factors that cause the decomposition of Nomex paper widely used as turn-to-turn insulation material of mining dry-type transformers. In this study, for understanding the effect of ambient humidity and thermal aging on the properties of Nomex paper, specimens with the initial moisture content of 7% were aged in the oven for 168, 504, 672 h at 180 degrees C, respectively. After thermal aging, corona discharge experiments of unaged and aged specimens with different aging degrees were carried out at different relative humidity (RH) levels from 10 to 70%. The characteristic parameters of corona discharge, such as the average discharge amplitude and the number of discharges, were measured. Then, the surface conductivity and the surface potential decay rate were measured. The morphology and attenuated total internal reflectance Fourier transform infrared spectroscopy were also analysed for explaining the difference of properties between unaged and aged specimens. The experiment results indicate that the average discharge amplitude decreases with the increase of RH or the deepening of the aging degree of specimens, but the number of discharges shows the reversal tendency. The changes in the physical structure and chemical composition, which is induced by the hydrolysis reaction of Nomex paper, accelerate the surface potential decay and increase the surface conductivity.
引用
收藏
页码:71 / 81
页数:11
相关论文
共 50 条
  • [1] Effect of Moisture on Accelerated Thermal Aging Degradation of Nomex Insulation of Dry-Type Transformer
    Li, Lu
    Song, Jiancheng
    Wen, Minmin
    Zhang, Sha
    Gao, Zhiwei
    Wang, Zhengyu
    2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 202 - 205
  • [2] Aging law and reliability analysis of Nomex paper used for dry-type transformer insulation
    Wen, Minmin
    Tian, Muqin
    Song, Yuan
    Liu, Yuan
    Lei, Zhipeng
    Song, Jiancheng
    Gaodianya Jishu/High Voltage Engineering, 2014, 40 (11): : 3430 - 3437
  • [3] The aging characteristics of the Nomex paper for the flameproof dry-type transformer
    Song, Jiancheng
    Wen, Minmin
    Li, Lu
    Isenberg, Arnd
    2016 IEEE INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD), VOLS 1-2, 2016, : 625 - 629
  • [4] Research on the aging experiment of the insulation resin of dry-type transformer
    Zhejiang Sanbian Sci-Tech Co. Ltd., Sanmen 317100, China
    Gaoya Dianqi, 2006, 5 (385-387):
  • [5] Investigation on the Partial Discharge of the Cavity in Nomex Insulation for Mining Dry Type Transformer
    Zhang, Sha
    Song, Jiancheng
    Tian, Muqin
    Wen, Minmin
    Li, Lu
    Gao, Zhiwei
    Wang, Zhengyu
    2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 525 - 529
  • [6] Investigation on space charge properties of Nomex insulation paper in the mining dry type transformer during hygrothermal ageing
    Li, Lu
    Song, Jiancheng
    Wang, Zhengyu
    Zhang, Rui
    Cao, Jinmei
    Ma, Yun
    Li, Yongzhi
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2020, 14 (05) : 576 - 584
  • [7] Thermal-ageing characteristics of dry-type transformer epoxy composite insulation
    Wang, Yongqiang
    Feng, Changhui
    Fei, Ruoyu
    Luo, Yu
    HIGH PERFORMANCE POLYMERS, 2020, 32 (07) : 741 - 752
  • [8] The Evaluation of Thermal endurance of Cast-Resin Dry-Type Transformer Insulation Structure
    Cai, Dingguo
    Tang, Jinquan
    Li, Jianfeng
    2012 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2012,
  • [9] Effect of Thermal Aging on Interturn Insulation Properties of Dry-type Air-core Power Reactors
    Wei, Xinlao
    Yu, Chunlai
    Liang, Jianquan
    Liu, Heqian
    Zhang, Hongda
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1590 - 1594
  • [10] Estimating the aging trend of dry-type current transformer
    Wu, RN
    Lin, YH
    JOURNAL OF THE CHINESE INSTITUTE OF ENGINEERS, 2004, 27 (01) : 69 - 77