Partial Discharge Ultrasound Detection Using the Sagnac Interferometer System

被引:40
|
作者
Wang, Yu [1 ]
Li, Xiaomin [2 ]
Gao, Yan [2 ]
Zhang, Hongjuan [2 ]
Wang, Dong [1 ]
Jin, Baoquan [1 ,3 ]
机构
[1] Taiyuan Univ Technol, Coll Phys & Optoelect, Key Lab Adv Transducers & Intelligent Control Sys, Minist Educ & Shanxi Prov, Taiyuan 030024, Shanxi, Peoples R China
[2] Taiyuan Univ Technol, Coll Elect & Power Engn, Taiyuan 030024, Shanxi, Peoples R China
[3] State Key Lab Coal & CBM Comin, Jincheng 048000, Shanxi, Peoples R China
基金
中国国家自然科学基金;
关键词
partial discharges; optical fiber sensor; ultrasound detection; time-frequency analysis; MICHELSON INTERFEROMETER; FIBER; SENSORS;
D O I
10.3390/s18051425
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Partial discharge detection is crucial for electrical cable safety evaluation. The ultrasonic signals frequently generated in the partial discharge process contains important characteristic information. However, traditional ultrasonic transducers are easily subject to strong electromagnetic interference in environments with high voltages and strong magnetic fields. In order to overcome this problem, an optical fiber Sagnac interferometer system is proposed for partial discharge ultrasound detection. Optical fiber sensing and time-frequency analysis of the ultrasonic signals excited by the piezoelectric ultrasonic transducer is realized for the first time. The effective frequency band of the Sagnac interferometer system was up to 175 kHz with the help of a designed 10 kV partial discharge simulator device. Using the cumulative histogram method, the characteristic ultrasonic frequency band of the partial discharges was between 28.9 kHz and 57.6 kHz for this optical fiber partial discharge detection system. This new ultrasound sensor can be used as an ideal ultrasonic source for the intrinsically safe detection of partial discharges in an explosive environment.
引用
收藏
页数:18
相关论文
共 50 条
  • [1] Sagnac interferometer for ultrasound detection on rough surfaces
    Fomitchov, P
    Krishnaswamy, S
    Achenbach, JD
    [J]. NONDESTRUCTIVE CHARACTERIZATION OF MATERIALS VIII, 1998, : 97 - 103
  • [2] Compact phase shifted Sagnac interferometer for ultrasound detection
    Fomitchov, PA
    Krishnaswamy, S
    Achenbach, JD
    [J]. OPTICS AND LASER TECHNOLOGY, 1997, 29 (06): : 333 - 338
  • [3] A Sagnac interferometer sensor system for intrusion detection and localization
    McAulay, AD
    Wang, J
    [J]. ENABLING PHOTONIC TECHNOLOGIES FOR AEROSPACE APPLICATIONS VI, 2004, 5435 : 114 - 119
  • [4] Fiberized Sagnac interferometer for ultrasound measurement
    Fomitchov, P
    Krishnaswamy, S
    Achenbach, JD
    [J]. REVIEW OF PROGRESS IN QUANTITATIVE NONDESTRUCTIVE EVALUATION, VOLS 15A AND 15B, 1996, 15 : 645 - 650
  • [5] Detection of terahertz pulses using a modified sagnac interferometer
    Clough B.
    Hurley D.H.
    Han P.
    Liao J.
    Huang R.
    Zhang X.-C.
    [J]. Sensing and Imaging: An International Journal, 2009, 10 (3-4) : 55 - 62
  • [6] Partial discharge detection using the fiber-optic Mach–Zehnder interferometer system for XLPE cables
    Yanpeng Hao
    Yanwen Chen
    Yun Chen
    Ying Liu
    Yanting Cheng
    Lin Yang
    Jiapeng Xiao
    Tao Huang
    [J]. Electrical Engineering, 2022, 104 : 2133 - 2140
  • [7] Partial Discharge Detection Based on Optimization of Optical Probe and Sagnac Interference
    Song, Yu
    Jiang, Jun
    He, Yaqian
    Zhou, Hongyang
    Ma, Guoming
    Li, Xiaohan
    Zhang, Dongdong
    Wang, Shuzheng
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2022, 71
  • [8] Partial Discharge Ultrasonic Detection Based on Sagnac Optical Interference Technique
    Jiang, Jun
    He, Yaqian
    Song, Yu
    Wang, Ruizhi
    Li, Xiaohan
    Ma, Guoming
    Wu, Qiang
    Liu, Jun
    [J]. IEEE SENSORS JOURNAL, 2023, 23 (22) : 27382 - 27389
  • [9] Detection limit of Sagnac's interferometer
    Palma-Vargas, Salvador
    Sandoval-Romero, G. Eduardo
    Ibarra, Angelica Ramirez
    [J]. SIXTH SYMPOSIUM: OPTICS IN INDUSTRY, 2007, 6422
  • [10] Partial discharge detection using the fiber-optic Mach-Zehnder interferometer system for XLPE cables
    Hao, Yanpeng
    Chen, Yanwen
    Chen, Yun
    Liu, Ying
    Cheng, Yanting
    Yang, Lin
    Xiao, Jiapeng
    Huang, Tao
    [J]. ELECTRICAL ENGINEERING, 2022, 104 (04) : 2133 - 2140