Frequency control is becoming increasingly critical today due to the growing size and changing structure of complex interconnected power networks. Scaling up economic pressures for efficiency and reliability of the power system has necessitated a requirement for maintaining system frequency, and tie-line power flows as close as possible to scheduled values. High-frequency deviations may degrade load performance, damage equipment, resulting in overloading of transmission lines, which may interfere with system protection schemes, and, finally, may also result in an unstable condition of the power system. More so, Load Frequency Control (LFC) plays a vital role in the modern power system as an auxiliary service to support power exchanges and, at the same time, to provide better conditions for the trading of electricity. Therefore, the tuning of the dynamic controller (i.e., net frequency and net power interchange errors) is a significant factor in achieving optimum LFC performance. Appropriate tuning of the controller parameters is required in order to achieve excellent control action. In view of this, this paper introduces the dynamic tuning of controller parameters in a two-area multi-source power system with an AC-DC parallel tie line for optimum load-frequency control performance. Matlab/Simulink software is used to realize the system simulation. System dynamic performance is observed for conventional PID tuning by the Ziegler Nichols method and the Kitamori method, fuzzy logic controllers, fuzzy-logic PID controllers, fuzzy PID controllers, and polar-Fuzzy controllers. Furthermore, the frequency and tie-line power response of the interconnected areas were compared based on the setting-time, peak-overshoot, and peak-undershoot. The simulation results show that the responses of the fuzzy-based controllers are faster than those of the classical controllers, resulting in minimized frequency and tie-line power deviations.
引用
收藏
页码:111 / 129
页数:19
相关论文
共 50 条
  • [21] Decentralized load frequency control for two-area interconnected power system
    Wang W.
    Ohmori H.
    [J]. Control Theory and Technology, 2015, 13 (02) : 101 - 114
  • [22] Intelligent Controllers for Load Frequency Control of Two-Area Power System
    Azeer, S. A.
    Ramjug-Ballgobin, R.
    Hassen, S. Z. Sayed
    [J]. IFAC PAPERSONLINE, 2017, 50 (02): : 301 - 306
  • [23] An Optimal Controller for Load Frequency Control in Multi-Area Deregulated power system
    Sina, Alireza
    Kaur, Damanjeet
    [J]. JOURNAL OF ELECTRICAL SYSTEMS, 2019, 15 (01) : 142 - 158
  • [24] Optimal Frequency Regulation of a Two-area Power System
    Hassen, S. Z. Sayed
    Jahmeerbacus, M. I.
    [J]. 2013 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY (ICIT), 2013, : 140 - 145
  • [25] Gravitational Search Algorithm (GSA) Based PID Controller Design for Two Area Multi-Source Power System Load Frequency Control (LFC)
    Safi, Shah Jahan
    Tezcan, Suleyman Sungur
    Eke, Ibrahim
    Farhad, Zakirhussain
    [J]. GAZI UNIVERSITY JOURNAL OF SCIENCE, 2018, 31 (01): : 139 - 153
  • [26] Bull-lion Optimization-based Proportional Integrated Derivative controller for regulating frequency in Two-Area Multi-Source power system
    Singh, Balvender
    Bishnoi, S. K.
    [J]. ADVANCES IN ENGINEERING SOFTWARE, 2023, 181
  • [27] Model predictive load frequency control of a two-area deregulated power system
    Ejegi, Evans E.
    Rossiter, John A.
    Trodden, Paul
    [J]. 2015 EUROPEAN CONTROL CONFERENCE (ECC), 2015, : 1044 - 1049
  • [28] Modified TID controller for load frequency control of a two-area interconnected diverse-unit power system
    Ahmed, Mohamed
    Magdy, Gaber
    Khamies, Mohamed
    Kamel, Salah
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 135
  • [29] Load Frequency Control in a Two-Area Power System with Supercapacitor Energy Storage System
    Dar, S. Zahid Nabi
    Mufti, Mairaj-ud-Din
    [J]. 2017 INTERNATIONAL CONFERENCE ON INTELLIGENT COMPUTING, INSTRUMENTATION AND CONTROL TECHNOLOGIES (ICICICT), 2017, : 710 - 714
  • [30] Equilibrium Optimizer and FLC of Two Area Load Frequency Control with Multi-Source Generators System
    Abdelwahab, Saad A. Mohamed
    Mohamed, Moayed
    Ebeed, Mohamed
    Abdellatif, Walid S. E.
    [J]. INTERNATIONAL JOURNAL OF RENEWABLE ENERGY RESEARCH, 2022, 12 (04): : 2180 - 2188