Power-over-Fiber LPIT for Voltage and Current Measurements in the Medium Voltage Distribution Networks

被引:14
|
作者
Bassan, Fabio R. [1 ]
Rosolem, Joao B. [1 ]
Floridia, Claudio [1 ]
Aires, Bruno N. [1 ]
Peres, Rodrigo [1 ]
Aprea, Javier F. [2 ]
Nascimento, Carlos Alexandre M. [3 ]
Fruett, Fabiano [4 ]
机构
[1] CPQD Res & Dev Ctr Telecommun, BR-13086902 Campinas, Brazil
[2] IMS Power Qual, BR-91160310 Porto Alegre, RS, Brazil
[3] CEMIG, BR-30190131 Belo Horizonte, MG, Brazil
[4] UNICAMP Univ Estadual Campinas, BR-13083970 Campinas, Brazil
关键词
LPIT; power-over-fiber; PoF; voltage sensor; current sensor; hybrid conductor; distribution network; optical fiber; SENSORS;
D O I
10.3390/s21020547
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
In this work, we present the design, laboratory tests, and the field trial results of a power-over-fiber (PoF) low power instrument transformer (LPIT) for voltage and current measurements in the medium voltage distribution networks. The new proposed design of this power-over-fiber LPIT aims to overcome the drawbacks presented by the previous technologies, such as the continuous operation (measuring and data transmission) for a wide current range conducted in the medium voltage transmission lines, damage due to lightning strikes, accuracy dependency on vibration, position and temperatures. The LPIT attends the accuracy criteria of IEC 61869-10 and IEC 61869-11 in terms of current and voltage accuracy and it attends the practical criteria adopted by Utilities companies including voltage measurements without removing the coating of the covered conductors. The PoF based LPIT was developed to be applied at 11.9 kV, 13.8 kV, and 23.0 kV phase-to-phase nominal voltages, and in two current ranges 1.25-30 A and 37.5-900 A. The digital data transmission of current, voltage, and temperature from the sensing unit to the processing unit uses a special synchronism technique and it is performed by two 62.5 mu m multimode fibers in 850 nm. The optical powering in 976 nm is also performed by one 62.5 mu m multimode fiber from the processing unit to the sensor unit. We presented all details of the sensor design and its laboratory characterization in terms of accuracy and temperature correction. We also presented the results of field tests of the sensor made in two different conditions: in a standard distribution network and an experimental hybrid fiber/power distribution network. We believe that these studies aim to incorporate optical fiber and devices, digital technologies, communications systems in electrical systems driving their evolution.
引用
收藏
页码:1 / 24
页数:24
相关论文
共 50 条
  • [21] Expansion Planning of Medium Voltage Distribution Networks
    Mansor, Nurulafiqah Nadzirah Binti
    Levi, Victor
    [J]. 2015 50TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC), 2015,
  • [22] Fault current limiter applications on medium and high voltage power distribution system
    Wu, AY
    Yin, YX
    [J]. CONFERENCE RECORD OF 1997 ANNUAL PULP AND PAPER INDUSTRY TECHNICAL CONFERENCE, 1997, : 179 - 185
  • [23] Undersea Medium Voltage DC Power Distribution
    Gaudreau, Marcel P. J.
    Butler, Neal
    Munderville, Matthew
    [J]. 2017 IEEE ELECTRIC SHIP TECHNOLOGIES SYMPOSIUM (ESTS), 2017, : 251 - 252
  • [24] A Power over Fiber Voltage and Current Sensor Using Multiplexed PWM Signals
    Bassan, Fabio Renato
    Rosolem, Joao Batista
    Barbosa, Celio Fonseca
    Viana Teixeira, Renan Augusto
    [J]. FIBER OPTIC SENSORS AND APPLICATIONS XV, 2018, 10654
  • [25] Assessing Losses of Power and Electrical Energy in Unbalanced Medium Voltage Distribution Networks
    Toader, C.
    Golovanov, N.
    Porumb, R.
    Tristiu, I.
    Bulac, C.
    Mandish, Al.
    Tirshu, M.
    [J]. PROBLEMELE ENERGETICII REGIONALE, 2016, (03): : 46 - 54
  • [26] Predictive Management of Medium Voltage Distribution Networks for Solar and Biomass Power Integration
    Kebir, Nisrine
    Maaroufi, Mohamed
    [J]. 2015 IEEE 15TH INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING (IEEE EEEIC 2015), 2015, : 2231 - 2235
  • [27] ANALYSIS OF UNRELIABILITY OF MEDIUM VOLTAGE POWER NETWORKS CHOSEN BRANCHES OF DISTRIBUTION COMPANIES
    Kornatka, Miroslaw
    [J]. RYNEK ENERGII, 2011, (03): : 99 - 102
  • [28] Neural voltage and current dependency on fault impedance value in medium voltage networks
    Frankovic, D.
    Marusic, A.
    [J]. Annals of DAAAM for 2005 & Proceedings of the 16th International DAAAM Symposium: INTELLIGENT MANUFACTURING & AUTOMATION: FOCUS ON YOUNG RESEARCHES AND SCIENTISTS, 2005, : 125 - 126
  • [29] Estimation of Lost Voltage Measurements in Distribution Networks
    Arguello, Andres
    Valverde, Gustavo
    [J]. 2014 NORTH AMERICAN POWER SYMPOSIUM (NAPS), 2014,
  • [30] Recent Advancement in Power-over-Fiber Technologies
    Matsuura, Motoharu
    [J]. PHOTONICS, 2021, 8 (08)