Power-over-Fiber LPIT for Voltage and Current Measurements in the Medium Voltage Distribution Networks

被引:14
|
作者
Bassan, Fabio R. [1 ]
Rosolem, Joao B. [1 ]
Floridia, Claudio [1 ]
Aires, Bruno N. [1 ]
Peres, Rodrigo [1 ]
Aprea, Javier F. [2 ]
Nascimento, Carlos Alexandre M. [3 ]
Fruett, Fabiano [4 ]
机构
[1] CPQD Res & Dev Ctr Telecommun, BR-13086902 Campinas, Brazil
[2] IMS Power Qual, BR-91160310 Porto Alegre, RS, Brazil
[3] CEMIG, BR-30190131 Belo Horizonte, MG, Brazil
[4] UNICAMP Univ Estadual Campinas, BR-13083970 Campinas, Brazil
关键词
LPIT; power-over-fiber; PoF; voltage sensor; current sensor; hybrid conductor; distribution network; optical fiber; SENSORS;
D O I
10.3390/s21020547
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
In this work, we present the design, laboratory tests, and the field trial results of a power-over-fiber (PoF) low power instrument transformer (LPIT) for voltage and current measurements in the medium voltage distribution networks. The new proposed design of this power-over-fiber LPIT aims to overcome the drawbacks presented by the previous technologies, such as the continuous operation (measuring and data transmission) for a wide current range conducted in the medium voltage transmission lines, damage due to lightning strikes, accuracy dependency on vibration, position and temperatures. The LPIT attends the accuracy criteria of IEC 61869-10 and IEC 61869-11 in terms of current and voltage accuracy and it attends the practical criteria adopted by Utilities companies including voltage measurements without removing the coating of the covered conductors. The PoF based LPIT was developed to be applied at 11.9 kV, 13.8 kV, and 23.0 kV phase-to-phase nominal voltages, and in two current ranges 1.25-30 A and 37.5-900 A. The digital data transmission of current, voltage, and temperature from the sensing unit to the processing unit uses a special synchronism technique and it is performed by two 62.5 mu m multimode fibers in 850 nm. The optical powering in 976 nm is also performed by one 62.5 mu m multimode fiber from the processing unit to the sensor unit. We presented all details of the sensor design and its laboratory characterization in terms of accuracy and temperature correction. We also presented the results of field tests of the sensor made in two different conditions: in a standard distribution network and an experimental hybrid fiber/power distribution network. We believe that these studies aim to incorporate optical fiber and devices, digital technologies, communications systems in electrical systems driving their evolution.
引用
收藏
页码:1 / 24
页数:24
相关论文
共 50 条
  • [1] Gas Insulated Medium Voltage Power Distribution Networks
    Cheetham, P.
    Stamm, T.
    Telikapalli, S.
    Mullings, A.
    Kvitkovicova, M.
    Kim, C. H.
    Pamidi, S. V.
    [J]. 2020 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2020, : 37 - 40
  • [2] Coordinated Voltage Control in Medium and Low Voltage Distribution Networks with Wind Power and Photovoltaics
    Leisse, Ingmar
    Samuelsson, Olof
    Svensson, Jorgen
    [J]. 2013 IEEE GRENOBLE POWERTECH (POWERTECH), 2013,
  • [3] Identification of the parameters of distribution networks by synchronized current and voltage measurements
    Zelenskii E.G.
    Kononov Y.G.
    Levchenko I.I.
    [J]. Russian Electrical Engineering, 2016, 87 (7) : 363 - 368
  • [4] Active power filter for medium voltage networks with predictive current control
    Verne, Santiago A.
    Valla, Maria I.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2010, 80 (12) : 1543 - 1551
  • [5] Modified unified power flow controller for medium voltage distribution networks
    Abdelrahman, Mohamed A.
    Yang, Peng
    Ming, Wenlong
    Wu, Jianzhong
    Jenkins, Nick
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2022, 16 (19) : 3849 - 3859
  • [6] Automatic Reconfiguration of Medium Voltage Power Distribution Networks in Emergency Mode
    Stefanescu, Valentin
    Antohi, Tudorel
    Poienar, Mihaela
    [J]. 2018 INTERNATIONAL CONFERENCE AND EXPOSITION ON ELECTRICAL AND POWER ENGINEERING (EPE), 2018, : 555 - 558
  • [7] Impact of Distributed Generation on Power Quality in Medium Voltage Distribution Networks
    Jusic, Alija
    Jareb, Edin
    Bajramovic, Zijad
    [J]. ADVANCED TECHNOLOGIES, SYSTEMS, AND APPLICATIONS II, 2018, 28 : 433 - 446
  • [8] Current Harmonic Estimation Techniques based on Voltage Measurements in Distribution Networks
    Yaghoobi, Jalil
    Alduraibi, Abdulrahman
    Zare, Firuz
    [J]. 2018 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2018,
  • [9] Power-Over-Fiber System With Intermittent Operation Based on Capacitor Voltage Estimation for High-Efficiency Energy Charging
    Kawano, Tomohiro
    Koyama, Ryo
    Kuroda, Akihiro
    Uematsu, Takui
    Fukai, Chisato
    Watanabe, Hiroshi
    Ogushi, Ikutaro
    [J]. IEEE ACCESS, 2024, 12 : 54999 - 55006
  • [10] Visualising the effect of DG on voltage profile in medium voltage Distribution Networks
    Nigar, Yasmin
    Agalgaonkar, A. P.
    Ciufo, Phil
    [J]. 2015 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2015,