Evaluation of low-pressure flooded evaporator performance for adsorption chillers

被引:28
|
作者
Thimmaiah, Poovanna Cheppudira [1 ]
Sharafian, Amir [1 ]
Rouhani, Mina [1 ]
Huttema, Wendell [1 ]
Bahrami, Majid [1 ]
机构
[1] Simon Fraser Univ, Sch Mechatron Syst Engn, LAEC, Burnaby, BC V3T 0A3, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Adsorption chiller; Flooded evaporator; Thermal resistance; Turbulent flow generator; Copper coating; Specific cooling power; CAPILLARY-ASSISTED EVAPORATION; AIR-CONDITIONING APPLICATIONS; FALLING-FILM EVAPORATION; COOLING SYSTEM; HEAT-TRANSFER; WASTE HEAT; REFRIGERATION SYSTEMS; HORIZONTAL TUBES; SOLAR-ENERGY; WATER;
D O I
10.1016/j.energy.2017.01.085
中图分类号
O414.1 [热力学];
学科分类号
摘要
In an adsorption chiller, the refrigerant (water) operating pressure is low (0.5-5 kPa) and the cooling power generation of a flooded evaporator is affected by the height of water column. To resolve this issue, we experimentally investigate the performance of a flooded evaporator as a function of water height. The results show an optimum water height equal to 80% of the tube diameter leading to achieve the highest cooling power. Under this condition, the internal and external thermal resistances on the inside and outside of the evaporator tubes account for up to 73% of the overall thermal resistance. To reduce the internal thermal resistance, twisted and Z-type turbulent flow generators are incorporated into the evaporator tubes. The evaporator cooling power shows an increase by 12% and 58% when twisted tape and Z-type turbulators are used at a cost of an increase in the internal pressure drop by 2.5 and 14.5 times, respectively. The twisted tape and Z-type turbulators improve the average specific cooling power of the adsorption chiller by 9% and 47%, respectively. To reduce the external thermal resistance, the outside surface of the evaporator tubes is coated with porous copper. The coated evaporator increases the overall heat transfer coefficient by 1.4 times and improves the specific cooling power of the adsorption chiller by 48% compared to the uncoated tubes. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:144 / 158
页数:15
相关论文
共 50 条
  • [1] Performance of finned tubes used in low-pressure capillary-assisted evaporator of adsorption cooling system
    Thimmaiah, Poovanna Cheppudira
    Sharafian, Amir
    Huttema, Wendell
    Osterman, Chantal
    Ismail, Ameer
    Dhillon, Aashkaran
    Bahrami, Majid
    [J]. APPLIED THERMAL ENGINEERING, 2016, 106 : 371 - 380
  • [2] Effects of Evaporator and Condenser in the Analysis of Adsorption Chillers
    Lee, Woo Su
    Park, Moon Yong
    Xuan Quang Duong
    Ngoc Vi Cao
    Chung, Jae Dong
    [J]. ENERGIES, 2020, 13 (08)
  • [4] Testing of a Falling-Film Evaporator for Adsorption Chillers
    Toppi, Tommaso
    Villa, Tommaso
    Vasta, Salvatore
    Mittelbach, Walter
    Freni, Angelo
    [J]. ENERGIES, 2022, 15 (05)
  • [5] Modelling of a falling-film evaporator for adsorption chillers
    Aprile, Marcello
    Di Cicco, Alejandro Jose
    Toppi, Tommaso
    Freni, Angelo
    Motta, Mario
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 146 : 471 - 482
  • [6] Performance evaluation of the electrical low-pressure impactor (ELPI)
    Marjamäki, M
    Keskinen, J
    Chen, DR
    Pui, DYH
    [J]. JOURNAL OF AEROSOL SCIENCE, 2000, 31 (02) : 249 - 261
  • [7] Low-Pressure Hysteresis in Adsorption: An Artifact?
    Silvestre-Albero, Ana M.
    Manuel Juarez-Galan, Juan
    Silvestre-Albero, Joaquin
    Rodriguez-Reinoso, Francisco
    [J]. JOURNAL OF PHYSICAL CHEMISTRY C, 2012, 116 (31): : 16652 - 16655
  • [8] LOW-PRESSURE ADSORPTION STORAGE OF HYDROGEN
    CHAHINE, R
    BOSE, TK
    [J]. INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 1994, 19 (02) : 161 - 164
  • [9] LOW-PRESSURE ADSORPTION HYSTERESIS IN MICROPOROUS CARBON
    MCENANEY, B
    [J]. CARBON, 1980, 18 (01) : 48 - 48
  • [10] PERFORMANCE OF LOW-PRESSURE DROP PACKINGS
    BILLET, R
    [J]. CHEMICAL ENGINEERING COMMUNICATIONS, 1987, 54 (1-6) : 93 - 118