Effects of Evaporator and Condenser in the Analysis of Adsorption Chillers

被引:5
|
作者
Lee, Woo Su [1 ]
Park, Moon Yong [1 ]
Xuan Quang Duong [1 ]
Ngoc Vi Cao [1 ]
Chung, Jae Dong [1 ]
机构
[1] Sejong Univ, Dept Mech Engn, Seoul 05006, South Korea
基金
新加坡国家研究基金会;
关键词
adsorption chiller; numerical analysis; evaporator; condenser; HEAT-EXCHANGER; CONTACT RESISTANCE; PERFORMANCE; MASS;
D O I
10.3390/en13081901
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In a survey of the literature from the last 20 years, 20% of the numerical models used to analyze the performance of adsorption chillers assumed the evaporator and condenser were ideal, with a fixed evaporation temperature and condenser temperature, and ignored interactions between the adsorption bed and evaporator/condenser. Even when the interaction with the evaporator and condenser was included, the other 80% of studies modeled the adsorption bed based on the LPM (lumped parameter method), which ignores the geometry effect and contact resistance of the bed, and thus reduces the accuracy of the analysis. As a consequence, these earlier numerical studies overestimated the system performance of the adsorption chiller. In this study, we conducted a refined numerical approach which avoids these limitations, producing estimates in close agreement with experimental results. Compared with our approach, the models with ideal treatment of evaporator and condenser overestimated COP (coefficient of performance) and SCP (specific cooling power) by as much as 16.12% and 24.64%, respectively. The models based on LPM overestimated COP and SCP by 22.82% and 11.28%, compared to our approach.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Modelling of a falling-film evaporator for adsorption chillers
    Aprile, Marcello
    Di Cicco, Alejandro Jose
    Toppi, Tommaso
    Freni, Angelo
    Motta, Mario
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 146 : 471 - 482
  • [2] Testing of a Falling-Film Evaporator for Adsorption Chillers
    Toppi, Tommaso
    Villa, Tommaso
    Vasta, Salvatore
    Mittelbach, Walter
    Freni, Angelo
    [J]. ENERGIES, 2022, 15 (05)
  • [3] Analysis of Exergy Destruction of an Evaporator or/and a Condenser
    Galovic, Antun
    Zivic, Marija
    Kokanovic, Mato
    [J]. STROJARSTVO, 2009, 51 (01): : 73 - 78
  • [4] Evaluation of low-pressure flooded evaporator performance for adsorption chillers
    Thimmaiah, Poovanna Cheppudira
    Sharafian, Amir
    Rouhani, Mina
    Huttema, Wendell
    Bahrami, Majid
    [J]. ENERGY, 2017, 122 : 144 - 158
  • [5] EVALUATION OF DIFFERENT EVAPORATOR AND CONDENSER CONCEPTS IN SEA WATER CHILLERS USING CO2 AS REFRIGERANT
    Rekstad, Inge Havard
    Ladam, Yves
    [J]. 12TH IIR GUSTAV LORENTZEN NATURAL WORKING FLUIDS CONFERENCE, 2016, : 737 - 743
  • [6] Effect of Evaporator and Condenser Temperatures on the Performance of Adsorption Desalination Cooling Cycle
    Youssef, P. G.
    Al-Dadah, R. K.
    Mahmoud, S. M.
    Dakkama, H. J.
    Elsayed, A.
    [J]. CLEAN, EFFICIENT AND AFFORDABLE ENERGY FOR A SUSTAINABLE FUTURE, 2015, 75 : 1464 - 1469
  • [7] METHOD OF CALCULATION OF CHILLERS WITH COMBINEDCOOLLED CONDENSER
    Fot, A. N.
    Vasiliev, V. K.
    [J]. PROBLEMELE ENERGETICII REGIONALE, 2014, (03): : 68 - 73
  • [8] A virtual condenser fouling sensor for chillers
    Zhao, Xinzhi
    Yang, Mo
    Li, Haorong
    [J]. ENERGY AND BUILDINGS, 2012, 52 : 68 - 76
  • [9] Numerical simulation of combined adsorption desalination and cooling cycles with integrated evaporator/condenser
    Youssef, Peter G.
    Mahmoud, Saad M.
    Al-Dadah, Raya K.
    [J]. DESALINATION, 2016, 392 : 14 - 24
  • [10] Effects of the evaporator and condenser length on the performance of pulsating heat pipes
    Wang, Jiansheng
    Ma, He
    Zhu, Qiang
    [J]. APPLIED THERMAL ENGINEERING, 2015, 91 : 1018 - 1025