Changes of insulation resistance of fire resistant cable under fire conditions

被引:0
|
作者
Polanska, M. [1 ]
Prosr, P. [2 ]
Polansky, R. [2 ]
机构
[1] Kabelovna KABEX As, Lab Thermal Analyses, Holysov, Czech Republic
[2] Univ W Bohemia, Reg Innovat Ctr Elect Engn, Plzen, Czech Republic
关键词
low-fire-hazard cable; insulation resistance; IEC; 60331-21; thermogravimetric analysis; fire retardant; ATH; FLAME-RETARDANT; NANOCOMPOSITE; POLYETHYLENE; DEGRADATION; COMPOSITES; BEHAVIOR;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Low-fire-hazard cable (LFHC) intended for low voltage applications with a fire barrier made from mica tape was tested under conditions similar to those of the fire test specified in IEC 60331-21. In addition to the other standard requirements, the measurement setup was modified to enable insulation resistance measurement throughout the entire fire test. In this manner, cable insulation as a whole can be tested under fire conditions. Results from insulation resistance measurement are supported by thermogravimetric analysis and by the data obtained from two thermocouples placed near the cable sheath and inside the cable core during the test. As results show, insulation resistance is markedly affected by the melting of the organic components of insulation, by decomposition of the flame retardant and by ignition of the core insulation along the first period of the test (10 minutes). The stable value of the insulation resistance from 10th to 90th minutes of testing, together with the insulation's behavior during cooling suggests the important role played by conductivity of the flame itself. The suggested procedure can assist in the comparison of the fire-proof functionalities of different cable designs, in the analysis of their failure mechanisms and in cable design optimization.
引用
收藏
页码:278 / 281
页数:4
相关论文
共 50 条
  • [1] Testing of the fire-proof functionality of cable insulation under fire conditions via insulation resistance measurements
    Polansky, R.
    Polanska, M.
    ENGINEERING FAILURE ANALYSIS, 2015, 57 : 334 - 349
  • [2] Changes in electrical insulation properties of fire resistant cables during a fire incident
    Polansky, Radek
    Prosr, Pavel
    Pinkerova, Martina
    Vesely, Ondrej
    PROCEEDINGS OF THE 2013 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS (ICSD 2013), VOLS 1 AND 2, 2013, : 670 - 673
  • [3] New cable insulation resists fire
    Hansen, B
    CIVIL ENGINEERING, 2005, 75 (01): : 34 - 34
  • [4] Not fire risk and fire-resistance cable NEXANS
    Nikolaev, P.V.
    Promyshlennaya Energetika, 2001, (06): : 39 - 42
  • [5] REDUCING SPREAD OF FIRE BY PVC CABLE INSULATION
    PHILBRICK, SE
    ELECTRICAL REVIEW, 1972, 190 (11): : 363 - +
  • [6] Insulation Failure Mechanism of Cable in Fire Environment
    Li, Qiang
    Zhang, Jiaqing
    Li, Jinmei
    Yang, Yichen
    Fan, Minghao
    ADVANCED FUNCTIONAL MATERIALS (CMC 2017), 2018, : 909 - 917
  • [7] Experimental study of fire resistant board configurations under standard fire conditions
    Steau, Edward
    Mahendran, Mahen
    Poologanathan, Keerthan
    FIRE SAFETY JOURNAL, 2020, 116
  • [8] FOAM INSULATION BEHAVIOR IN VOID SPACE UNDER FIRE CONDITIONS
    Kurzawski, Andrew
    Ezekoye, Ofodike A.
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2014, VOL 8B, 2015,
  • [9] Fire resistance without fire resistant glazing
    Koudijs, Johan
    Csoke, Csilla
    1ST INTERNATIONAL SEMINAR FOR FIRE SAFETY OF FACADES, 2013, 9
  • [10] Fire Resistance Without Fire Resistant Glazing
    Csoke, Csilla
    Koudijs, Johan
    CHALLENGING GLASS 3, 2012, : 925 - 931