Parametrization of ground-fault relays in MV distribution networks with resonant grounding

被引:2
|
作者
Polajzer, Bostjan [1 ]
Pintaric, Matej [1 ]
Ribic, Janez [1 ]
Roser, Miran [2 ]
Stumberger, Gorazd [1 ]
机构
[1] Univ Maribor, Fac Elect Engn & Comp Sci, Koroska 46, Maribor 2000, Slovenia
[2] Elektro Celje Dd, Vrunceva 2a, Celje 3000, Slovenia
关键词
Phase-to-ground faults; Resonantly grounded networks; Ground-fault relay; Timing coordination; PROTECTION;
D O I
10.1016/j.ijepes.2022.108449
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a methodology for the parametrization of Ground-Fault Relays (GFRs) in medium-voltage distribution networks with resonant grounding. In these networks, a Petersen coil suppresses the self-distinguishing Phase-to-Ground (Ph-G) faults, whereas permanent Ph-G faults are detected by connecting a low-ohmic grounding resistor in parallel with the Petersen coil, thus enabling the operation of the assigned GFRs. The proposed methodology assures the security of the GFRs by considering the transient response of residual (zero-sequence) currents before the connection of a grounding resistor. Furthermore, safety is assured through the maximum-allowed operating times of the GFRs, given by the dangerous touch and step voltages, which are critical for back-up GFRs during distant Ph-G faults. The selectivity is achieved through timing coordination of the GFRs' operation, using self-adaptive differential evolution and variable penalties. The proposed optimization model minimizes the pick-up-current settings together with the GFRs' operating times for metallic and resistive Ph-G faults, thus increasing the sensitivity considerably. For radial network topologies the proposed methodology assures reliable and safe GFR operations for Ph-G faults with a resistance of up to 100 Omega. Moreover, since the dependability of distant in-loop GFRs is questionable, a communication-assisted solution is proposed based on a directional criterion.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Parametrization of ground-fault relays in MV distribution networks with resonant grounding
    Polajžer, Boštjan
    Pintarič, Matej
    Ribič, Janez
    Rošer, Miran
    Štumberger, Gorazd
    International Journal of Electrical Power and Energy Systems, 2022, 143
  • [2] Evaluation of the Grounding Circuit Measurements for Stator Ground-Fault Location of Synchronous Generators
    Blanquez, F. R.
    Rebollo, E.
    Platero, C. A.
    2013 13TH INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING (EEEIC), 2013, : 229 - 233
  • [3] GROUNDING AND GROUND-FAULT PROTECTION FOR COGENERATION AND PEAK-SHAVING SYSTEMS.
    Regan, Ronald R.
    Williamson, Ronald H.
    Electr Syst Des, 1986, 66 (05):
  • [4] System grounding and ground-fault protection in the petrochemical industry: A need for a better understanding
    Nelson, JP
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (06) : 1633 - 1640
  • [5] Ground Fault Detection Based on Fault Data Stitching and Image Generation of Resonant Grounding Distribution Systems
    Nie, Xianglun
    Zhang, Jing
    He, Yu
    Luo, Wenjian
    Gu, Tingyun
    Li, Bowen
    Hu, Xiangxie
    ENERGIES, 2023, 16 (07)
  • [6] Ground-fault currents in unit-connected generators with different elements grounding neutral
    Fulczyk, M
    Bertsch, J
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2002, 17 (01) : 61 - 66
  • [7] Impact of the Main Bonding Jumper and the Equipment Grounding Conductor on Ground-Fault Circuit Interrupters
    Rubio Perez, Maria Camila
    Ramos, Gustavo
    2018 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING (IAS), 2018,
  • [8] Line selection method for grounding fault in resonant grounding distribution systems
    Long R.
    Huang C.
    Tang T.
    Zeng J.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2019, 47 (21): : 21 - 29
  • [9] Ground-fault Location Algorithm for Ungrounded Radial Distribution Systems
    Soon-Ryul Nam
    Sang-Hee Kang
    Jin-Man Sohn
    Jong-Keun Park
    Electrical Engineering, 2007, 89 : 503 - 508
  • [10] Single-phase-to-ground fault section location in flexible resonant grounding distribution networks using soft open points
    Li, Zhengtian
    Ye, Yuqing
    Ma, Xiao
    Lin, Xiangning
    Xu, Feng
    Wang, Chaoliang
    Ni, Xiaojun
    Ding, Chao
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 122 (122)