Air tightness measurement with transient methods using sudden expansion from a compressed chamber

被引:12
|
作者
Lee, Min Jung [1 ]
Kim, Nam Il [1 ]
Ryou, Hong Sun [1 ]
机构
[1] Chung Ang Univ, Sch Mech Engn, Seoul 156756, South Korea
关键词
Fire safety; Air tightness measurement; Effective leakage area; Smoke suppression; LEAKAGES; HOUSES; FIRE;
D O I
10.1016/j.buildenv.2011.04.001
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Air tightness in an escape route of a building is important in preventing a fatal disaster by smoke spreading during a fire. To measure air tightness, transient methods using sudden air expansion from a small compressed air chamber into a room are proposed. Pressure variations in the chamber and the room are measured, and effective leakage areas are evaluated using differential and integral transient methods. The results of the two transient methods are compared with results from a typical steady method using an external blower fan. As a result, it was confirmed that all three experimental methods show good linearity between the imposed open hole area and the estimated effective leakage area. Therefore, the effective leakage area estimated using the transient methods could be converted to the equivalent leakage area of the steady method. The transient methods proposed in this study are expected to be more conveniently adopted for measuring air tightness if a suitable conversion factor is preliminarily evaluated. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1937 / 1945
页数:9