Permanent Single-Line-to-Ground Fault Removal Method for Ferro-Resonance Avoidance in Neutral Ungrounded Distribution Network

被引:5
|
作者
Lu, Pan [1 ]
Wang, Wen [1 ]
Yu, Qian [2 ]
Fan, Bishuang [1 ]
Liu, Pengfei [3 ]
Wang, Faliang [4 ]
Zeng, Xiangjun [1 ]
机构
[1] Changsha Univ Sci & Technol, Coll Elect & Informat Engn, Changsha 410114, Peoples R China
[2] Hunan Univ Finance & Econ, Coll Business Adm, Changsha 410205, Peoples R China
[3] State Grid Hunan Elect Power Co, Yongzhou 410029, Peoples R China
[4] State Grid Jiangxi Elect Power Co, Yichun 336000, Peoples R China
基金
中国国家自然科学基金;
关键词
Circuit faults; Ferroresonance; Voltage; Inductance; Capacitance; Distribution networks; Resistance; Distribution network; permanent single-line-to-ground fault; ferroresonance avoidance; fault removal instant; FERRORESONANCE; VOLTAGE; TRANSFORMERS; SERIES; SYSTEM;
D O I
10.1109/ACCESS.2022.3175513
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In the neutral ungrounded distribution network, the removal of permanent single-line-to-ground (SLG) fault easily leads to saturation of the electromagnetic voltage transformers (PT), which may cause ferroresonance overvoltage and PT failure. This paper analyzes the zero-sequence voltage after the removal of the SLG fault and reveals the mechanism of ferroresonance excited by the removal of the SLG fault. Then, the total power and transient energy of the zero-sequence circuit under the SLG fault are analyzed. It is deduced that the energy reaches the minimum value at the zero-cross point (ZCP) of the neutral voltage. Based on this, a permanent SLG fault removal method to avoid ferroresonance is proposed, which uses the ZCP point as the fault removal instant. Simulations in ATP-EMTP show that the proposed method can effectively avoid ferroresonance on subharmonic mode. It can also enhance the ferroresonance suppression performance of the ferroresonance suppression resistor in the fundamental-frequency and high-frequency conditions.
引用
下载
收藏
页码:53724 / 53734
页数:11
相关论文
共 50 条
  • [21] New algorithm for the single-line-to-ground fault location in the 10kV or 6kV direct distribution line
    Shu, Hongchun
    Xu, Chengbin
    Xu, Xianmin
    Chen, Xueyun
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 1995, 15 (06): : 423 - 428
  • [22] Zero-sequence voltage trajectory analysis for unbalanced distribution networks on single-line-to-ground fault condition
    Meng, Jun
    Wang, Wen
    Tang, Xin
    Xu, Xianyong
    ELECTRIC POWER SYSTEMS RESEARCH, 2018, 161 : 17 - 25
  • [23] Location of Single-Line-to-Ground Fault Using 1-D Convolutional Neural Network and Waveform Concatenation in Resonant Grounding Distribution Systems
    Guo, Mou-Fa
    Gao, Jian-Hong
    Shao, Xiang
    Chen, Duan-Yu
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2021, 70
  • [24] A novel fault line selection algorithm of single-phase ground faults in ungrounded neutral system using wavelets transform
    Shu, HC
    Xiao, B
    POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, 2002, : 2532 - 2536
  • [25] Faulted feeder identification and location for a single line-to-ground fault in ungrounded distribution system based on principal frequency component
    Liu, Ling
    ARCHIVES OF ELECTRICAL ENGINEERING, 2020, 69 (03) : 695 - 704
  • [26] Single Line to Ground Fault Detection in a Non-Effectively Grounded Distribution Network
    Wang, Xiaowei
    Gao, Jie
    Wei, Xiangxiang
    Zeng, Zhihui
    Wei, Yanfang
    Kheshti, Mostafa
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) : 3173 - 3186
  • [27] Estimation of Single Line to Ground Fault Location in Unearthed Medium Voltage Distribution Network
    Adzman, Mohd Rafi
    Lehtonen, Matti
    PROCEEDINGS OF THE 13TH INTERNATIONAL SCIENTIFIC CONFERENCE ELECTRIC POWER ENGINEERING 2012, VOLS 1 AND 2, 2012, : 9 - 15
  • [28] Single-phase Ground Fault Line Selection for Distribution Network Based on Frequency Domain Parameter Identification Method
    Cheng, Siwen
    Fu, Zhouxing
    2019 3RD INTERNATIONAL WORKSHOP ON RENEWABLE ENERGY AND DEVELOPMENT (IWRED 2019), 2019, 267
  • [29] Relay Setting Guidelines for Single-Line Ground Fault Detection in Ungrounded Distribution Systems within High-Voltage Customer Premises
    Koo D.-H.
    Kim J.-B.
    Park K.-J.
    Lee M.-G.
    Kim J.-E.
    Transactions of the Korean Institute of Electrical Engineers, 2024, 73 (03): : 637 - 645
  • [30] Novel method of fault line selection by transient component for single-phase to ground fault in distribution networks
    College of Information and Control Engineering, China University of Petroleum, Dongying 257061, China
    Zhongguo Shiyou Daxue Xuebao (Ziran Kexue Ban), 2006, 3 (135-139+143):