Optimum operation of open-loop ground heat exchanger considering subsurface temperature gradient

被引:6
|
作者
Choi, Hyun-Jun [1 ]
Park, Sangwoo [1 ]
Lee, Hyungi [1 ]
Khanh Linh Nguyen Pham [1 ]
Ryu, Hyungkyou [2 ]
Choi, Hangseok [1 ]
机构
[1] Korea Univ, Sch Civil Environm & Architectural Engn, Seoul, South Korea
[2] Korea Inst Mech Facil Ind, Off Facil Technol Res, Seoul, South Korea
基金
新加坡国家研究基金会;
关键词
open-Loop ground heat exchanger; standing column well; LMTD; Entering water temperature; thermal response test; THERMAL PERFORMANCE; PUMP; PILE;
D O I
10.1002/er.3435
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposes an optimum operation method for open-loop ground heat exchangers (GHEX) considering the subsurface temperature gradient. A series of thermal response tests and artificial heating/cooling operations was carried out along with monitoring temperatures in the standing column well. The underground temperature naturally increases with depth, but a switch between the cooling and heating modes can alter the temperature distribution. The effect of the mode change was evaluated by performing logarithmic mean temperature difference (LMTD) and computational fluid dynamics (CFD) analyses for a reduced (or physical) model with the well depth of 150m. As a result, in the cooling mode, the upstream operation is more efficient than the downstream operation and reduces entering water temperature (EWT) by 2.26 degrees C. On the other hand, in the heating mode, the downstream operation is advantageous over the upstream operation and increases EWT by 3.19 degrees C. According to the results of the LMTD and CFD analysis, the thermal conductivity of the ground formation and the flow direction of water are the most important factors in the open-loop GHEX. Finally, an optimum flow direction with respect to each operation is proposed to enhance its efficiency; thus, a new GHEX system is flexible to a change in the flow direction. Copyright (c) 2015 John Wiley & Sons, Ltd.
引用
收藏
页码:651 / 661
页数:11
相关论文
共 50 条
  • [31] Design Issues in Commercial Open-Loop Heat Pump Systems
    Rafferty, Kevin
    ASHRAE TRANSACTIONS 2008, VOL 114, PT 2, 2008, 114 : 316 - 327
  • [32] Open-loop operation of MEMS WDM routers with analog micromirror array
    Huang, S
    Tsai, JC
    Hah, D
    Toshiyoshi, H
    Wu, MC
    2002 IEEE/LEOS INTERNATIONAL CONFERENCE ON OPTICAL MEMS, CONFERENCE DIGEST, 2002, : 179 - 180
  • [33] Effect of process design/operation on the open-loop operability of a polymerization reactor
    Flores-Tlacuahuac, A
    Silva-Beard, A
    COMPUTERS & CHEMICAL ENGINEERING, 1998, 22 : S703 - S706
  • [34] Stacked Open-Loop Square Ring Antenna for Circular Polarization Operation
    Seo, D. C.
    Sung, Y.
    IEEE ANTENNAS AND WIRELESS PROPAGATION LETTERS, 2015, 14 : 835 - 838
  • [35] Planar Multibranch Open-Loop Robotic Manipulators Subjected to Ground Collision
    Shafei, A. M.
    Shafei, H. R.
    JOURNAL OF COMPUTATIONAL AND NONLINEAR DYNAMICS, 2017, 12 (06):
  • [36] ANALYSIS OF HEAT EXCHANGER CONSIDERING THE TEMPERATURE DISTRIBUTION PERPENDICULAR TO HEAT EXCHANGER SURFACE.
    Yamashita, Hiroshi
    Izumi, Ryotaro
    Yamaguchi, Shigeki
    1978, 21 (157): : 1168 - 1174
  • [37] Evaluation of Analytical and Numerical Techniques for Defining the Radius of Influence for an Open-Loop Ground Source Heat Pump System
    Freedman, Vicky L.
    Mackley, Rob
    Waichler, Scott R.
    Horner, Jake
    JOURNAL OF HYDROLOGIC ENGINEERING, 2013, 18 (09) : 1170 - 1179
  • [38] Mapping suitability for open-loop ground source heat pump systems: a screening tool for England and Wales, UK
    Abesser, Corinna
    Lewis, Melinda A.
    Marchant, Andrew P.
    Hulbert, Andrew G.
    QUARTERLY JOURNAL OF ENGINEERING GEOLOGY AND HYDROGEOLOGY, 2014, 47 (04) : 373 - 380
  • [39] Free Convection and Heat Transfer in Porous Ground Massif during Ground Heat Exchanger Operation
    Basok, Borys
    Davydenko, Borys
    Koshlak, Hanna
    Novikov, Volodymyr
    MATERIALS, 2022, 15 (14)
  • [40] Operation characteristics and experience of a ground source heat pump system with a vertical ground heat exchanger
    Michopoulos, A.
    Zachariadis, T.
    Kyriakis, N.
    ENERGY, 2013, 51 : 349 - 357