Effects of the operation parameters of a closed-type heating tower on the performance of heating tower heat pump system

被引:0
|
作者
Rong, Feng [1 ,2 ]
Li, Xiuzhen [3 ]
Zhao, Xingcheng [1 ]
Fang, Junfei [1 ,2 ]
机构
[1] Shaanxi Univ Technol, Sch Mech Engn, Hanzhong, Peoples R China
[2] Shaanxi Key Lab Ind Automat, Hanzhong, Peoples R China
[3] Henan Univ Sci & Technol, Inst Refrigerat & Air Conditioning, Luoyang, Peoples R China
基金
中国国家自然科学基金;
关键词
Closed-type heating tower; operation parameters; heat pump system; energy efficiency; coefficient of performance; MASS-TRANSFER CHARACTERISTICS; COOLING-TOWER; FLOW; AIR;
D O I
10.1177/0144598720933698
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The ventilator of the heating tower and the circulating pump of the anti-freeze solution are the main electrical equipment of a heating tower heat pump system, besides the compressor. By controlling the working frequencies of the ventilator of the heating tower and circulating pump of the anti-freeze solution, the effects of the operation parameters of a closed-type heating tower on its heat absorption and the performance of heating tower heat pump system were investigated under winter heat conditions. The results indicated that reducing the frequency of the circulating pump for the anti-freeze solution leads to a decrease in the temperature of the outlet evaporator of the anti-freezing solution and an increased temperature difference between the anti-freeze solution flowing into and out of the heating tower; meanwhile, excessively high and low anti-freeze flow rates lead to reduced heat absorption of the closed-type heating tower. The coefficient of performance fluctuates slightly if the frequency of circulating pump is above 20 Hz, but a slight drop in coefficient of performance is observed when the frequency is less than 15 Hz. The system energy efficiency ratio tends to increase as the frequency of circulating pump is reduced, although a substantial reduction occurs at 10 Hz. Furthermore, a reduced ventilator frequency decreases the temperatures of the anti-freeze solution at the inlet and outlet of the heating tower and the temperature difference, hindering the heat absorption of the heating tower. With reductions in the ventilator frequency, the coefficient of performance exhibits an initial increase followed by subsequent decreases, while the system energy efficiency ratio showed continual increases until the ventilator frequency dropped to 10 Hz. When the ventilator frequency or circulating pump frequency drops to 15 Hz and 10 Hz, the evaporation temperature of the heat pump unit decreases, resulting in an excessively exhaust temperature, which is not favorable for the safe operation of the system.
引用
收藏
页码:1983 / 1997
页数:15
相关论文
共 50 条
  • [1] Heating performance of solar assisted closed-type heating tower heat pump system in winter
    Feng R.
    Liu Y.
    Fang J.
    Meng X.
    [J]. Nongye Gongcheng Xuebao/Transactions of the Chinese Society of Agricultural Engineering, 2020, 36 (11): : 210 - 217
  • [2] Experimental investigation on closed-type heating tower using glycerol solution
    Song, Pengyuan
    Xiao, Hansong
    Shi, Wenxing
    Li, Xianting
    Wang, Baolong
    Li, Zhiming
    Zhang, Yong
    Zhong, Huian
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 99 : 272 - 287
  • [3] OPERATION EFFICIENCY PERFORMANCE OF MULTI-MODE REGENERATION HEATING TOWER HEAT PUMP SYSTEM
    Zhao S.
    Zhang X.
    Liang C.
    Huang S.
    [J]. Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (07): : 107 - 115
  • [4] Performance investigation of a multi-connected heating tower heat pump system
    Hu, Han
    Ji, Jianzhou
    Xie, Lingyun
    Le, Yi
    Zhang, Xiaosong
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 135 : 154 - 163
  • [5] Sensitivity analysis and optimization of design parameters of heating tower heat pump
    Xie, Lingyun
    Zhang, Muxing
    Huang, Shifang
    Zhao, Shanguo
    Zhang, Xiaosong
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2022, 258
  • [6] Model-based optimal operation of heating tower heat pump systems
    Huang, Shifang
    Lu, Xing
    Zuo, Wangda
    Zhang, Xiaosong
    Liang, Caihua
    [J]. BUILDING AND ENVIRONMENT, 2019, 160
  • [7] Experimental Study on Optimal Operation of Heating Tower Heat Pump in Summer Condition
    Huang, Shi-Fang
    Xie, Ling-Yun
    Bing, Yi-Wei
    Liang, Cai-Hua
    Zhang, Xiao-Song
    [J]. Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2020, 41 (03): : 621 - 627
  • [8] Performance evaluation of heating tower heat pump systems over the world
    Huang, Shifang
    Ye, Yunyang
    Han, Xu
    Zuo, Wangda
    Zhang, Xiaosong
    Jiang, Li
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2019, 186 : 500 - 515
  • [9] A Study of the Mechanical Draft Heating/Cooling Tower Heat Pump System
    Luo, Yi
    Ma, Rongsheng
    Ding, Xingfeng
    Wang, Zhilin
    [J]. 6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 702 - 707
  • [10] Experimental Study on Solution Regeneration Performance of Closed-type Heat-source Tower
    Song, Pengyuan
    Li, Xianting
    Wang, Baolong
    Shi, Wenxing
    [J]. 10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 446 - 452