Numeral analysis model for shielding failure of transmission line under lightning stroke

被引:82
|
作者
He, JL [1 ]
Tu, YP
Zeng, R
Lee, JB
Chang, SH
Guan, ZC
机构
[1] Tsinghua Univ, Dept Elect Engn, Beijing 100084, Peoples R China
[2] N China Elect Power Univ Beijing, Dept Elect Engn, Beijing 102206, Peoples R China
[3] Korea Electrotechnol Res Inst, Elect Environm & Transmiss Grp, Chang Won 641600, South Korea
关键词
critical breakdown electrical field; electrical field; electrogeometric model; lightning leader; numerical analysis model; shielding failure; transmission line;
D O I
10.1109/TPWRD.2004.839189
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The shielding failure is the occurrence of a lightning stroke that bypasses the overhead ground wires and terminates on the phase conductors. The correct design to improve the shielding effect of transmission line to lightning is one of the key problems of transmission line design. A numerical analysis model for shielding failure of transmission line based on electromagnetic field theory is proposed in this paper. The electrical field of the system including lightning leader, transmission line and ground is solved, the range of lightning current striking the phase conductor is obtained, and the shielding failure probability of transmission line is calculated. The lightning leader model and the critical breakdown electrical field intensity of long gap are discussed. The analyzed results by numerical analysis model are compared with those by the electro-geometric model.
引用
收藏
页码:815 / 822
页数:8
相关论文
共 50 条
  • [21] Simulation model of lightning stroke to a transmission line considering the leader propagation randomicity
    Jiang, Zhenglong
    Lin, Fuchang
    Dai, Ling
    Li, Hua
    Han, Yongxia
    Kang, Ren
    Yu, Hui
    Ye, Huisheng
    2007 CONFERENCE PROCEEDINGS IPEC, VOLS 1-3, 2007, : 1282 - +
  • [22] Calculation Research on Influence of Adjacent Lines on Lightning Shielding Failure of ±1100 kV DC Transmission Line
    Wen X.
    Deng Y.
    Wang L.
    He H.
    Wang Y.
    Sun Z.
    Wang, Yu (wy_20002@163.com), 1600, Power System Technology Press (41): : 3420 - 3426
  • [23] An optimized transmission line model of grounding electrodes under lightning currents
    YANG Lin
    WU GuangNing
    CAO XiaoBin
    Science China(Technological Sciences) , 2013, (02) : 335 - 341
  • [24] An optimized transmission line model of grounding electrodes under lightning currents
    Yang Lin
    Wu GuangNing
    Cao XiaoBin
    SCIENCE CHINA-TECHNOLOGICAL SCIENCES, 2013, 56 (02) : 335 - 341
  • [25] An optimized transmission line model of grounding electrodes under lightning currents
    YANG Lin
    WU GuangNing
    CAO XiaoBin
    Science China(Technological Sciences), 2013, 56 (02) : 335 - 341
  • [26] An optimized transmission line model of grounding electrodes under lightning currents
    Lin Yang
    GuangNing Wu
    XiaoBin Cao
    Science China Technological Sciences, 2013, 56 : 335 - 341
  • [27] Discussion on Tower Shunt Coefficient of UHV DC Transmission Line under Lightning Stroke
    Chen, S.
    Hu, J.
    Zhang, B.
    Yin, Y.
    Hua, M.
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 1983 - 1986
  • [28] Study of Lightning Stroke Trip-out Fault Analysis for Transmission Line
    Li, Xiaolan
    Chen, Jiahong
    Gu, Shanqiang
    2016 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2016, : 2296 - 2300
  • [29] Transmission line sag influence on lightning stroke probability
    Alush, S.
    Braunstein, A.
    Elmakias, D.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2012, 6 (10) : 1046 - 1052
  • [30] Analysis of Lightning Shielding Failure for 500-kV Overhead Transmission Lines Based on an Improved Leader Progression Model
    Wei, Bengang
    Fu, Zhengcai
    Yuan, Haiyan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) : 1433 - 1440