A transformer differential relay based on a multiple park transformation

被引:0
|
作者
Guerreiro, Manuel [1 ]
Pires, V. Fernao [2 ]
机构
[1] Inst Politecn Setubal, Escola Sup Tecnol Setubal, Setubal, Portugal
[2] LabSEI Lab Sist Elect Ind, Setubal, Portugal
关键词
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Discrimination between an internal fault and a magnetizing inrush current has been recognized as a power transformer protection problem, since can cause malfunction of a differential relay. To overcome this problem the paper proposes a new approach for transformer differential protection. This approach is based on the Park transformation of the differential currents. Using this technique each harmonic that must be used for the protection will be converted in a dc component. So, one of the advantages of this approach is that the proposed algorithm does not require a very high computational effort. The evaluation of this technique is performed by a Matlab/Simulink-based simulator. From the obtained results it is possible to verify that the relay can correctly discriminates magnetic inrush from an internal fault.
引用
收藏
页码:400 / +
页数:2
相关论文
共 50 条
  • [31] MATLAB-SIMULINK-based simulation for digital differential relay protection of power transformer for educational purpose
    Vahidi, B.
    Esmaeeli, E.
    [J]. COMPUTER APPLICATIONS IN ENGINEERING EDUCATION, 2013, 21 (03) : 475 - 483
  • [32] The Improvement of the Digital Differential Relay in On-load Tap Changer Transformer
    Zhao, W. K.
    He, J. H.
    Bo, Z. Q.
    Kimek, A.
    [J]. 2009 INTERNATIONAL CONFERENCE ON SUSTAINABLE POWER GENERATION AND SUPPLY, VOLS 1-4, 2009, : 2195 - +
  • [33] Fuzzy logic based relay for power transformer protection
    Saha, Murari M.
    Hillstrom, Birger
    Kasztenny, Bogdan
    Rosolowski, Eugeniusz
    [J]. ABB Review, 1998, (01): : 41 - 48
  • [34] MICROPROCESSOR-BASED OVERFLUXING RELAY FOR A GENERATOR TRANSFORMER
    VERMA, HK
    BASHA, AM
    [J]. JOURNAL OF MICROCOMPUTER APPLICATIONS, 1987, 10 (03): : 229 - 236
  • [35] A KALMAN FILTER BASED DIGITAL PERCENTAGE DIFFERENTIAL AND GROUND FAULT RELAY FOR A 3-PHASE POWER TRANSFORMER
    MURTY, YVVS
    SMOLINSKI, WJ
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (03) : 1299 - 1308
  • [36] DESIGN AND IMPLEMENTATION OF A DIGITAL DIFFERENTIAL RELAY FOR A 3-PHASE POWER TRANSFORMER BASED ON KALMAN FILTERING THEORY
    MURTY, YVVS
    SMOLINSKI, WJ
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (02) : 525 - 533
  • [37] A NEW COMPUTER-BASED FLUX-RESTRAINED CURRENT-DIFFERENTIAL RELAY FOR POWER TRANSFORMER PROTECTION
    PHADKE, AG
    THORP, JS
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (11): : 3624 - 3629
  • [38] Differential relay reliability enhancement using fourth harmonic for a large power transformer
    Bouderbala R.
    Bentarzi H.
    [J]. International Journal of System Assurance Engineering and Management, 2017, 8 (Suppl 2) : 592 - 598
  • [39] A Detailed Testing Procedure of Numerical Differential Protection Relay for EHV Auto Transformer
    Ehsan, Umer
    Jawad, Muhammad
    Javed, Umar
    Shabih Zaidi, Khurram
    Ur Rehman, Ateeq
    Rassolkin, Anton
    Althobaiti, Maha M.
    Hamam, Habib
    Shafiq, Muhammad
    [J]. ENERGIES, 2021, 14 (24)
  • [40] Analysis of a main transformer's differential relay operation in a 110 kV substation
    Wang, Guang-Zhong
    Hao, Jian-Hong
    Wang, Shu-Jun
    Fan, Ping
    [J]. Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (04): : 134 - 136