Flow and Containment Characteristics of an Air-curtain Fume Hood Operated at High Temperatures

被引:5
|
作者
Chen, Jia-Kun [2 ]
Huang, Rong Fung [1 ]
Hsin, Pei-Yi [1 ]
Hsu, Ching Min [2 ]
Chen, Chun-Wann [3 ]
机构
[1] Natl Taiwan Univ Sci & Technol, Dept Mech Engn, Taipei, Taiwan
[2] Natl Taiwan Univ Sci & Technol, Grad Inst Appl Sci & Technol, Taipei, Taiwan
[3] Council Labor Affairs, Inst Occupat Safety & Hlth, Shijr City, Taipei County, Taiwan
关键词
Air-curtain fume hood; Flow visualization; Tracer-gas test; High temperature operation; AIRBORNE NANOPARTICLE EXPOSURES; PERFORMANCE; CUPBOARDS;
D O I
10.2486/indhealth.MS1326
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The flow and leakage characteristics of the air-curtain fume hood under high temperature operation (between 100 degrees C and 250 degrees C) were studied. Laser-assisted flow visualization technique was used to reveal the hot plume movements in the cabinet and the critical conditions for the hood-top leakage. The sulfur hexafluoride tracer-gas concentration test method was employed to examine the containment spillages from the sash opening and the hood top. It was found that the primary parameters dominating the behavior of the flow field and hood performance are the sash height and the suction velocity as an air-curtain hood is operated at high temperatures. At large sash height and low suction velocity, the air curtain broke down and accompanied with three-dimensional flow in the cabinet. Since the suction velocity was low and the sash opening was large, the makeup air drawn down from the hood top became insufficient to counter act the rising hot plume. Under this situation, containment leakage from the sash opening and the hood top was observed. At small sash opening and high suction velocity, the air curtain presented robust characteristics and the makeup air flow from the hood top was sufficiently large. Therefore the containment leakages from the sash opening and the hood top were not observed. According to the results of experiments, quantitative operation sash height and suction velocity corresponding to the operation temperatures were suggested.
引用
收藏
页码:103 / 114
页数:12
相关论文
共 50 条