On the effective thermal conductivity of wetted zeolite under the working conditions of an adsorption chiller

被引:37
|
作者
Dawoud, B. [2 ]
Sohel, M. Imroz [3 ]
Freni, A. [1 ]
Vasta, S. [1 ]
Restuccia, G. [1 ]
机构
[1] CNR Ist Tecnol Avanzate Nicola Giordano, Via S Lucia S Contesse, I-98126 Messina, Italy
[2] Viessmann Werke Allendorf GmbH, D-35107 Allendorf Eder, Germany
[3] Univ Canterbury, Dept Mech Engn, Christchurch 1, New Zealand
关键词
Adsorption Chiller; Thermal conductivity; Wetted zeolite; HEAT-PUMP; SILICA; WATER; REFRIGERATION; ADSORBENT; SORPTION;
D O I
10.1016/j.applthermaleng.2011.03.016
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a theoretical model for predicting the effective thermal conductivity of wetted zeolite. The model comprises the thermal conductivities of the zeolite crystal as well as of the adsorbed water. The temperature dependence of both thermal conductivities is considered. Moreover, the contribution to the effective thermal conductivity due to vapor conductance is also taken into account. The effective thermal conductivity of 4A zeolite-water is measured by transient "hot wire" method under various conditions of vapor pressure, temperature and water loading. The measurement ranges are chosen according to the operating conditions of a typical adsorption cooling cycle. The experimentally measured data are fitted to the proposed theoretical model. The maximum deviation between the experimental results and the theoretical values is estimated to be +/- 5.8%. The validated model is used to realize a zeolite 4A conductivity chart, which represents an useful tool for thermal design of adsorption machines. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2241 / 2246
页数:6
相关论文
共 50 条
  • [1] Prediction of the effective thermal conductivity of an adsorption bed packed with 5A zeolite particles under working conditions
    Wang, H.
    Qu, Z. G.
    Yin, Y.
    Bai, J. Q.
    He, C.
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2021, 159
  • [2] Thermal conductivity of selective water sorbents under the working conditions of a sorption chiller
    Freni, A
    Tokarev, MM
    Restuccia, G
    Okunev, AG
    Aristov, YI
    APPLIED THERMAL ENGINEERING, 2002, 22 (14) : 1631 - 1642
  • [3] EFFECTIVE THERMAL-CONDUCTIVITY OF WETTED ANTIGRANULOCYTES BEDS
    TANAKA, M
    KAGAKU KOGAKU RONBUNSHU, 1991, 17 (02) : 445 - 447
  • [4] APPROXIMATE METHOD FOR PREDICTION OF EFFECTIVE THERMAL-CONDUCTIVITY OF WETTED POROUS MATERIALS
    PALOSAARI, SM
    CORNISH, ARH
    ACTA POLYTECHNICA SCANDINAVICA-CHEMICAL TECHNOLOGY SERIES, 1975, (126): : 1 - 24
  • [5] Dynamic Performance Analysis for an Absorption Chiller under Different Working Conditions
    Wang, Jian
    Shang, Sheng
    Li, Xianting
    Wang, Baolong
    Wu, Wei
    Shi, Wenxing
    APPLIED SCIENCES-BASEL, 2017, 7 (08):
  • [6] Effect of Residual Gas on Water Adsorption Dynamics Under Typical Conditions of an Adsorption Chiller
    Glaznev, Ivan
    Ovoshchnikov, Daniil
    Aristov, Yuriy
    HEAT TRANSFER ENGINEERING, 2010, 31 (11) : 924 - 930
  • [7] Prediction of effective thermal conductivity of consolidated porous materials under ambient conditions
    Zeb, A.
    Misbah
    Maqsood, A.
    INDIAN JOURNAL OF PHYSICS, 2014, 88 (06) : 603 - 607
  • [8] Determination of the effective thermal conductivity of granular materials under varying pressure conditions
    Huetter, E. S.
    Koemle, N. I.
    Kargl, G.
    Kaufmann, E.
    JOURNAL OF GEOPHYSICAL RESEARCH-PLANETS, 2008, 113 (E12)
  • [9] Prediction of effective thermal conductivity of consolidated porous materials under ambient conditions
    A Zeb
    A Misbah
    Indian Journal of Physics, 2014, 88 : 603 - 607
  • [10] Performance evaluation of a solar adsorption chiller under different climatic conditions
    Alahmer, Ali
    Wang, Xiaolin
    Al-Rbaihat, Raed
    Alam, K. C. Amanul
    Saha, B. B.
    APPLIED ENERGY, 2016, 175 : 293 - 304